background image

PAGE 2 

08 June 2005 

MAN0509-03 

001FOX007

IN

FIBER I/O

TO REMOTE BASE

OUT

 

3 INSTALLATION 

 
Refer to the hardware manual of the controller you are using for more information.  (See the 

Additional 

References

 section in this document.)  

 

3.1 Connectors 

 
The FOX100 must be placed in the first slot of the controller.  For 

Ethernet

 capability, the SmartStack 

Ethernet

 

Module (ETN1xx) is plugged into the FOX100.  (In this case, the ETN needs to occupy the 

second slot of the controller.)  
 

Note:

  The FOX100 has a 10-pin connector, which is reserved for factory use only. 

 
 
 
 
 

Figure 1 – FOX100 Connectors 

 
 
 
 
 

Figure 2 – FOX100 Connectors 

 

3.2 

Fiber Optic Cable Installation 

 
Important considerations for installing the FOX include the following guidelines:    
 
a. 

To ensure reliable communication between the FOX base and OCS/RCS module, high quality 
cables need to be installed.  See Table 2 for fiber cable part numbers.  

b. 

The maximum fiber optic cable distance is 10 meters between drops. 

c. 

During installment of the fiber optic cable, all direction changes need to adhere to a 

Minimum 

Bend Radius

 of one inch (25.44mm).  

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Figure 3 – Fiber Optic Cable Bend Radius

 

 

FI

B

E

R

OP

T

IC

MO

D

U

L

E

IN

OUT

FIBER I/O

TO REMOTE BASE

001FOX010

1.00” (25.4mm) Min.

Bend Radius 

001FOX011

2.00” (50.8mm)

Min. Diameter 

Summary of Contents for HE800FOX100

Page 1: ...m number of stacks total number of hubs and bases 5 Maximum number of cable drops to any specific hub or base 3 See Section Five for Example Setups Maximum length of Fiber Optic cable 10 Meters per Drop Base ID Each Base or Hub must have a unique Base ID Expansion I O EIAJ RC 5720 Plastic Fiber TX RX 10m per drop max host OCS or hub to base Type of Fiber Optic Cable EIAJ RC 5720 RC Primary Power 9...

Page 2: ...served for factory use only Figure 1 FOX100 Connectors Figure 2 FOX100 Connectors 3 2 Fiber Optic Cable Installation Important considerations for installing the FOX include the following guidelines a To ensure reliable communication between the FOX base and OCS RCS module high quality cables need to be installed See Table 2 for fiber cable part numbers b The maximum fiber optic cable distance is 1...

Page 3: ...IBER OPTIC MODULE FIBER OK 001FOX009 MODULE OK 4 LEDs Figure 4 FOX 100 LEDs Table 2 LEDs FOX100 LED Meaning Module OK ON if firmware is loaded and operating properly Fiber OK ON indicates a Fiber carrier is being received from first base hub ...

Page 4: ... FOX100 110 is used with a FOX104 or FOX404 they extend a high speed OCS RCS backplane enabling SmartStack I O Modules to be mounted several meters from the OCS RCS They also significantly increase the number of SmartStack I O modules supported by one OCS RCS Figure 5 OCS RCS to FOX404 Single Hub via FOX100 FOX110 001OCS010 R2 4 3 2 1 HOST Color Touch OCS Or Or Using FOX100 RCS250 Using FOX100 OCS...

Page 5: ...gure 6 OCS RCS to FOX One Hub FOX404 and Multiple Bases FOX104 via FOX100 HOST 4 3 2 1 HOST HOST 001OCS012 R2 HOST Color Touch OCS Or Or Using FOX100 RCS250 Using FOX100 OCS110 OCS210 Graphic OCS OCS250 HUB FOX404 FOX104 FOX104 FOX104 ...

Page 6: ... RCS to FOX Multiple Hubs FOX404 and Bases FOX104 via FOX100 HOST HOST 4 3 2 1 HOST HOST 001OCS011 R2 HOST 4 3 2 1 Color Touch OCS Or Or Using FOX100 RCS250 Using FOX100 OCS110 OCS210 Graphic OCS OCS250 HUB FOX404 HUB FOX404 FOX104 FOX104 FOX104 ...

Page 7: ...ons to power circuits Ensure hands shoes and floor are dry before making any connection to a power line Make sure the unit is turned OFF before making connection to terminals Make sure all circuits are de energized before making connections Before each use inspect all cables for breaks or cracks in the insulation Replace immediately if defective Warning Consult user documentation Warning Electrica...

Page 8: ...OCS OCX e g OCS1XX 2XX Graphic OCS250 Remote Control Station Hardware RCS except RCS116 RCX e g RCS210 RCS250 MAN0227 Color Touch OCS Hardware e g OCS300 OCS301 OCS350 OCS351 e g OCS451 OCS551 OCS651 MAN0465 OCS LX Series Hardware e g LX280 LX300 RCS116 MAN0755 MiniOCS MiniRCS MiniOCX MiniRCX Hardware e g HE500OCSxxx MAN0305 Other Useful References Cscape Programming and Reference MAN0313 DeviceNe...

Reviews: