Once the panel design has been completed using the criteria and suggestions in the following
sections, use the following steps to panel mount the EXL6 OCS.
1.
Remove all connectors from the EXL6 OCS unit.
2.
Make sure the gasket is installed on the EXL6 OCS and is free from dust and debris.
Check that the corners of the gasket are secure.
3.
Pass the unit through the panel.
4.
Insert each of the ten (10) mounting clips into the slots in the EXL6 OCS case. One clip
should be installed on each corner. Lightly tighten each screw so the clip is held in
place.
5.
Tighten the screws on the clips such that the gasket is compressed against the panel.
Recommended torque is 4-8 in-lbs (0.45-0.90 N-m).
3.3 Mounting Orientation
3.3.1 EXL6 OCS Mounting Clip
Figure 3.2
–
EXL6 OCS with Mounting Clips
001XLQX007