T
ECHNICAL
D
ATA
4465AC/4475AC/4800AC/6870AC/6875AC Additional Technical Manual - V01.03
13 / 14
hopf
Elektronik GmbH
Nottebohmstr. 41
• D-58511 Lüdenscheid • Tel.: +49 (0)2351 9386-86 • Fax: +49 (0)2351 9386-93 • Internet: http://www.hopf.com • E-Mail: [email protected]
4
Technical Data
4.1
General
The technical data in this document are only valid in connection with the technical manual of
the according module.
All specified data in this document replaces those of the appropriate technical manual of the
module.
Regarding all other articles the technical manual of the module is the relevant document.
4.2
Power Supply
hopf
DIN Rail Module
General Data
Installation position
On horizontal 35mm DIN rail per
DIN EN 50 022
Protection Type of the housing
IP40
Protection Class
I, with PE connection
MTBF
> 300,000h
Type of housing
Aluminium, closed
Dimensions (W x H x D) + DIN Rail
100 x 105 x 130mm (Type 2)
Weight
approx. 1.05kg
Climatic Data
Environmental temperature
Operation
0° C ... +55° C
Storage
-20° C ... +75° C
Humidity
Up to 90% at +25° C, no condensation
CE compliant to EMC Directive 89/336/EEC and Low Voltage Directive 73/23/EEC
Safety - Low Voltage Directive
DIN EN 60950-1:2001
+ A11 + Corrigendum
EN 61000-6-4:
EMC (Electro-Magnetic Compatibility)
Stability
EN 610000-4-2 /-3/-4/-5/-6/-11
EN 61000-6-2:
EN 61000 -3 -2 /-3
Interference Voltage
EN 55022
EN 55022 Class B
Interference Voltage
EN 55022
EN 55022 Class B
4.3
Power Supply
Internal Power Supply
(with wide input range)
hopf
type:
AC-M05-D
/
AC-M10-D
Power consumption
AC-M05-D
max. 6 VA
Power consumption
AC-M10-D
max. 15 VA