MAN1029-10-EN_EXL10_XL10P_UM
J u l y 6 , 2 0 2 2
P a g e 78 | 195
8.3
Model and I/O Overview
Table 8.1
–
I/O and Model Overview
EXL10/XL10
PRIME
Models
DC In DC Out Relays HS In HS Out mA/V In
mA/V
RTD/Tc
mA/V Out
Model 0
Model 2
12
6
4
4
Model 3
12
12
4
2
2
Model 4
24
16
4
2
2
Model 5
12
12
4
2
2
2
Model 6
12
12
4
2
6*
6*
4*
Table 8.1 shows the different types of I/O included with the various EXL10/XL10 PRIME OCS models.
Specific specifications, jumper settings and wiring diagrams can be found on the data sheets attached at
the end of the manual. Descriptions and applications of the different type of I/O can be found below.
*up to 6mA/V In, mA/V RTD/TC, and 4mA/V Out.
8.4
Solid-State Digital Outputs
Solid-state digital outputs are generally used to activate lamps, low voltage solenoids, relays and other low
voltage and low current devices.
NOTE
:
The digital outputs used on the EXL10/XL10 PRIME
OCS are “sourcing” outputs. This means the
output applies a positive voltage to the output pin when turned ON. When turned off, the output applies
approximately zero volts with respect to the I/O ground.
Figure 8.4
–
Typical Output Wiring
Q14
Q15
V+
0V
LOAD
LOAD
10 - 30VDC
Q16
LOAD
J2
J4