Honeywell VK41 R Series Instruction Sheet Download Page 5

EN1R--9137 9808R6--NE

5

Ensure combustion chamber is free of gas before

start up.
Conduct a thorough check out when installation is

completed.
At the first start the ignition controller can be in lock

out; depress reset button to free control.

Tightness test after installation

·

Apply an approved liquid leak detector to all pipe

connections.

·

Start the appliance and check for bubbles. If a leak is

found in a pipe connection, remake the joint.

A gasket leak can usually be stopped by tightening the

mounting screws. Otherwise, replace the gasket.

·

Be careful not to clog bleed vent parts with liquid leak

detector residue.

Remember bleed vents will discharge air during gas valve

opening or closing giving false indication of leakage.

CAUTION

Keep liquid leak detector away from electrical connec-

tions.

ADJUSTMENTS

WARNING

Adjustments must be made by qualified persons only.
If the appliance manufacturer supplies checkout and/

or service and maintenance instructions carefully

follow them.
If such instructions are not provided then use the

procedure outlined below.

Pressure tap

The combination gas control is provided with a pressure tap of

9 mm O.D. at inlet and outlet side.
The gas/air module is provided with pressure taps of 9 mm

outer diameter to measure the high and the low air pressure.

The air pressure difference measured on the pressure taps of

the module is reduced with the same factor as the

amplification factor is reduced compared with the actual air

pressure difference.
When checking the pressure undo the screw a half turn and

slip tube over nipple.

Ensure that screw is retightened after making test.

CAUTION

To ensure a safe closing of the valves, it is essential

that voltage over the terminals of electric operators is

reduced to 0 Volt.

Offset adjustment on CO

2

% (see fig. 1)

·

Remove cap screw with a screw driver to expose offset

adjustment screw.

·

Check gas supply pressure to the appliance using a

pressure gauge connected to the inlet pressure tap.

·

Start fan and check air flow.

·

Energize both electric operators in order to have gas input

to burner and ignite boiler.

·

Adjust CO

2

% at the desired value at low output with offset

adjustment screw. Turn offset adjustment screw counter

clockwise to increase CO

2

%.

·

Replace cap screw and tighten pressure taps.

Offset adjustment on outlet pressure

·

Remove cap screw with a screw driver to expose offset

adjustment screw.

·

Check gas supply pressure to the appliance using a

pressure gauge connected to the inlet pressure tap.

·

Control the fan to produce the air pressure difference

stated by the boiler manufacturer.

·

Energize both electric operators in order to have gas input

to burner and ignite boiler. The main burner should ignite

within 3 seconds.

IMPORTANT

Adjustments must be made in the final mounting

position to avoid shift caused by weigth of the

diaphragm

·

Because of amplification factor tolerance, it is advisable to

adjust the offset at low outlet pressures. Turn offset

adjustment screw counter clockwise to increase or

clockwise to decrease outlet pressure.

·

Replace cap screw and tighten pressure taps.

Maximum outlet pressure adjustment (depending on combination gas
control) See fig. 1

The maximium outlet pressure is an optional feature, which

can only be used in atmospheric burner applications.

The maximum outlet pressure adjustment is used to limit the

load supplied to the main burner

·

Remove cap screw with a screw driver to expose offset

adjustment screw.

·

Determine the value to which the maximum outlet pressure

is to be set. Adjustments must be made when the main

burner is burning and the fan is in the maximum air flow

position.

·

Turn the maximum outlet pressure adjustment screw

slowly until the desired pressure is obtained.

Turn adjustment screw clockwise to increase or counter

clockwise to decrease outlet pressure.

·

Replace cap screw and tighten pressure taps.

CHECKOUT

After any adjustment check pressure taps and gas connec-

tions with an approved leak detection fluid for gas leakage.
After any adjustment set appliance in operation and observe

several complete cycles to ensure that all burner components

function correctly.

MAINTENANCE AND SERVICE

Under normal circumstances no maintenance or service is

required.

WARNING

Screws on the valve that have been sealed must

never be removed.

Summary of Contents for VK41 R Series

Page 1: ...in burner of domestic central heating equipment warm air furnaces back boilers and water heaters VK41 R VK81 R combined gas controls hold a first electric on off direct operator for opening the safety valve of class A or class B according to EN161 and a second electric on off servo operator of class B or class C to EN 161 VK41 R VK81 R combined gas controls comply with the additional requirement f...

Page 2: ...onal J Side outlet K Pressure tap gas pressure 2 9 mm outer diameter L Maximum pressure regulator optional M M5 x 0 8 pressure feedback connection N Outlet Ø 18 mm or 1 2 ISO 7 1 thread O Air pressure connection low M11 x 1 P Air pressure connection high M11 x 1 Q M8 x 1 pilot outlet for 4 mm tubing R Molex 1 1 square pin header S Flange thread 3 8 or 1 2 ISO 7 1 thread T Inlet Ø 18 mm or 1 2 ISO ...

Page 3: ...ustable amplification factor Amplification factor Minimum outlet pressure mbar Range Nominal pressure mbar 3 5 5 5 1 5 7 10 10 2 5 10 5 15 15 3 5 17 5 25 25 5 5 Outlet pressure Po Outlet pressure is pressure drop across the main burner orifice Air pressure difference Pair high Pair low Offset Offset Po Pair high x A Offset range 0 5 x A 0 0 x A mbar depending on O S number Outlet pressure range 0 ...

Page 4: ...pright position i e from the position when coil is on top When mounted in 90_ from the upright position a deviation of more than 3_ can result in an unacceptable deviation of gas pressure Al least one of the air connections must be made with a metal tube with an outside diameter of 6 mm To prevent blockage due to condensation the positive air pressure connection should not be connected to combusti...

Page 5: ...r to have gas input to burner and ignite boiler Adjust CO2 at the desired value at low output with offset adjustment screw Turn offset adjustment screw counter clockwise to increase CO2 Replace cap screw and tighten pressure taps Offset adjustment on outlet pressure Remove cap screw with a screw driver to expose offset adjustment screw Check gas supply pressure to the appliance using a pressure ga...

Page 6: ...9137 9808R6 NE 6 Home and Building Control Combustion Controls Center Europe Honeywell BV Phileas Foggstraat 7 7821 AJ Emmen The Netherlands Tel 31 591 695911 Fax 31 591 695200 http europe hbc honeywell com ...

Reviews: