Honeywell W7100 Manual Download Page 6

W7100G DISCHARGE WATER TEMPERATURE CONTROL

63-4046—1

6

OPERATION

Chiller System Description (Fig. 5)

Chiller systems are used to provide cold water for many 

types of end uses. The cold water may be piped to many air 

handling units located throughout a building. These units then 

provide cooling and ventilation for individual zones throughout 

that building. Chillers are also used to supply cold fluid for a 

variety of process applications. In either case, precise 

discharge water temperature control is desired.

Fig. 5. Chiller system.

Discharge Water Temperature 

Control Operation

The W7100G uses an integrating control band concept to 

provide close, stable temperature control in discharge water 

chiller systems. The control band concept matches required 

operating capacity to chiller load, while the integral action 

minimizes the offset from the control setpoint which normally 

occurs in proportional-only type controllers.

The control band setting is centered on the discharge waters 

setpoint (see Fig. 6). The control band setting is adjustable 

from 0 to 10°F (0 to 6°C). This adjustment is used to stabilize 

system operation.

Fig. 6. Discharge water control algorithm operation.

A description of how chiller control stages operate follows:

1.

Using Fig. 6 and beginning at point A, the discharge 

water temperature is above the upper control band limit 

and the minimum OFF time has elapsed (selectable 

either 30 or 60 seconds, using fast response input).

2.

The W7100 first stage energizes.

3.

At point B, the discharge water temperature is still 

above the upper control band limit.

4.

If the minimum time between stages has elapsed 

(selectable), the next highest cooling stage energizes.

5.

At point C, the discharge water temperature has fallen 

below the lower control band.

6.

If the minimum ON time has elapsed for that stage, the 

highest stage that is on shuts off.

7.

This sequence continues until the cooling demand 

increases (point D) at which time stages sequence ON 

in the same manner as before.

8.

As a rule, any time the discharge water temperature:

a. is above the upper control band limit, a stage turns 

on.

b. falls below the lower control band limit, a stage turns 

off.

Reset of Discharge Water Temperature

Industrial Applications

Reset of discharge water temperature is not recommended in 

a W7100G industrial application, because loads on industrial 

applications typically require a constant temperature fluid for 

cooling. Check industrial process manufacturers for specific 

details.

Environmental Applications

In order to save additional energy under lighter loading 

conditions, it may be desirable to change or reset the 

discharge water temperature setpoint based on either space 

or outside air temperatures. Reset has proved itself on hot 

water boilers as an energy saving opportunity. These same 

energy saving techniques can also be applied to chillers, to 

more evenly match system capacity with system load.

Reset from Space Temperature

A chiller that is being used to chill water for single or multiple 

air handling units can be made more efficient by resetting the 

discharge water temperature up as the average space 

temperature goes below a space temperature setpoint.

In order to accomplish this, space sensors (such as 

T7047C1025) are strategically located in the building to 

measure average space temperature. It is recommended that 

at least 4 sensors be installed and wired to provide a signal 

proportional to the average space temperature. The setpoint 

of the reset potentiometer should be set at the lowest desired 

cooling temperature of the building. See Fig. 7 for space reset 

operation (algorithm). See Fig. 8 for wiring details.

As the average space temperature drops below the setpoint 

of the reset sensors, the W7100G discharge temperature 

setpoint is reset upward by an adjustable amount. Maximum 

reset occurs when the average space temperature is 3°F 

(1.7°C) below the setpoint of those sensors. At this time, 

the W7100G setpoint will be fully reset.

In reset applications where high humidity can be a concern, 

an outdoor air thermostat can be installed to override the reset 

function. In lieu of outdoor air override an indoor space 

humidistat can also be used. See Fig. 8 for wiring diagrams.

M17921

PUMP

RETURN

WATER

SUPPLY WATER

TO SYSTEM LOAD

REMOTE

SETPOINT

COMPRESSOR(S)

CHILLER 

BARREL

W7100G 

DISCHARGE

WATER CONTROL

ADJUSTABLE

CONTROL

BAND

0 TO 10 F

LOWER CONTROL BAND LIMIT

UPPER CONTROL BAND LIMIT

DISCHARGE WATER TEMPERATURE

W7100 SETPOINT

A

B

C

D

M17917

Summary of Contents for W7100

Page 1: ...ages using a W7101 Advanced proportional plus integral microprocessor control algorithm minimizes droop Soft start to minimize compressor cycling during system start up Adjustable minimum on off timing and time delay between stages of either 30 or 60 seconds Adjustable setpoint from 10 to 110 F 12 to 43 C Adjustable reset differential from 5 to 20 F 3 to 11K Adjustable control band from 0 to 10 F ...

Page 2: ...rminals 7 and 6 to determine num ber of ON OFF stages See Table 2 Temperature Ratings Ambient 40 F to 150 F 40 C to 66 C Shipping 30 F to 150 F 34 C to 66 C Humidity Rating 5 to 90 percent RH noncondensing Mounting Four mounting holes in base Use No 6 screws not provided Approvals Underwriter s Laboratories Inc Component Recognized Additional System Components C7170A1010 Discharge Water Sensor sen...

Page 3: ... to correct the interference Any unauthorized modification of this equipment may result in the revocation of the owner s authority to continue its operation CAUTION Electrical Shock or Equipment Damage Hazard Can shock individuals or short equipment circuitry Disconnect power supply before installation CAUTION Equipment Damage Hazard Compressor stage ON OFF times less than four minutes can damage ...

Page 4: ...ng under the control of the W7100G This includes any stages on a W7101A sequencer connected to the W7100G control Connecting Additional Stages Control of up to 4 additional stages of ON OFF cooling can be added by using a W7101A Satellite Sequencer to the W7100G system as shown in Fig 4 The fixed resistor value across the W7100G terminals 7 and 8 Table 2 must agree with the total number of cooling...

Page 5: ...R OF STAGES CONTROLLED FAST RESPONSE INPUT REFERS TO THE MINIMUM ON TIME MINIMUM OFF TIME AND MINIMUM TIME DELAY BETWEEN STAGES LEAVE OPEN FOR 60 SEC TIMINGS JUMPER FOR 30 SEC TIMINGS 90 85 80 75 70 65 55 60 60 45 40 SETPOINT F 31 15 15 11 10 10 13 5 5 16 14 12 10 8 6 4 CONTROL BAND 20 20 2 GND TR TR 10 9 8 7 6 T T1 P2 P1 4 3 2 1 5 B C A B C A B C A B C A B C A B C A 24VAC FAST RESPONSE NO STAGES ...

Page 6: ...imit a stage turns off Reset of Discharge Water Temperature Industrial Applications Reset of discharge water temperature is not recommended in a W7100G industrial application because loads on industrial applications typically require a constant temperature fluid for cooling Check industrial process manufacturers for specific details Environmental Applications In order to save additional energy und...

Page 7: ...dify the outside air reset start and stop temperatures To do this a resistor must be placed in parallel with the outside air sensor Rp and a resistor must be placed in series with the outside air sensor Rs See Fig 10 Fig 10 Reset modification schematic wiring diagram Use Table 3 to select the point at which no W7100 setpoint reset will occur T High and the point at which the W7100 will be fully re...

Page 8: ...l band Increasing the control band slows down the W7100 response and increases the temperature deviation Lowering the control band speeds up the W7100 response while decreasing the temperature deviation from setpoint The control band setpoint should be as narrow as possible without causing hunting or rapid cycling If instability hunting or rapid cycling occurs widen the control band setpoint Fast ...

Page 9: ...red leads 6 Jumper W7100 terminals P and P1 7 Remove red plastic dust plug from W7100 bottom and install 195770A Test Plug in the revealed socket 8 Set W7100 reset knob at 20 F 11K 9 Set W7100 setpoint at 10 F 12 C 10 Connect 24 Vac power to the W7100 TR and TR terminals Check for 24 Vac across W7100 TR and TR terminals 11 Wait 15 seconds 12 All W7100 stages should be energized All red LED should ...

Page 10: ...lding engineering requirements No cooling 1 Shorted or open discharge sensor terminals T T1 1 Correct the wiring 2 Open reset terminals 6 7 interpreted as maximum reset 2 Jumper terminals 6 7 or connect reset thermostat 3 Remote setpoint terminals P P1 open 3 Jumper terminals P P1 or connect remote setpoint potentiometer 4 System malfunction 4 Consult HVAC manufacturer s equipment manual and or bu...

Page 11: ...11 63 4046 1 ...

Page 12: ...0 Brussels 480 Sawgrass Corporate Parkway Golden Valley MN 55422 Scarborough Ontario No 30 Harbour Road Belgium Suite 200 M1V 4Z9 Wanchai Sunrise FL 33325 Hong Kong By using this Honeywell literature you agree that Honeywell will have no liability for any damages arising out of your use or modification to the literature You will defend and indemnify Honeywell its affiliates and subsidiaries from a...

Reviews: