![Honeywell XLS140 Installation Manual Download Page 53](http://html.mh-extra.com/html/honeywell/xls140/xls140_installation-manual_150769053.webp)
XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005
53
Installing Remote Printers and/or CRT
Installation
Setting up the Keltron Printer
Set up a Keltron printer as follows:
1. The printer communicates using the following protocol:
• Baud Rate: 9600 • Parity: Even • Data bits: 7
2. Set the printer DIP switches SP1 and SP2 according to settings in Table 3.6.
Table 3.6 Keltron DIP Switch Settings
3.14.4 Installing and Configuring a CRT-2
A CRT-2 can only be used in a non-networked application when used with the XLS140. For further
details on setting up the CRT-2, refer to the
XLS140 Operations Manual.
Connect a CRT-2 to the Control Panel as follows:
1. Connect the three (3) open leads of the custom cable to the TB15 terminal block on the control
panel as shown in Figure 3.28.
2. Plug the DB-25 connector end of the custom cable into the EIA-232 port of the CRT-2. Tighten
securely.
3. Set parameters as discussed in Table 3.28.
TB14
TB15
PRINTER
TX RX REF
PC/CRT
TX RX REF
24V
24V
NONRST
RESET
+ – +
–
TB
7
nfs6
40
-ke
ltcon
n.cd
r
DB-25 connector
on Keltron Printer
(female socket
shown)
Keltron printer
24 VDC
connections
(14 AWG,
2.08 mm
2
)
Control Panel
Terminate one end of
shield at backbox
Figure 3.27 Keltron Printer Connections
SP1
On
Off
1
X
2
X
3
X
4
X
5
X
6
X
7
X
8
X
SP2
On
Off
1
X
2
X
3
X
4
X
5
X
6
X
7
X
8
X
Summary of Contents for XLS140
Page 8: ...8 XLS140 Installation Manual Form Number 95 7673 3 P N 51927 C 12 06 2005 ...
Page 57: ...XLS140 Installation Manual Form Number 95 7673 3 P N 51927 C 12 06 2005 57 Notes ...
Page 68: ...68 XLS140 Installation Manual Form Number 95 7673 3 P N 51927 C 12 06 2005 Notes ...
Page 87: ...XLS140 Installation Manual Form Number 95 7673 3 P N 51927 C 12 06 2005 87 ...