![HORNER XL7 OCS User Manual Download Page 124](http://html.mh-extra.com/html/horner/xl7-ocs/xl7-ocs_user-manual_2163915124.webp)
MAN0974-09-EN_XL7_UserManual
March 4
th
, 2019
Page 124 | 185
Table 14.3
–
%SR Registers
Register
Name
Description
Min Val
Max Val
%SR178-179
Removable Media
Indicates the total card capacity in K bytes.
0
2
31
%SR180
Reserved
-
-
-
%SR181
ALM_UNACK
Unacknowledged Alarm (high bit indicates
what group #)
%SR182
ALM_ACT
Active Alarm (high bit indicates what group #)
%SR183
SYS_BEEP
System Beep Enable (0=disabled; 1=enabled)
0
1
%SR184
USER_BEEP
Software configurable (0=OFF; 1=ON)
0
1
%SR185
SCR_SAVER
Screen Saver Enabled (0=disabled; 1=enabled)
0
1
%SR186
SCR_SA_TM
Screen Saver Time in minutes (delay)
5
1200
%SR187
NET_USE
Average Net Usage of all units on the CAN
network
0
1000
%SR188
NET_MIN
Minimum Net Usage of all units on the CAN
network
0
1000
%SR189
NET_MAX
Maximum Net Usage of all units on the CAN
network
0
1000
%SR190
NT_TX_AVG
Average Net Usage of this unit
0
1000
%SR191
NT_TX_MIN
Minimum Net Usage of this unit
0
1000
%SR192
NT_TX_MAX
Maximum Net Usage of this unit
0
1000
%SR193
ONLINE_CHG
Online Change
%SR193.1
TRUE if there are two ladder programs stored
in target Flash.
%SR193.2
TRUE to tell the target to switch the currently
executing program; target clears bit when
switch is complete.
%SR193.3
TRUE if currently executing program is a
temporary test program (that was loaded via
on-line programming,)
%SR193.4
TRUE during last scan of a ladder program
being switched from
%SR193.5
TRUE during first scan of a ladder program
being switched to
%SR193.6
TRUE to tell the target to revert back to the
program in Flash and delete all ladder
programs in RAM; target clears bit when
switch is complete.
%SR193.9
TRUE if there is error in temporary program
%SR194
CPU Frequency
%SR195
Max Die Temperature (115 is max)
%SR196
Charging State (0=Waiting, 1=Normal
Charging, >1=Special Condition)
%SR197
Charging Current Max mA
%SR198
Battery Voltage is mV
%SR209.3
WebMI Server Status. Bit 3 is ON if server
running.
%SR209.4
WebMI User Logged in Status. Bit 4 is ON if 1
or more users logged in.
%SR209.8-
209.16
Number of Users. Shows in upper byte in
decimal format.
%SR210
(R/W)
Time Zone: set in hours + / - UTC.
%SR211
(R/W)
Daylight Saving: YES = 1
Daylight Saving: NO = 0
(If daylight saving is enabled, one
hour will be added to the local time).
%SR212 (R)
UTC
–
Seconds