Honeywell VR8405 Manual Download Page 9

9

68-0150

VR8405

STARTUP AND CHECKOUT  •  MAINTENANCE  •  OPERATION

1. Turn off knobs on entire gas control.
2. Set thermostat or controller above room temperature

to call for heat.

3. Watch for ignition spark or glow at hot surface

igniter either immediately or following prepurge. See DI
Module specifications.

4. Time the length of the igniter operation. See DI

Module specifications.

5. After the module locks out, open gas control knobs

and make sure there is no gas flow to the main burner.

6. Set thermostat below room temperature and wait

one minute.

7. Operate system through one complete cycle to make

sure all controls operate properly.

Maintenance

WARNING

FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE,
SEVERE INJURY, OR DEATH.
Do not disassemble the gas control or either valve.
They contain no replaceable components. Attempted
disassembly or repair can damage the gas control.

Regular preventive maintenance is important in applica-

tions such as commercial cooking, agricultural and indus-
trial operations that place a heavy load on system controls
because:

• In many applications, particularly commercial cook-

ing, the equipment operates 100,000 to 200,000 cycles
per year. Such heavy cycling can wear out the gas
control in one to two years.

• Exposure to water, dirt, chemicals and heat can dam-

age the gas control and shut down the control system.

The maintenance program should include regular check-

out of the entire gas control; see Startup and Checkout
section. To check out the control system, see the appliance
manufacturer literature. Maintenance frequency must be

determined individually for each application. Some consid-
erations are:

• Cycling frequency. Appliances that may cycle 100,000

times annually should be checked monthly.

• Intermittent use. Appliances that are used seasonally

should be checked before shutdown and again before
the next use.

• Consequence of unexpected shutdown. Where the

cost of an unexpected shutdown would be high, the
system should be checked more often.

• Dusty, wet, or corrosive environment. Since these

environments can cause the gas control to deteriorate
more rapidly, the system should be checked more
often.

If the gas controls will be exposed to high ammonia

conditions; e.g., those used in greenhouses or animal barns,
contact your Honeywell sales representative to request a
gas control with corrosion resistant construction.

The entire gas control should be replaced if:
• It does not perform properly during checkout or

troubleshooting.

• The gas control knobs are hard to turn.
• The gas control is likely to have operated for more

than 200,000 cycles.

Operation

The VR8405 gas controls provide ON-OFF manual con-

trol of gas flow. When both knobs are in the OFF position,
main burner gas flow is prevented. When both knobs are in
the ON position, main burner gas flow is under control of
the thermostat, the direct ignition module, and the two auto-
matic valve operators of each valve.

The VR8405 gas controls consist of two parallel valves

on a die-cast manifold to provide high capacity. The indi-
vidual valves operate in unison to regulate gas flow. The
following information describes how each individual valve
operates as well as how they interact.

SYSTEM OPERATION WITH MODULE

When the thermostat calls for heat, the DI module is

energized. The module activates the first and second auto-
matic valves of the gas controls which allows main burner

gas flow. At the same time, the DI module generates a
spark at the igniter-sensor to light the main burner.

The second automatic valve diaphragm of each valve,

controlled by its servo pressure regulator, opens and adjusts
gas flow as long as the system is powered. The servo pres-
sure regulators monitor outlet pressure to provide an even
main burner gas flow. Loss of power (thermostat satisfied)
de-energizes the DI module and closes the automatic valves.
The system is ready to return to normal service when power
is restored through the thermostat.

If the igniter-sensor stops detecting a flame at the main

burner, the trial for ignition is restarted. On DI modules
with lockout timers, the automatic valves are de-energized
and ignition stops after the lockout period. On modules with-
out lockout timers, the trial for ignition continues indefinitely.

Summary of Contents for VR8405

Page 1: ...t3 hour 20 3 meters3 hour Minimum capacity rated 200 feet3 hour 5 7 meters3 hour Solenoid operated dual first automatic valves open on thermostat call for heat and close when call for heat ends Diaphragm operatedsecondautomaticvalvesopen under control of the regulator and close if gas or power supply is interrupted Two position gas control knobs have ON and OFF positions All adjustments and wiring...

Page 2: ...e ordering number or specify 1 Order Number 2 Natural or LP gas 3 Step pressure on VR8405P 4 Accessories is desired 5 Order separately transformer igniter sensor module limit controller and thermostat or controller as required If you have additional questions need further information or would like to comment on our products or services please write or phone 1 Your local Honeywell Home and Building...

Page 3: ...ravity natural gas at 0 25 kPa pressure drop PRESSURE REGULATION Not adjustable DIMENSIONS See Fig 1 TEMPERATURE RATING VR8405H 0 F to 175 F 18 C to 79 C VR8405M P 40 F to 175 F 40 C to 79 C PRESSURE TAPPING Inlet and outlet taps standard Taps accessible from top of control Tap is 1 8 in NPT with plug containing recess for 3 16 in Allen wrench PRESSURE RATING AGA rating 1 2 psi 3 5 kPa inlet press...

Page 4: ...e appliance manufacturer instructions if avail able otherwise use the instructions provided below INSTALL BUSHINGS ON ENTIRE GAS CONTROL 1 Remove seals over gas control inlet or outlet 2 Apply moderate amount of good quality pipe com pound to bushing leaving two end threads bare On an LP gas installation use compound resistant to LP gas See Fig 3 Do not use Teflon tape 3 Insert bushing in entire g...

Page 5: ...ENGTH IN IN Pipe Size Thread Pipe This Amount Maximum Depth Pipe Can Be Inserted Into Control 3 4 13 16 3 4 1 1 1 16 1 5 Remove seals over gas control inlet and outlet if necessary 6 Connect pipe to gas control inlet and outlet Use a wrench on the manifold rather than on the gas control Refer to Figs 4 and 5 WIRING Follow the wiring instructions furnished by the appli ance manufacturer if availabl...

Page 6: ... VALVE GND TEMPERATURE CONTROLLER POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED ALTERNATE LIMIT CONTROLLER LOCATION MAXIMUM IGNITER SENSOR CABLE LENGTH 3 ft 9 m OR LESS 3 A REPLACEABLE FUSE ALARM TERMINAL PROVIDED ON SOME MODELS M8051 MVPV MVPV L1 HOT L2 1 2 1 2 3 VR8405 COMBINATION GAS CONTROL Q347 IGNITER SENSOR BURNER 4 4 5 IGNITER SENSOR AND BURNER GROUND 3 5 ALARM ...

Page 7: ... leak is detected tighten the pipe connection 3 Stand clear while lighting main burner to prevent injury caused from hidden gas leaks that could cause flash back in the appliance vestibule Turn on the entire gas control and light the main burner as described below 4 With the main burner in operation paint all pipe joints and gas control inlet and outlet with a rich soap and water solution 5 Ifanot...

Page 8: ...ustable Step Opening Pressure Regulator 1 The gas control outlet pressure should match the manifold pressure listed on the appliance nameplate 2 With the main burner operating check the gas con trol flow rate using the meter clocking method 3 If desired flow rate is not as stamped on the control check the inlet pressure using a manometer at inlet pres sure tap or upstream of the gas control Regula...

Page 9: ...nce these environments can cause the gas control to deteriorate more rapidly the system should be checked more often If the gas controls will be exposed to high ammonia conditions e g those used in greenhouses or animal barns contact your Honeywell sales representative to request a gas control with corrosion resistant construction The entire gas control should be replaced if It does not perform pr...

Page 10: ... repositions to change the flow rate through the regulator valve and thus through the automatic valve If outlet pressure begins to rise the pressure regulator diaphragm moves slightly higher allowing less gas flow to the gas control outlet This increases gas pressure under the automatic valve diaphragm and repositions the valve disc closer to the seat Thus flow of gas through the second automatic ...

Page 11: ...operators close bypassing the regulator s and shutting off the main burner As pres sure inside the gas controls and underneath the automatic valvediaphragmsequalize springpressureclosesthesecond automatic valves to provide a second barrier to gas flow Fig 9 Position of gas control components during burner on cycle Both valves are positioned the same one valve shown for simplicity two main valves a...

Page 12: ...appliance The information below will be of assistance in a typical control application but the specific controls used and the procedures outlined by the manufac turer of your appliance may differ and require special instructions TO TURN ON THE APPLIANCE STOP READ THE WARNING ABOVE The lighting sequence of this appliance is automatic Do not attempt to manually light the main burner If the appli anc...

Reviews: