Honeywell VR4305 Quick Start Manual Download Page 6

69-0696—1

6

4. If the desired outlet gas pressure or gas flow rate can

not be achieved by adjusting the gas control, check the gas
control inlet pressure by using a manometer at the inlet
pressure tap. If the inlet pressure is in the normal range
(refer to Table 5 or 6), replace the gas control. Otherwise,
take the necessary steps to provide proper gas pressure to
the gas control.

Step-Opening Pressure Regulator

1. The gas control outlet pressure should match the

manifold pressure listed on the appliance nameplate.

2. With the main burner operating, check the gas con-

trol flow rate by using the meter clocking method or check
the gas pressure by using a manometer connected to the gas
control outlet pressure tap. Refer to Fig. 4.

3. If necessary, adjust the pressure regulator to match

the appliance rating. Refer to Table 5 or 6 for factory set
nominal outlet pressures and adjustment ranges.

a. Remove the pressure regulator adjustment cap screw.
b. Using a screwdriver, turn the inner adjustment screw

clockwise

to increase or counterclockwise

to decrease the main burner gas pressure.

c. Always replace the cap screw and tighten firmly to

safeguard proper operation.

4. If desired outlet pressure or flow rate can not be

achieved by adjusting the gas control, check the inlet pres-
sure by using a manometer at inlet pressure tap or upstream
of the gas control. If the inlet pressure is in the normal range
(refer to Table 5 or 6), replace the existing gas control.
Otherwise, take the necessary steps to provide proper gas
pressure to the gas control.

5. Carefully check main burner lightoff at the step

pressure. Make sure the main burner lights smoothly and
without flashback to the orifice and that all ports remain
lit. Cycle the main burner several times, allowing at least
30 seconds between cycles for the regulator to resume the

step function. Repeat after allowing main burner to cool.
Readjust the full rate outlet pressure, if necessary, to im-
prove lightoff characteristics.

CHECK SAFETY SHUTDOWN PERFORMANCE

WARNING

FIRE OR EXPLOSION HAZARD
CAN CAUSE PROPERTY DAMAGE,
SEVERE INJURY, OR DEATH
Perform the safety shutdown test anytime work is
done on a gas system.

NOTE: Read steps 1 through 7 below before starting and

compare to the safety shutdown or safety lockout tests
recommended for the direct ignition (DI) module. Where
they differ, use the procedure recommended for the
module.

1. Turn off gas supply.
2. Set the thermostat or controller above room tem-

perature to call for heat.

3. Watch for ignition spark or for glow at hot surface

igniter either immediately or following prepurge. See DI
module specifications.

4. If module has timed ignition, time the length of the

igniter operation. See DI module specifications.

5. After the module locks out, open gas control knob

and make sure there is no gas flow to the main burner.

6. Set the thermostat below room temperature and wait

one minute.

7. Operate system through one complete cycle to make

sure all controls operate properly.

Outlet Pressure

Nominal Factory

Outlet Setting

Adjustment

Setting Range

Model

Type of

Gas

Nominal Inlet

Pressure Range

Step

Full

Rate

Step

Full

Rate

Standard-,

Natural

1.2 - 1.7

0.9

0.7 - 1.2

Slow-opening

LP

2.9 - 3.9

2.7

2.0 - 3.0

Step-opening

Natural

1.2 - 1.7

0.2

0.9

0.7 - 1.2

LP

2.9 - 3.9

0.9

2.7

2.0 - 3.0

TABLE 6—PRESSURE REGULATOR SPECIFICATION PRESSURES IN kPa.

Outlet Pressure

Nominal Factory

Outlet Setting

Adjustment

Setting Range

Model

Type of

Gas

Nominal Inlet

Pressure Range

Step

Full

Rate

Step

Full

Rate

Standard-,

Natural

5.0 - 7.0

3.5

3.0 - 5.0

Slow-opening

LP

12.0 - 14.0

10.0

8.0 - 12.0

Step-opening

Natural

5.0 - 7.0

0.9

3.5

3.0 - 5.0

LP

12.0 - 14.0

2.2

10.0

8.0 - 12.0

TABLE 5—PRESSURE REGULATOR SPECIFICATION PRESSURES IN INCHES WC.

Summary of Contents for VR4305

Page 1: ...hour 3 4 x 3 4 300 feet3 hour 8 5 meter3 hour 30 feet3 hour 0 8 meter3 hour 415 feet3 hour 11 8 meter3 hour a Capacity based on 1000 Btu feet3 0 64 specific gravity natural gas at 1 inch wc pressure drop 37 3 MJ meter3 0 64 specific gravity natural gas at 0 25 kPa pressure drop TABLE 1 TEMPERATURE RANGES AND REGULATOR TYPES Model Number Ambient Temperature Range Regulator Type VR4305H 0 F to 175 F...

Page 2: ...P GAS WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE INJURY OR DEATH Do not attempt to use a gas control set for natural gas on LP gas or a gas control set for LP gas on natural gas To convert a gas control from natural to LP gas or from LP to natural gas contact your Honeywell representative Convert standard or slow opening gas controls from one gas to another with a conversion...

Page 3: ...gas control 3 Install sediment trap in the supply line to the gas control See Fig 2 Install Gas Control 1 This gas control can be mounted from 0 to 90 degrees in any direction from the vertical position of the gas control knob 2 Mount the gas control so gas flow is in the direction of the arrow on the bottom of the gas control Fig 2 Install sediment trap GAS CONTROL GAS CONTROL HORIZONTAL DROP PIP...

Page 4: ...All wiring including insulated quick connect terminals mustcomplywithapplicableelectricalcodesandordinances Disconnect power supply before making wiring con nections to prevent electrical shock or equipment damage 1 Check the power supply rating on the gas control and make sure it matches the available supply Install thermo stat and other controls as required 2 When the gas control is installed ex...

Page 5: ...r recom mended burner orifice pressure for the size orifice s used Make certain the primary air supply to the main burner is properly adjusted for complete combustion refer to the appli ance manufacturer instructions 2 IF CHECKING GAS INPUT BY CLOCK ING THE GAS METER Make sure that the only gas flow through the meter is that of the appliance being checked Makecertainthatotherappliancesareturned of...

Page 6: ...s allowing at least 30 seconds between cycles for the regulator to resume the step function Repeat after allowing main burner to cool Readjust the full rate outlet pressure if necessary to im prove lightoff characteristics CHECK SAFETY SHUTDOWN PERFORMANCE WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE INJURY OR DEATH Perform the safety shutdown test anytime work is done on a ga...

Page 7: ...than 200 000 cycles Service WARNING FIRE OR EXPLOSION HAZARD CAN CAUSE PROPERTY DAMAGE SEVERE INJURY OR DEATH Do not disassemble the gas control it contains no replaceable components Attempted disassembly or repair can damage the gas control CAUTION Do not apply a jumper across or short the valve coil terminals Doing so may burn out the heat anticipator in the thermostat or damage the elec tronic ...

Page 8: ...set the safety control 2 Disconnect all electric power to the appliance 3 Remove the gas control access panel 4 Push in the gas control knob slightly and turn clockwise to OFF 5 Wait five minutes to clear out any unburned gas If you then smell gas STOP Follow step 2 in the Warning in the Instructions To The Homeowner section If you do not smell gas continue with the next step 6 Turn the gas contro...

Reviews: