Heating does not come 
on. System on indicator
( = 

heat) 

displays.

Communication is not being 
completed.

Heat load at W8635A is not 
connected correctly.

End and repeat the call for heat. Check the Flash COM 
OK LED on the W8635A EIM while the call is being 
made.
If the Flash COM OK LED does not blink:

check communication Bus wiring.

If the Flash COM OK LED blinks:

check that 24 Vac is present at W1 terminal.

If 24 Vac is not present:

check R to Rh connection.

If the connection is good:

 replace the W8635A EIM.

Cooling does not come 
on. System on indicator

= cool) displays.

Communication is not being 
completed.

Cool load at W8635A is not 
connected correctly.

End and repeat the call for cool. Check the Flash COM 
OK LED on the W8635A EIM while the call is being 
made.
If the Flash COM OK LED does not blink:

 check communication bus wiring.

If the Flash COM OK LED blinks:

check that 24 Vac is present at Y1 terminal.

If 24 Vac is not present:

 

check R to Rh to Rc jumper connection.

If the R to Rh to Rc connection is good:

 replace the W8635A EIM.

“wait” is displayed and 
the call for Cool has not 
started.

Compressor protection is in 
effect.

Compressor protection can be set from 0 to 5 minutes
to prevent compressor damage due to rapid cycling. 
Wait until the compressor protection period expires.

To bypass compressor protection during the installation 
phase, see the Installer System Test section. 

2

nd

 stage heat or cool 

does not energize.

Stage configuration not set 
correctly to match the number of 
selected stages.

Cool load at W8635A is not 
connected correctly.

Set the Stage configuration in Installer Setup for two 
stages or heat and/or two stages of cool.

Check that 24 Vac is present at Y2 or W2 terminal. If 
24 Vac is not present, all connections are good and the 
thermostat is correctly configured, replace W8635A EIM.

Fan does not come on 
with a call for electric 
heat.

Electric heat setting is not 
configured.

Fan load at W8635A is not 
connected correctly.

Set Installer Setup No. 4 to 1 for electric heat.

Check that 24 Vac is present at G terminal. If 24 Vac is 
not present, all connections are good and the thermostat 
is configured, replace the W8635A EIM.

Table 7. Troubleshooting Guide. (Continued)

Symptom

Possible Cause

Action

Summary of Contents for W8635A

Page 1: ...ller must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operation CAUTION Voltage Hazard Can cause electrical shock or equipment damage Disconnect power before supply before beginning installation Location CAUTION Mounting Location Hazard Mounting W8635A inside HVAC equipment can damage the EIM Mount the W8635A only on t...

Page 2: ... CAUTION Voltage Hazard Can cause electrical shock or equipment damage Disconnect power before beginning installation 1 Loosen the terminal screws on the W8635A and connect the system wires See Fig 3 2 Securely tighten each terminal screw Fig 3 Wiring the W8635A terminals Table 2 Terminal Designations Fig 4 2H 2C single transformer Y2 W2 Y1 G W1 C R RH RC 1 2 3 MOUNTING HOLES 2 MOUNTING SCREWS 2 W...

Page 3: ...sed on the information it received during Discovery Mode See Table 4 To change the default cycle rate settings enter T8635L Thermostat Installer Setup and select the desired cycle rate settings for each stage All stages can be set between 1 and 12 cph Table 4 Default Cycle Rate Settings Electric Heat Setting When using the W8635A on an electric heat application set the T8635L Thermostat Installer ...

Page 4: ...ection period To start the Installer System Test 1 Press and hold the T8635L Thermostat increase and decrease keys at the same time until 10 appears All display segments display before the 10 appears See Fig 7 and 8 Fig 7 LCD segments display Fig 8 Installer Test Number display 2 Refer to Table 6 for Installer System Test option Test Number System Test Description 10 12 Heating stages can be turne...

Page 5: ... returns to normal operating mode Table 6 Installer System Test Options Continued Key to Press Test Number Description Run Program Table 7 Troubleshooting Guide Symptom Possible Cause Action Display does not come on at thermostat Thermostat is not being powered Check if the thermostat is mounted and latched on the wallplate if not mount and latch the thermostat on the wallplate Check if the circui...

Page 6: ...ing If the Flash COM OK LED blinks check that 24 Vac is present at Y1 terminal If 24 Vac is not present check R to Rh to Rc jumper connection If the R to Rh to Rc connection is good replace the W8635A EIM wait is displayed and the call for Cool has not started Compressor protection is in effect Compressor protection can be set from 0 to 5 minutes to prevent compressor damage due to rapid cycling W...

Reviews: