68-0139
38
W180 ZONE CONTROL SYSTEM
Fig. 43—Mounting the T7660A/T7660B Space
Temperature Sensor circuit board on the
mounting plate.
P
CIRCUIT
BOARD
TEMPERATURE
SENSOR
UPPER
NOTCH
SPRING
CLIPS
COVER MOUNTING
SCREWS
MOUNTING
PLATE
SWITCH/LED
ASSEMBLY
M9179
Fig. 44—Mounting the T7660A/T7660B Space
Temperature Sensor cover.
M8163
SWITCH/LED
ASSEMBLY
2 [51]
1
1
2
[38]
3
3
16
[81]
2 [51]
COVER MOUNTING SLOTS
C7600C Solid State Humidity Sensor
CAUTION
Disconnect the power supply before making wiring
connections to prevent electrical shock or equip-
ment damage.
The sensor may be installed in any position in a duct or
outdoors.
NOTES:
1. Check the ratings given in the instructions and on the
product to make sure the product is suitable for the
application.
2. Locate the sensor:
a. Where there is a minimum of 500 ft/min airflow.
b. Locate the sensor where it is exposed to freely
circulating air, but protected from rain and direct
sunlight.
c. Locate the sensor away from traffic areas, on an
inside wall, at least 3 ft (1m) from an outside wall
and 54 in. (1.4m) from the floor.
Mount and install the C7600C Solid State Humidity
Sensor as described in the instructions furnished by the
manufacturer. Wire the C7600C Solid State Humidity Sen-
sor as shown in the job drawings and Fig. 45.
Fig. 45—Typical C7600C Solid State Humidity
Sensor wiring.
–1
+1
–2
+2
–3
+3
–4
+4
–5
+5
–6
+6
–7
+7
–8
+8
SENSOR/INPUT
CONNECTIONS
M8176
SENSOR GND
SENSOR PWR
C7600C
20 VDC
5 VDC
+
–
CABLE SHIELD
(IF REQUIRED)
DAMPERS
CAUTION
Do not attempt to turn the damper shaft by hand
or with a wrench because this will damage the