PROBLEM
POSSIBLE CAUSE
REMEDY
l) Controller Board
1. Defective
1. See “II.2[e] CHECKING
CONTROLLER BOARD.”
m) Interlock Switch
1. “OFF” position.
1. Move to “ON” position.
(Cleaning Valve)
2. Bad contacts.
2. Check for continuity and
replace.
[2] Water
a) Float switch
1. Connector disconnected.
1. Place in position.
continues to
2. Leads opened or defective
2. Check and replace.
be supplied,
switch.
and the ice-
3. Float does not move freely.
3. Clean or replace.
maker will not
b) Controller Board
1. Defective.
1. Replace.
start.
[3] Compressor
a) Wash Switch
1. “WASH” position.
1. Move to “ICE” position.
will not start
2. Bad contacts.
2. Check and replace.
or operates
b) High Pressure
1. Dirty Air Filter or
1. Clean.
intermittently.
Control
Condenser.
2. Ambient or condenser
2. Reduce ambient temp.
water temp. too warm.
3. Refrigerant overcharged.
3. Recharge.
4. Condenser water pressure
4. Check and get
too low or off. [Water-
recommended pressure.
cooled model only].
5. Fan not operating. [Except
5. See chart 1 - [6].
water-cooled model].
6. Refrigerant line or
6. Clean and replace Drier.
components plugged.
c) Water Regulator
1. Set too high.
1. Adjust lower.
d) Overload Protector
1. Bad contacts.
1. Check for continuity and
replace.
2. Voltage too low.
2. Increase voltage.
3. Refrigerant overcharged or
3. Recharge.
undercharged.
4. Line Valve continues to
4. Check Line Valve's
close in freeze cycle and
operation in freeze cycle
Overload Protector
and replace.
operates.
e) Starter
1. Bad contacts.
1. Check and replace.
2. Coil winding opened.
2. Replace.
f) Start Capacitor or
1. Defective.
1. Replace.
Run Capacitor
g) Magnetic Contactor
1. Bad contacts.
1. Check for continuity and
replace.
2. Coil winding opened.
2. Replace.
h) Compressor
1. Wiring to Compressor.
1. Check for loose
connection or open, and
replace.
2. Defective.
2. Replace.
3. Protector tripped.
3. Reduce temperature.
i) Controller board
1. Defective.
1. See “II.2. [e] CHECKING
CONTROLLER BOARD.”
j) Discharge Temp.
1. Refrigerant
1. Recharge.
Switch
undercharged.
2. Cooling Fan not operating.
2. See chart 1 - [6]
Summary of Contents for KM-900MAH
Page 1: ...6 59 0 18 668 7 2 2 5 2 2 3 4 5 2 5HOLDELOLW LV D EHDXWLIXO WKLQJ70 5 9 6 180 5 73105...
Page 10: ...10 5 CONDENSING UNIT URC 12F...
Page 13: ...13 b KM 900MWH Models with Thermostat Models with Mechanical Bin Control...
Page 14: ...14 c KM 900MRH Models with Thermostat Models with Mechanical Bin Control...
Page 15: ...15 d KM 900MRH3 Models with Thermostat Models with Mechanical Bin Control...
Page 30: ...30 III TECHNICAL INFORMATION 1 WATER CIRCUIT AND REFRIGERANT CIRCUIT a KM 900MAH...
Page 31: ...31 b KM 900MWH...
Page 32: ...32 c KM 900MRH and KM 900MRH3...
Page 41: ...41 3 TIMING CHART...
Page 42: ...42...