CHECKOUT

In this section, make sure the ventilation system is operating 

correctly. 

1.

On thermostat, set Fan switch to Auto and System 

switch to Off.

2.

Set any remote switches throughout the house in the 

Off position.

3.

On the W8150, set the control switch to Off (remote 

only). 

4.

Press Test button for two seconds to enter test mode:

• A light on the control begins flashing.

• The HVAC system fan comes on.

• The damper moves to the Open position.

5.

Press the Test button again to exit test mode:

• No lights on the control are on.

• The HVAC system fan turns off.

• The damper returns to the closed position.

6.

Return the thermostat, ventilation control, and remote 

switches to the original settings.

7.

Refer to Troubleshooting section, if needed.

TIP:

• W8150 Ventilation Control automatically exits test mode 

after three minutes.

TROUBLESHOOTING

Problem

Possible cause 

What to do

Flashing red light 

during test mode 

(The current settings 

do not meet the 

selected ventilation 

requirement)

Not enough airflow

Measure airflow and check dial setting.

See Problem: Not enough airflow.

Ventilation on-time limit 

setting

• If the device is set to 60%:

 Set the ventilation control to 100% maximum 

on time. This allows the HVAC fan to run up to 100% of the time. It may be 

preferable to increase airflow.

• If the device is set to 100%:

 There is not enough airflow through the 

fresh air duct. 

Ventilation continues to occur according to the settings but chosen 

standard may not be met.

Flashing red light 

during normal 

operation

Low voltage

Check the voltage from the transformer for at least 20 Vac. If voltage is 

OK, replace W8150 Control. If voltage is not OK, disconnect damper and 

remote switch connections and check again. If voltage does not return to 

at least 20 Vac, replace transformer.

No light on ventilation 

control when switch 

set to:

On 

Override Off/

Remote Only and a 

remote switch is on.

No power to control

Verify 24 volt input to R and C terminals on ventilation control.

Check wiring connections per appropriate system diagram and replace 

transformer, if necessary.

Device malfunction

Cycle power off to control for ten seconds and recheck. If control does not 

recover, replace ventilation control.

HVAC fan does not 

come on after pressing 

Test button. 

Wiring

Check wiring connections per appropriate system diagram.

HVAC system does not 

have power

Restore power to the HVAC system.

Summary of Contents for Y8150

Page 1: ...luding ASHRAE 62 2 2010 standard Ventilation and Acceptable Indoor Air Quality in Low Rise Residential Buildings Microcontroller optimizes the air delivery schedule to make efficient use of normal HVAC run times Easy to use input dials allow customized ventilation for each installation Test mode that includes immediate feedback to installer to confirm that air delivery requirements of selected ven...

Page 2: ...6 24 Vac 12 VA 60 Hz Operation Power open spring closed Diameter 6 in Transformer AT120 Input 120 Vac Output 27 Vac open circuit 24 Vac full load at 20 VA Mounting Foot mounted Temperature 20 F to 160 F 29 C to 71 C Humidity 5 to 90 RH noncondensing Input Setting Ranges Bedrooms 2 5 Area 1000 4600 sq ft Vent Airflow 40 160 cfm Composite Setting Resolution 12 of ASHRAE 62 2 2010 recommended ventila...

Page 3: ...entilation continuously Off Remote Only W8150 supplies ventilation only when there is a remote call 8 Light Green Indicates device is powered and operating normally Used in Test Mode to signal if dial settings meet chosen standard 9 Light Red Indicates the device is not operating normally Used in Test Mode to signal if dial settings do not meet chosen standard 10 DIP1 Ventilation limit Choose betw...

Page 4: ...inals 24 Vac dry contacts allow W8150 to control an auxiliary device such as exhaust fan or HRV ERV with a call for ventilation 18 DAMPER Damper two terminals 24 Vac powered contacts control fresh air damper 19 XFMR C 24 Vac ventilation control common Supplies power to W8150 and damper from transformer provided 20 XFMR R 24 Vac ventilation control power Supplies power to W8150 and damper from tran...

Page 5: ...ut and move the upper lever until the desired position is reached Tighten the wing nut Keep the lower lever in the position shown Wiring the control CAUTION Electrical Hazard Can cause personal injury or equipment damage Disconnect power to all systems before beginning installation 1 Wire the control See wiring diagrams in Fig 1 10 as listed below All wiring must comply with local codes ordinances...

Page 6: ... the control to meet the ventilation requirements for the home Ventilation Standard Building codes are different everywhere The W8150 Ventilation Control can be configured to operate based on ASHRAE 62 2 ASHRAE 62 1999 TIP Clear understanding of local codes and practices is required to make sure the ventilation system is installed and configured correctly Generally ASHRAE 62 2 control method is re...

Page 7: ...area sq ft dial to the nearest value For airflow set airflow cfm dial to the nearest value Vaulted ceilings do not need to be considered when setting this control For homes with multiple systems Honeywell recommends a ventilation control and fresh air intake for each system Measure ventilation airflow for each system independently Refer to Multi system Setup Example for further details Customizing...

Page 8: ...blem Not enough airflow Ventilation on time limit setting If the device is set to 60 Set the ventilation control to 100 maximum on time This allows the HVAC fan to run up to 100 of the time It may be preferable to increase airflow If the device is set to 100 There is not enough airflow through the fresh air duct Ventilation continues to occur according to the settings but chosen standard may not b...

Page 9: ...ed to actuator Damper actuator motor failure or mechanical failure Manually open damper and verify free movement damper should return to closed position when no power is applied If damper moves freely but does not operate when 24 volts is applied replace damper actuator If damper does not move freely replace fresh air damper Cooling compressor comes on when there is no cooling call from the thermo...

Page 10: ...mp without emergency heat Wake Room System Fan Heat Auto AM DST Tue R C W Y G R RC W Y G M19994A GF RC CC CH W GT W8150A HVAC Wake Room System Fan Heat Auto AM DST Tue W R HVAC COOLING HEATING R C C Y G R RC W Y G M19995A GF RC CC CH W GT NOTE REMOVE FACTORY INSTALLED JUMPER BETWEEN CC AND CH ON W8150 W8150A Wake Room System Fan Heat Auto AM DST Tue W1 C R W2 Y1 Y2 G W1 C RC R W2 Y1 Y2 G M19996 GF...

Page 11: ...TTON ON THE PC8900 THEN SERVES AS A REMOTE AND THE W8150 CONTROLS BACKGROUND VENTILATION Ventilation Control Ventilation Control Service Auto Continuous Off Remote Only M22000 EARD 6 FAN TIMER REMOTE AUX DAMPER C R XFMR AT120 W8150A Ventilation Control Ventilation Control Service Auto Continuous Off Remote Only M22001 HR150 ER150 EARD DAMPER NOT USED WITH HRV ERV REMOTE AUX DAMPER C R XFMR RED BLA...

Page 12: ...red at 127 cfm System 2 serves 1800 sq ft four bedrooms fresh air intake measured at 98 cfm Set W8150 for System 1 3100 sq ft four bedrooms 130 cfm Set W8150 for System 2 1900 sq ft two bedrooms 100 cfm CONVERSION TABLE Wake Room System Fan Heat Auto AM DST Tue W1 C R W2 Y1 Y2 G W1 C RC R W2 Y1 Y2 G M22021A GF RC CC CH W GT HVAC W8150A HE440 FAN R8222 BLACK BLUE BLUE RED Area Airflow sq ft sq m cf...

Reviews: