Honeywell VS8420C Installation Instructions Manual Download Page 7

VS8420C,M MILLIVOLT GAS VALVE

7

69-1304

Checking Gas Input With Manometer

NOTE:

Both the inlet and outlet pressure taps have a 
captive screw.

1.

Be sure the gas control knob is in the OFF posi-
tion.

2.

Loosen, but do not remove the outlet tap captive 
screw.

3.

Attach a plastic tube with a 9 mm OD and 1/4 
in.(6.4 mm)  shell ID and connect the manometer.

4.

Check the outlet tap pressure.

5.

Turn the gas control knob to the OFF position.

6.

Shut off the gas supply at the manual valve in the 
gas piping to the appliance or, for LP, at the tank.

7.

Loosen, but do not remove the inlet tap captive 
screw.

8.

Attach a plastic tube with a 9 mm OD and 1/4 
in.(6.4 mm)  shell ID and connect the manometer.

9.

Check the inlet tap pressure.

10.

Turn the gas control knob to the OFF position.

11.

Repeat the Gas Leak Test at the pressure tap 
with the main burner operating.

Check Safety Shutdown Performance

WARNING

Fire or Explosion Hazard.
Can cause property damage, severe injury or 
death.
Perform the safety shutdown test any time work 
is done on a gas system.

1.

Place gas control knob in PILOT position. Main 
burner should go off and pilot should remain lit.

2.

Extinguish pilot flame. The  VS8420 pilot gas flow 
stops within thirty seconds. Pilot gas safety shut-
off proves complete shutdown because the safety 
shutoff valve prohibits main burner and pilot gas 
flow.

3.

Relight pilot burner and operate the system 
through one complete cycle to ensure all controls 
operate properly.

MAINTENANCE

WARNING

Fire or Explosion Hazard.
Can cause property damage, severe injury or 
death.
Do not attempt to take apart the gas valve or 
clean it. Improper assembly and cleaning can 
cause unreliable operation.

Regular preventive maintenance is important in applica-
tions that place a heavy load on system controls such 
as those used in the commercial cooking and agricul-
tural and industrial industries because:

In applications such as commercial cooking, the 
equipment operates 100,000 to 200,000 cycles per 
year. This heavy cycling can wear out the gas valve 
in one to two years.

Exposure to water, dirt, chemicals and heat can 
damage the gas valve and shut down the control 
system.

The maintenance program should include regular 
system checkout as outlined in the Checkout section, 
and checkout of the control system as described in the 
appliance manufacturer literature.

Maintenance frequency must be determined individually 
for each application:

Cycling frequency—Appliances that cycle 20,000 
times annually should be checked monthly.

Intermittent use—Appliances that are used 
seasonally should be checked before shutdown and 
again before the next use.

Consequence of unexpected shutdown—Where the 
cost of an unexpected shutdown would be high, the 
system should be checked more often.

Dusty, wet, or corrosive environment—Because 
these environments can cause the gas valve to 
deteriorate more rapidly, the system should be 
checked more often.

Any valve should be replaced if it does not perform 
properly on checkout or service. In addition, replace any 
module if it is wet or looks like it has ever been wet. 

SERVICE

WARNING

Fire or Explosion Hazard.
Attempted disassembly or repair can cause 
property damage, severe injury or death.
Do not disassemble the gas valve; it contains no 
replaceable components.

CAUTION

Equipment Damage Hazard.
Can burn out heat anticipator in thermostat.
Do not apply a jumper across (or short) the 
valve coil terminals even temporarily.

If Main Burner Does Not Come On With 
Call For Heat

1.

Confirm that the gas control knob is in the ON 
position.

2.

Adjust the thermostat several degrees above the 
room temperature.

3.

Use a dc voltmeter to measure the voltage across 
the THTP and TP terminals.

4.

If no voltage is present, check the control circuit 
for proper operation.

5.

If proper control system voltage is present, 
replace the gas valve.

Warning To The Appliance Owner. For 
Your Safety, Read Before Lighting 
Appliance.

WARNING

Fire or Explosion Hazard.
Can cause property damage, severe injury or 
death.
Follow  exactly the instructions for Pre-Lighting 
Checks.

Summary of Contents for VS8420C

Page 1: ...ith EN 88 class C Natural Gas 9 mbar typical LP 27 mbar typical Regulator Adjustments Standard Regulator Natural Gas 7 5 mbar to 12 5 mbar field adjustable LP 20 mbar to 30 mbar field adjustable In appliances where no regulation is required the pres sure regulator must be blocked by turning the pressure regulator adjustment screw fully down The regulator will then be set at 30 mbar Voltage VS8420 ...

Page 2: ...onvert from natural gas to LP High low regulator model VS8420C cannot be converted Location Locate the combination gas valve where it cannot be affected by steam cleaning high humidity dripping water corrosive chemicals dust or grease accumula tion or excessive heat To assure proper operation follow these guidelines Locate gas valve in a well ventilated area Mount gas valve high enough to avoid ex...

Page 3: ...pilot burner according to the manufacturer s instructions WARNING Fire or Explosion Hazard Can cause property damage severe injury or death Do not bend tubing at gas valve after compres sion fitting has been tightened as this may result in a gas leak at the connection Fig 3 Top view of gas valve with HI LO regulator Fig 4 Top view of gas valve with standard regulator GAS CONTROL GAS CONTROL HORIZO...

Page 4: ...ting stamped on the valve operator Table 1 Maximum Thermostat Wire Length ECO Connection Supplementary 1 Push the ECO into the window of the gas valve See Fig 5 2 The leadwires of the ECO must be equipped with insulated 6 3 mm female quick connect terminals 3 Leadwire length must not exceed the length as shown in Table 2 Table 2 Maximum Length mm of Supplementary Limit Leadwires When Using Q309A T...

Page 5: ...erclockwise to the ON position On a call for heat the main valve opens and the main burner ignites Shut off Procedure 1 To shut off the system turn the knob clockwise to the OFF position This action closes the main gas and safety valves however the power unit must drop out before the lighting sequence can begin again The VS8420 drops out within 30 seconds 2 To relight the pilot light follow the st...

Page 6: ...ot gas flow Gas valve and thermostat control main burner gas flow PILOT Opens pilot valve and allows gas flow to the pilot burner HI LO Manually adjusts outlet pressure NOTE Valves are shipped with the gas control knob in the ON position Perform Gas Leak Test WARNING Fire or Explosion Hazard Can cause property damage severe injury or death Stand away from the main burner while lighting Hidden gas ...

Page 7: ...equipment operates 100 000 to 200 000 cycles per year This heavy cycling can wear out the gas valve in one to two years Exposure to water dirt chemicals and heat can damage the gas valve and shut down the control system The maintenance program should include regular system checkout as outlined in the Checkout section and checkout of the control system as described in the appliance manufacturer lit...

Page 8: ...ff the manual valve in the gas piping to the appliance or on LP at the tank Leave the building immediately and call your gas supplier If your gas supplier cannot be reached call the fire department 3 Do not force the gas valve control knob Use only your hand to turn the control knob 4 If the knob does not operate by hand the valve should be replaced by a qualified service techni cian 5 The gas val...

Reviews: