![Honeywell XLS140 Installation Manual Download Page 13](http://html.mh-extra.com/html/honeywell/xls140/xls140_installation-manual_150769013.webp)
XLS140 Installation Manual Form Number 95-7673-3 P/N 51927:C 12/06/2005
13
Section 2: System Overview
2.1 System Description
The XLS140 and XLS140E control panels are modular, intelligent fire alarm control panels
(FACPs) with an extensive list of powerful features. The control panel integrates a central
processing unit (CPU), a 6 amp power supply, and a battery charger. This is combined with a
mounting chassis and cabinet to create a complete fire alarm control system. The panel supports
FlashScan® protocol and has network capabilities. A single SLC loop is supported with the basic
equipment package; a second SLC loop can be added by attaching an optional loop expander
module (LEM-320).
Modular devices mount to the chassis to provide additional output circuits, including voice and
telephone modules to form a complete voice evacuation system. Five cabinet options for enclosing
system components are available.
The control panel has the capacity for installing up to 636 addressable points; 159 detectors and
159 monitor/control modules per SLC (Signaling Line Circuit).
2.1.1 Standard Features
•
Uses early warning fire detection and the FlashScan® or Classic Loop Interface Protocol
(CLIP) families of detectors and modules
•
Four standard Notification Appliance Circuits (NAC), Class A or B
•
Alarm, Trouble, Supervisory and Security relays
•
Support for 32 annunciator addresses, with 10 special annunciator groups
•
Supports Style 4, Style 6, Style 7 SLC loops
•
Connections to easily mount an expander board to add a second SLC loop
•
Releasing service using on-board NACs or XLS-CM-N/XLS-CM-N/TC810N1013 modules
•
Logic Equations
•
Display scroll selection
•
Alarm verification supervisory indication (NYC)
•
Supervisory duct detectors
•
Supports Advanced Warning Addressable Combustion Sensing (AWACS) algorithms
•
Network operation
•
Battery charger supports 12-55 amp hour sealed lead-acid batteries
•
EIA-485 connections for wiring ACS annunciators (including LDM custom graphic
annunciators), TM-4 transmitter
•
EIA-232 connections for printer, CRT, printer/CRT, or network operation
•
Autoprogram feature for faster programming of new devices
•
The control panel provides 6.0 amps of usable output power in an alarm condition; it provides
3.0 amps of usable output power in normal or continuous operating conditions
•
Diagnostic LEDs and switches
•
Ground fault detection
•
Battery and battery-charger supervision, voltage-monitoring, and current-monitoring
•
Panel circuit modules support up to 64 circuits
•
Programmable for strobe synchronization
2.1.2 Options
Refer to Section 2.2 “System Components” for descriptions of the various optional modules.
Summary of Contents for XLS140
Page 8: ...8 XLS140 Installation Manual Form Number 95 7673 3 P N 51927 C 12 06 2005 ...
Page 57: ...XLS140 Installation Manual Form Number 95 7673 3 P N 51927 C 12 06 2005 57 Notes ...
Page 68: ...68 XLS140 Installation Manual Form Number 95 7673 3 P N 51927 C 12 06 2005 Notes ...
Page 87: ...XLS140 Installation Manual Form Number 95 7673 3 P N 51927 C 12 06 2005 87 ...