24
2nd Cycle and after with pump drain
IMPORTANT
Freeze cycle time is limited to 60 minutes even
if float switch does not open.
1. Float switch opens and signals to complete
freeze cycle.
Drain timer starts counting.
2. Drain timer stops counting.
Pump drain is completed
3. Thermistor reads 48°F.
Defrost timer starts
counting.
IMPORTANT
Water valve
opening is limited to 6
minutes.
4. Defrost timer stops counting.
Defrost cycle is completed and freeze cycle
starts.
IMPORTANT
1. Board never accepts defrost completion
signal within the first 2 minutes in defrost
cycle.
2. Defrost cycle time is limited to 20 minutes
even if defrost timer does not stop counting.
&
5. After first 5 minutes in freeze cycle, cycle can
complete when float switch circuit opens.
If bin control signals that bin is full within first
5 minutes in freeze cycle, the machine will shut
down.
IMPORTANT
1. Board never accepts freeze completion signal
from float switch within first 5 minutes in freeze
cycle.
2. If bin control signals that bin is full after first
5 minutes in freeze cycle, board will allow
machine to complete freeze cycle and following
harvest cycle.