W8635A EQUIPMENT INTERFACE MODULE

5

69-1339—2

TROUBLESHOOTING GUIDE

Refer to Table 7 for troubleshooting information.

Fan and Damper Test (Damper Test available only when using W8703A)

40

Enter Fan and Damper test.

41

Fan turns on; damper for this zone opens.

42

Damper closes for this zone (if not already closed); fan stays on.

41

Damper opens for this zone. 

40

Fan turns off.

Key Operation Test 

60

Enter Key Operation test.

Press any key to test if the key is functional. Each time a key is pressed, a different number is displayed. This 
indicates the key is functioning properly. Pressing 

 enters the next test.

Thermostat Information

70

Enter Thermostat Information mode.

71

Production date code is displayed. The first two large digits are 
the month and the third digit is the last digit of the year (example: 
031 = March 2001).

72

Software identification code is displayed.

73

Software revision number is displayed.

74

EEPROM identification code is displayed.

Exit Installer Test Mode

Thermostat returns to normal operating mode.

Table 6. Installer System Test Options. (Continued)

Key to Press

Test Number

Description

Run

Program

Table 7. Troubleshooting Guide.

Symptom

Possible Cause

Action

Display does not come 
on at thermostat.

Thermostat is not being powered. Check if the thermostat is mounted and latched on the 

wallplate; if not:

—mount and latch the thermostat on the wallplate.

Check if the circuit breaker is tripped; if it is:

—reset the circuit breaker.

Check if the fuse is blown; if it is:

—replace the fuse.

Check if the power switch at the equipment is in the Off 
position; if it is:

—set to the On position.

Check for 24 Vac on terminals 2 and 3:
—replace any broken wires.

If 24 Vac is present on terminals 2 and 3:

 replace the thermostat.

“1 COM”, “2 COM” or
“3 COM” is displayed.

Thermostat is unable to 
communicate with the W8635A.

Check the connection to terminal 1 at the thermostat 
and W8635A EIM:

—replace any broken wires.

cycle power.

System Switch setting 
displays “off only.”

During Discovery Mode, the 
thermostat did not correctly set 
the number of heat or cool stages.

Manually run Discovery Mode; see Installer Setup.

manually configure heat and/or cool stages 

(Installer Setup 5 and 8).

Summary of Contents for W8635A

Page 1: ...ller must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operation CAUTION Voltage Hazard Can cause electrical shock or equipment damage Disconnect power before supply before beginning installation Location CAUTION Mounting Location Hazard Mounting W8635A inside HVAC equipment can damage the EIM Mount the W8635A only on t...

Page 2: ... CAUTION Voltage Hazard Can cause electrical shock or equipment damage Disconnect power before beginning installation 1 Loosen the terminal screws on the W8635A and connect the system wires See Fig 3 2 Securely tighten each terminal screw Fig 3 Wiring the W8635A terminals Table 2 Terminal Designations Fig 4 2H 2C single transformer Y2 W2 Y1 G W1 C R RH RC 1 2 3 MOUNTING HOLES 2 MOUNTING SCREWS 2 W...

Page 3: ...sed on the information it received during Discovery Mode See Table 4 To change the default cycle rate settings enter T8635L Thermostat Installer Setup and select the desired cycle rate settings for each stage All stages can be set between 1 and 12 cph Table 4 Default Cycle Rate Settings Electric Heat Setting When using the W8635A on an electric heat application set the T8635L Thermostat Installer ...

Page 4: ...ection period To start the Installer System Test 1 Press and hold the T8635L Thermostat increase and decrease keys at the same time until 10 appears All display segments display before the 10 appears See Fig 7 and 8 Fig 7 LCD segments display Fig 8 Installer Test Number display 2 Refer to Table 6 for Installer System Test option Test Number System Test Description 10 12 Heating stages can be turne...

Page 5: ... returns to normal operating mode Table 6 Installer System Test Options Continued Key to Press Test Number Description Run Program Table 7 Troubleshooting Guide Symptom Possible Cause Action Display does not come on at thermostat Thermostat is not being powered Check if the thermostat is mounted and latched on the wallplate if not mount and latch the thermostat on the wallplate Check if the circui...

Page 6: ...ing If the Flash COM OK LED blinks check that 24 Vac is present at Y1 terminal If 24 Vac is not present check R to Rh to Rc jumper connection If the R to Rh to Rc connection is good replace the W8635A EIM wait is displayed and the call for Cool has not started Compressor protection is in effect Compressor protection can be set from 0 to 5 minutes to prevent compressor damage due to rapid cycling W...

Reviews: