13
switch 1)." When the pump-out/drain selector is set to pump-out, PM takes water from
the tank and forces it through DV and down the drain. When the pump-out/drain selector
is set to drain, water drains by gravity through DV.
CAUTION! Do not adjust S2 dip
switch 1 out of the factory default position on this model. This dip switch must be
left in the factory default position or this unit will not operate correctly.
The water
tank drains for a maximum of 5 minutes or until F/S opens. DV and PM (if applicable)
then de-energize. When BC closes again calling for ice, the unit starts at the 1-minute fill
cycle. There is a 90-second minimum off time before the icemaker can restart.
Legend:
BC
–bin control;
CB
–control board;
Comp
–compressor;
DV
–drain valve;
FM
–fan
motor;
FMR
–fan motor-remote;
F/S
–float switch;
HGV
–hot gas valve;
LLV
–liquid
line valve;
PM
– pump motor;
WV
–inlet water valve