Honeywell VR8305 Quick Manual Download Page 10

Maintenance

WARNING

FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE,
SEVERE INJURY, OR DEATH
Improper cleaning or reassembly could cause gas
leakage. When cleaning, ensure that control is reas-
sembled properly and perform gas leak test.

Regular preventive maintenance is important in applica-

tions such as in the commercial cooking and agricultural and
industrial industries that place a heavy load on system con-
trols because:

• The equipment operates 100,000-200,000 cycles per

year in many such applications, particularly commer-
cial cooking. Such heavy cycling can wear out the gas
control in one to two years.

• Exposure to water, dirt, chemicals and heat can damage

the gas control and shut down the control system.

The maintenance program should include regular check-

out of the gas control, see Start-Up and Checkout, page 8, and
the control system as described in the appliance manufacturer’s
literature.

Maintenance frequency must be determined individually

for each application. Some considerations are:

• Cycling frequency. Appliances that may cycle 100,000

times annually should be checked monthly.

• Intermittent use. Appliances that are used seasonally

should be checked before shutdown and again before
the next use.

• Consequence of unexpected shutdown. Where the cost

of an unexpected shutdown would be high, the system
should be checked more often.

• Dusty, wet, or corrosive environment. Since these

environments can cause the gas control to deteriorate
more rapidly, the system should be checked more
often.

The gas control should be replaced if:
• It does not perform properly on checkout or trouble-

shooting.

• The gas control knob is hard to turn or push down, or

it fails to pop back up when released.

• The gas control is likely to have operated for more than

200,000 cycles.

Operation

The VR8305 Gas Controls provide ON-OFF manual

control of gas flow. In the OFF position, main burner gas flow
is prevented. In the ON position, main burner gas flow is
under control of the thermostat, the direct ignition (DI)
module, and the two automatic main valves.

SYSTEM OPERATION WITH MODULE

When the thermostat calls for heat, the DI module is

energized. The module activates the first and second auto-
matic valves of the gas control, which allows main burner gas
flow. At the same time, the DI module generates a spark at the
igniter-sensor to light the main burner.

The second automatic valve diaphragm, controlled by the

servo pressure regulator, opens and adjusts gas flow as long
as the system is powered. The servo pressure regulator
monitors outlet pressure to provide an even main burner gas
flow. Loss of power (thermostat satisfied) de-energizes the
DI module and closes the automatic valves. The system is
ready to return to normal service when power is restored
through the thermostat.

If the igniter-sensor stops detecting a flame at the main

burner, the trial for ignition is restarted. On DI modules with
lockout timers, the automatic valves are de-energized and
ignition stops after the lockout period. On modules without
lockout timers, the trial for ignition continues indefinitely.

If main burner flame is restarted successfully, operation

continues as described above. Gas control operation is de-
scribed in more detail below.

VALVE POSITION DURING THERMOSTAT OFF
CYCLE

The valve is positioned as shown in Fig. 10 when the:

• gas control knob is in the ON position.
• thermostat is not calling for heat.

The first automatic valve is closed. The second automatic

valve operator is de-energized, closing the channel to the
pressure regulator, and opening a channel to the underside of
the second automatic valve operator valve diaphragm. The
combination of spring pressure under the second automatic
valve diaphragm and lack of outlet pressure hold the dia-
phragm firmly closed. Main burner gas flow is blocked by
both valves.

WHEN THERMOSTAT CALLS FOR HEAT

When the thermostat calls for heat, the DI module gener-

ates a spark at the main burner and the first automatic valve
and second automatic valve operators are energized, Fig. 11.
The first automatic valve opens, and the second automatic
valve operator valve disc is lifted off its seat. This diverts gas
flow from the second automatic valve diaphragm, and causes
a reduction of pressure on the underside of this diaphragm.
The reduced pressure on the bottom of the automatic valve
diaphragm repositions the diaphragm downward, away from
the valve seat, allowing main burner gas flow.

Standard-Opening Pressure Regulation (VR8305M)

During the On cycle, the servo pressure regulator provides

VR8305

MAINTENANCE • OPERATION

10

Summary of Contents for VR8305

Page 1: ...ontrols include a safety shut off a manual valve two automatic operators and a pressure regulator Used with S89C E F and S87 series 5 and later Used with 24 Vac heating appliances that burn natural or liquefied petroleum LP gas Capacity rated up to 300 feet3 hour at 1 inch wc pressure drop 8 5 meters3 hour at 0 25 kPa Maximum capacity rated up to 415 feet3 hour 11 8 meters3 hour Minimum capacity r...

Page 2: ...expected if those con ditions are changed MODELS VR8305 Dual Automatic Valve Combination Gas Controls for use in Direct Ignition Systems See Table 1 for model specifications SUPPLY VOLTAGE 24 Vac 60 Hz CURRENT DRAW 0 7A ELECTRICALCONNECTIONS 1 4inchmalequick con nects Two convenience terminals on top of control op tional Terminal block color coded brown TYPE OF GAS VR8305 setup for natural gas inc...

Page 3: ...PT Straight 393690 6 393690 16 Elbow 393690 3 393690 13 3 4 inch NPT Straight 393690 4 393690 14 Elbow 393690 5 393690 15 NOTE Flange Kits include one flange with attached O ring and four mounting screws PRESSURE TAPPING Inletandoutlettapsstandard Taps accessible from top of gas control Tap is 1 8 inch NPT with plug containing recess for 3 16 inch Allen wrench PRESSURE RATING A G A rating 1 2 psi ...

Page 4: ...nect piping Followtheappliancemanufacturer sinstructionsifavail able otherwise use the instructions provided below CONVERTING BETWEEN NATURAL AND LP GAS WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE INJURY OR DEATH 1 DonotuseagascontrolsetfornaturalgasonLP gasoragascontrolsetforLPgasonnaturalgas 2 Whenmakingconversion mainandpilotburner orifices MUST be changed to meet applianc...

Page 5: ...endofthesupplypipeinplaceofthegascontrol following the same precautions and instructions that are used for installingthegascontrol Aftertheadapterisinstalled thegas control is attached to the adapter as outlined above Note that using an adapter increases the overall length of the gas control CHOOSE GAS CONTROL LOCATION Do not locate the gas control where it can be affected by steam cleaning high h...

Page 6: ...mount Control 3 8 9 16 3 8 1 2 3 4 1 2 3 4 13 16 3 4 GAS CONTROL GAS CONTROL HORIZONTAL DROP PIPED GAS SUPPLY PIPED GAS SUPPLY 3 IN 76 MM MINIMUM 3 IN 76 MM MINIMUM RISER GAS CONTROL TUBING GAS SUPPLY HORIZONTAL DROP 3 IN 76 MM MINIMUM RISER M3077 2 1 2 2 1 2 ALL BENDS IN METALLIC TUBING SHOULD BE SMOOTH CAUTION SHUT OFF THE MAIN GAS SUPPLY BEFORE REMOVING END CAP TO PREVENT GAS FROM FILLING THE W...

Page 7: ...ctrical shock or equipment damage 1 Checkthepowersupplyratingonthevalveandensure it matches the available supply Install transformer thermo stat and other controls as required 2 Connect control circuit to gas control terminals See Figs 2 8 and 9 3 Adjust thermostat heat anticipator to 0 70 rating stamped on valve operator Fig 8 VR8305 Wiring Connections in S87 Direct Ignition System Fig 9 VR8305 W...

Page 8: ...ER CAUTION 1 Do not exceed the input rating stamped on the appliance nameplate or manufacturer s recom mended burner orifice pressure for the size ori fice used Ensure the main burner primary air supply is properly adjusted for complete com bustion refer to the appliance manufacturer s instructions 2 IF CHECKING GAS INPUT BY CLOCKING THE GAS METER Ensure that the only gas flow through the meter is...

Page 9: ...ure regulator adjustment cap screw b Using a screwdriver turn the inner adjustment screw clockwise toincreaseorcounterclockwise to decrease the main burner gas pressure c Always replace the cap screw and tighten firmly to ensure proper operation 4 Ifdesiredoutletpressureorflowratecannotbeachieved by adjusting the gas control check the inlet pressure using a manometeratinletpressuretaporupstreamoft...

Page 10: ...ticvalvesofthegascontrol whichallowsmainburnergas flow Atthesametime theDImodulegeneratesasparkatthe igniter sensor to light the main burner The second automatic valve diaphragm controlled by the servo pressure regulator opens and adjusts gas flow as long as the system is powered The servo pressure regulator monitors outlet pressure to provide an even main burner gas flow Loss of power thermostat ...

Page 11: ...let pressure and 3 5 inches wc 0 9 kPa outlet pressure Step Opening Pressure Regulation VR8305P Step opening gas controls actually combine two pressure regulators one for the low pressure and one for the full rate pressure When the thermostat calls for heat the automatic operator valve disc opens The low pressure regulator main tainsoutletpressureatthepresetsteprateforseveralseconds Then the regul...

Page 12: ...RATOR SECOND AUTOMATIC OPERATOR SOLENOID SECOND AUTOMATIC OPERATOR VALVE DISC SERVO PRESSURE REGULATOR GAS CONTROL OUTLET SECOND AUTOMATIC VALVE DIAPHRAGM FIRST AUTOMATIC VALVE NOTE SECOND AUTOMATIC VALVE OPERATOR AND SERVO PRESSURE REGULATOR SHOWN OUTSIDE GAS CONTROL FOR EASE IN TRACING GAS FLOW SLOW OPENING GAS CONTROL HAS A GAS FLOW RESTRICTOR IN THIS PASSAGE M9115 1 1 ...

Page 13: ...ty control 2 Disconnect all electric power to the appliance 3 Remove the gas control access panel 4 Push in the gas control knob slightly and turn clock wise to OFF 5 Waitfiveminutestoclearoutanyunburnedgas Ifyou then smell gas STOP Follow Step 3 in the Warnings above If you do not smell gas continue with the next step WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE INJURY OR DEA...

Page 14: ... will completely shut off Follow the Instructions to the Homeowner above to resume normal operation 6 Turn the gas control knob counterclockwise to ON 7 Replace the gas control access panel 8 Reconnect all electric power to the appliance 9 Set the thermostat to the desired setting 10 If the appliance does not turn on set the gas control knob to OFF and contact a qualified service technician for as...

Page 15: ...15 68 0109 3 ...

Page 16: ...elping You Control Your World Building Controls Division Building Controls Division Honeywell Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley MN 55422 Scarborough Ontario QUALITY IS KEY ...

Reviews: