![Horstmann ComPass B Instructions For Use Manual Download Page 19](http://html1.mh-extra.com/html/horstmann/compass-b/compass-b_instructions-for-use-manual_2164205019.webp)
Instructions for Use
ComPass B 4023841-001
External input
for connection of a potential-free contact,
configurable function
Digital outputs
4 relays
NC/NO
Permanent contact/momentary contact (1 s)
Contact capacity: 230 V AC/1 A/62.5 VA max.
220 V DC/1 A/60 W max.
Breakdown voltage: 1.5 kV, 1 minute
Current transformers (CT)
3 pcs. single-phase CT (L1, L2, L3)
alternatively: 2 pcs. single-phase CT +
1 pc. summation CT
Environmental Conditions
Operating temperature
-30° C... +70° C
19
Dipl.-Ing. H. Horstmann GmbH