Horstmann ComPass B Instructions For Use Manual Download Page 12

Instructions for Use

ComPass B 4023841-001

Test mode

3.5. 

The ComPass B features a built-in test mode. This mode can be activated via the

front panel control

• 

RS485/MODBUS interface

• 

external input contact

• 

During test mode, the ComPass B controls both its electronics and its software. The yellow light of 

the multicolour LED starts flashing to indicate the test mode.
If an error is detected on the device, the multicolour LED flashes yellow, either in a double or triple 

flash mode which depends on the type of error. Further information on the error can be gathered 

either from the front panel control or via the RS485/MODBUS interface (see section 3.1.5).

Installation

4. 

Safety instructions

4.1. 

Make sure that the ComPass B is only used for the purpose described in the present opera-

• 

ting manual.

When installing the device, the “five safety rules” as defined by the DIN VDE 0105 standard 

• 

and the accident prevention rules as per BGV A3 “Electrical Installations and Equipment” 

must be complied with.
Make sure that current transformers are mounted and dismounted and cabling work is exe-

• 

cuted only in a de-energized condition on the disconnected and earthed medium-voltage 

switchgear.
If current transformers remain in the switchgear without being connected to the indicator, 

• 

the leads must be applied to suitable insulated terminals ensuring that such leads are short-

circuited.

Plug-in housing for panel mount

4.2. 

Insert the plug-in housing into a prepared DIN size cut-out of 92

+0.8

 mm x 45

+0.6

 mm on the front of 

the switchgear panel and lock it by means of 4 integrated spring clips with self-retaining feature. 

Provide a minimum installation depth of 95 mm with connected leads. 
If you need to dismount the device, remove the front frame and front plate pushing the retainer 

spring clips towards the centre of the device (Order No. of Disassembly Clip: 040401-0008).

Installation of current transformers (CTs)

4.3. 

General

4.3.1. 

The CTs are split-core types (allow also for subsequent mounting) and are mounted on insu-

• 

lated conductors.
Ensure shielding of each conductor is repassed through the yoke of the CT to compensate 

• 

any shield currents (see illustration 18). On connecting the wires to the ComPass B mind 

the allocation of the cable lead colours (brown/blue) to the terminals (marking br/bl) and the 

respective L1, L2, L3 phases. 

G

Make sure current transformers are mounted only on fully insulated i. e. touch-safe conduc-

tors.

12

Dipl.-Ing. H. Horstmann GmbH

Summary of Contents for ComPass B

Page 1: ...4023841 001 June 2011 Instructions for Use ComPass B 100104 0426 Translation of the German version Dipl Ing H Horstmann GmbH Humboldtstra e 2 42579 Heiligenhaus www horstmanngmbh com...

Page 2: ...2 0 Operator control 1 3 3 0 Front panel 1 3 3 1 0 RS485 MODBUS interface 1 3 3 2 1 Digital inputs outputs 1 3 3 3 1 Power Supply 1 3 4 1 Test mode 1 3 5 2 Installation 1 4 2 Safty instructions 1 4 1...

Page 3: ...the instrument is only used for the purpose for which it has been designed as described in the present operating manual Abbreviations Abbreviations Meaning IE Earth fault I Short circuit IB Operating...

Page 4: ...ss B includes 1 display unit in a plug in housing for panel mount 3 single phase current transformers alternatively 2 single phase current transformers and 1 summation current transformer Integrated v...

Page 5: ...E 0682 Part 415 standard IEC 61243 5 for capacitive voltage detecting systems Besides their main function WEGA 1 2 C and WEGA 2 2 C respectively can provide the tapped capacitive voltage to the ComPas...

Page 6: ...hematic illustration of a medium voltage network The ComPass B is or can be installed in any switchgear unit The instrument measures permanently the phase voltages and currents taking these values as...

Page 7: ...ected phases to de rive the direction of a fault therefrom If the impedance angle ranges from 45 to 135 the Com Pass B determines a forward fault B direction Earth fault in resonant earthed isolated s...

Page 8: ...se voltages are extrapolated in time in order to obtain information on the phase relation Inrush current suppression 3 1 4 The ComPass B uses an inrush current suppression to avoid unintended tripping...

Page 9: ...figured for permanent contact it will remain engaged as long as ComPass B is indicating the fault If a second fault occurs it will disengage for 1s and then re engage RS485 MODBUS interface ComPass B...

Page 10: ...ntrol of ComPass B Figure 16 OLED display 4x21 alphanumerical characters Multilingual plain text menus German English Dutch Portuguese Multicolour LED Green Yellow Red Rocker switch 4 directions Activ...

Page 11: ...e is used for remote control remote readout and remote parameteri zing of ComPass B The ComPass B uses a 2 wire interface according to the RS485 standard with no line termination in the ComPass B The...

Page 12: ...the disconnected and earthed medium voltage switchgear If current transformers remain in the switchgear without being connected to the indicator the leads must be applied to suitable insulated termina...

Page 13: ...sformers 4 3 2 Install each CT as to ensure that the arrow and the B show towards the bottom of the switchgear Direction indication B Figure 19 Installation of summation current transformers 4 3 3 Wra...

Page 14: ...nal strips 4 4 2 Circuit diagram on top side of the instrument Figure 20 CT Digital I O Supply Voltage Terminal No Designation Assignment Direction 1 I1 br CT Phase 1 brown Input 2 I1 bl CT Phase 1 bl...

Page 15: ...hase 1 Input 3 U2 Voltage Phase 2 Input 4 U3 Voltage Phase 3 Input Terminal assignment of MV interface Table 3 RS485 MODBUS interface Terminal No Designation Assignment Direction 1 COM Common Input Ou...

Page 16: ...bration is required after ComPass B has been installed in the switch gear and the switch gear has been energised Below voltage calibration is carried out using the example of a 11 kV network Step 2 Vo...

Page 17: ...ch to the right If the following security prompt appears V AutoCal Select Yes Note Presence of calibration voltage of 11 kV 6 35 kV is requi red Indication on the display during the calibration proces...

Page 18: ...ay External supply 24 230 V AC DC 10 Power consumption 1 W DC supply 1 5 VA AC supply MV network parameters Rated voltage 1 36 kV Frequency 50 Hz 60 Hz Load current single phase 0 630 A Short circuit...

Page 19: ...lays NC NO Permanent contact momentary contact 1 s Contact capacity 230 V AC 1 A 62 5 VA max 220 V DC 1 A 60 W max Breakdown voltage 1 5 kV 1 minute Current transformers CT 3 pcs single phase CT L1 L2...

Page 20: ...Nominal voltage 1 36 kV 10 0 kV Neutral earthing low impedance earthed temporary low impedance earthes isolated earthed Resonant earthed Low ohmic KNOSPE Isolated Resonant earthed Low ohmic Relais Eac...

Page 21: ...ervoltage On Off Adjustable for each relay V Undervoltage On Off Adjustable for each relay Test Relay responds to test mode On Off Adjustable for each relay DevErr Relay responds to device error On Of...

Page 22: ...direction backwards Common message for all phases L1 L2 L3 Test mode Type NO Mode Momentary I Off I A On I B Off IE Off IE A On IE B Off L1 On L2 On L3 On V Off V Off Test On DevErr Off MODBUS Parity...

Page 23: ...200 120 V Threshold for low voltage detection 0 100 80 V V Conf Choice of voltages for the V V detection VLE phase to ground VLL phase to pha se VLL VNE Threshold for the residual voltage for earth f...

Page 24: ...ents Settings tI ms I A IE L1 L2 L3 E Status OK L1 L2 L3 E Status uncalibrated L1 L2 L3 E Status Battery low L1 L2 L3 E Status Conf Error L1 L2 L3 E Status Device Error Date event no time fault type f...

Page 25: ...Save 496025 00x Cancel Save Cancel Save SUM CT SUM CT Up Down 496023 00x Cancel Save CT 1 Pol CT 1 Pol Up Down Normal Invers Cancel Save CT 2 Pol CT 2 Pol Up Down Normal Invers Cancel Save CT 3 Pol C...

Page 26: ...ff Up Down 1 65535 Cancel Save D VL1 Up Down 50 0 50 0 Cancel Save D VL2 Up Down 50 0 50 0 Cancel Save D VL3 Up Down 50 0 50 0 Cancel Save Back Start Calibration V AutoCal No Yes Back Relay1 Type Type...

Page 27: ...arity Parity Up Down On Off Cancel Save Mode Mode Up Down Even Odd Cancel Save Stop Bits Stop Bits Up Down 1 2 Cancel Save Address Address Up Down 1 247 Cancel Save Idle Time Idle Time Up Down 0 10ms...

Page 28: ...ff Up Down 0 60000 ms Cancel Save IDet IDet Up Down 1 630 A Cancel Save tIReset tIReset Up Down 0 60000 ms Cancel Save VDet VDet Up Down 0 100 Cancel Save tVReset tVReset Up Down 0 60000 ms Cancel Sav...

Page 29: ...History Delete History No Yes Reset battery Reset battery No Yes Back Test Selftest active Device Reset Test activated Test activated Test activated Test activated Activate Relay1 Test activated Back...

Reviews: