Honeywell VisionPRO TH8110U Installation Instructions Manual Download Page 11

TH8110U TOUCH SCREEN PROGRAMMABLE THERMOSTATS

11

69-1700

SYSTEM CHECKOUT

Installer System Test

The Installer System Test mode is used to test the HVAC 
system(s). See Table 7. While in System Test mode, 
minimum off -time for compressors is bypassed. 

The Installer Test is part of Installer Setup options. Enter 
Installer Setup screen and press Down arrow key to bring 
up test selection(s) quickly. See Fig. 16.

ADVANCED FEATURES

Outdoor or Indoor Temperature Sensor

Allow outdoor or indoor temperature sensor to absorb the 
air for a minimum of five minutes before taking a reading. 
See the Sensor instructions for more information.

Keypad 
Lockout

0670

0

Unlocked keypad 1, 2

1

—partially locked      

keypad                                              

2

—fully locked keypad

Unlocked—all 
functions are 
available.
Partially locked—
only temperature up 
and down keys and 
ability to enter and 
modify Installer 
Setup mode are 
available.                                  
Fully locked—only 
ability to enter and 
modify Installer 
Setup mode are 
available.

Temperature 
Control in Heat

0680

2

Standard 
temperature 
control in heating

1, 3

1

—less aggressive 

temperature control 
(could cause 
temperature 
undershoot)                                                                           

3

—more aggressive 

temperature control 
(could cause 
temperature overshoot)

Applies to recovery 
ramp and use of 
auxiliary heat during 
recovery.

Choose 1 if getting 
temperature 
overshoot.

Choose 3 if getting 
temperature 
undershoot.

Temperature 
Control in Cool

0690

2

Standard 
temperature 
control in cooling

1, 3

1

—less aggressive 

temperature control 
(could cause 
temperature 
undershoot)                                                                           

3

—more aggressive 

temperature control 
(could cause 
temperature overshoot)

Applies to recovery 
ramp.

Choose 1 if getting 
temperature 
overshoot.

Choose 3 if getting 
temperature 
undershoot.

Temperature 
Display Offset

0700

0

No difference in 
displayed 
temperature and 
actual room 
temperature

 -3, -2, -1, 
0, 1, 2, 3

 -3

°

F (-1.5

°

C)                                                                                    

-2°F (-1°C)                                                                              
-1°F (-.5°C)                                                                               
0 F (0.°C)                                                                                 
1°F (.5°C)                                                                                
2°F (1°C)                                                                         
3°F (1.5°C)

 —

Reset 
Thermostat

0710

0

No thermostat 
reset.

1

Resets all Installer 
Setup Options to default 
values and resets 
schedule to default 
setting. 

Only calendar 
settings and time are 
retained.

Table 6. Advanced Settings Menu. (Continued)

Select

Installer 

Setup 

Number

Factory Setting

Other Choices

Comments

Option

Description

Options

Description

Summary of Contents for VisionPRO TH8110U

Page 1: ...tion 2 Check the ratings given in the instructions to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operation Selecting Location Install the thermostat about 5 ft 1 5m above the floor in an area with good air circulation at average temperature See Fi...

Page 2: ...et of terminal identifications Table 2 that corresponds with system type conventional or heat pump in Fig 3 2 Loosen the screws for the appropriate system type selected see Table 2 Insert wires in the terminal block under the loosened screw See Fig 4 3 Securely tighten each screw 4 Push excess wire back into the hole 5 Plug the hole with nonflammable insulation to prevent drafts from affecting the...

Page 3: ...ELAY FAN RELAY R C POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED REMOVE FACTORY INSTALLED JUMPER OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR AVAILABLE ON SELECT MODELS WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE 1 1 3 2 3 OPTIONAL 24 VAC COMMON CONNECTION Y2 RC S1 R S2 W W2 Y G C 2 CONVENTIONAL M19897 OUTDOOR INDOOR TEMPERATURE SENSOR HEAT RELAY R C POWER SU...

Page 4: ...9899 OUTDOOR INDOOR TEMPERATURE SENSOR POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED FACTORY INSTALLED JUMPER OPTIONAL OUTDOOR OR INDOOR REMOTE SENSOR AVAILABLE ON SELECT MODELS WIRES MUST HAVE A CABLE SEPARATE FROM THE THERMOSTAT CABLE 1 3 2 3 Y2 RC S1 R S2 W W2 Y G C 2 CONVENTIONAL R TR C 1 TR W B R SERIES 20 MOTOR OR VALVE M19900 OUTDOOR INDOOR TEMPERATURE SENSOR FAN...

Page 5: ...splay is ready to enter calendar date Fig 15 Fig 15 Setting calendar and time after initial powerup IMPORTANT The tab on back of thermostat in lower left corner must be removed to activate this feature Using the Thermostat The thermostat has a touch screen interface Words or symbols appear highlighting keys as needed to complete tasks Press keys with your fingertips Sharp tips on pens or pencils c...

Page 6: ...ering Installer Setup 1 Thermostat must be powered either with Alkaline AAA batteries or with 24 Vac Common wire 2 From the home screen press System key Press Done or Cancel key to return to home screen 3 Five blank touch keys show on the bottom of the screen between the Done and Cancel keys Press and hold the two blank keys on either side of the center blank key for approximately five seconds unt...

Page 7: ...h 1 12 Select number that represents current calendar month Date Day 0150 15 Digit s represents current calendar date 1 31 Select number that represents current calendar date Schedule Options 0160 4 7 day programming 0 0 nonprogrammable System Type Selection 0170 1 1 Heat 1 Cool Conventional System 1 6 1 1 heat 1 cool 2 single stage heat pump no aux heat 3 heat only no fan 4 heat only with fan 5 h...

Page 8: ...ge changes default cph for 2nd stage heat Continuous Backlight 0280 0 Backlight not on continuously Thermostat backlight comes on with each key press 1 Backlight is on continuously thermostat must have a common wire attached for this function Option is always shown however continuously on backlight works only if thermostat is wired with 24 vac Common Additional Menu Choices 0290 0 Only main menu o...

Page 9: ... 5 F 3 C 6 6 F 3 5 C 7 7 F 4 C 8 8 F 4 5 C 9 9 F 5 C Shown only if automatic changeover is selected Temperature Indication Scale 0320 0 Temperature is displayed in F 1 Temperature is displayed in C Daylight Savings 0330 1 Daylight savings enabled United States 0 0 daylight savings is disabled Set to 0 in areas that do not follow daylight savings Remote Temperature Sensor Outdoor or Indoor 0340 0 N...

Page 10: ... 0540 4 Four periods available Wake Leave Return Sleep 2 Two periods availbable Wake and Sleep Not shown in non programmable is selected 2 or 4 applies to all days of the week Minimum Compressor Off Time 0580 5 Five minute minimum off time for compressor 0 2 3 4 Minimum number of minutes compressor is off between calls for compressor Heat Temperature Range Stop 0600 90 Highest heating setpoint 40 ...

Page 11: ...Standard temperature control in heating 1 3 1 less aggressive temperature control could cause temperature undershoot 3 more aggressive temperature control could cause temperature overshoot Applies to recovery ramp and use of auxiliary heat during recovery Choose 1 if getting temperature overshoot Choose 3 if getting temperature undershoot Temperature Control in Cool 0690 2 Standard temperature con...

Page 12: ...heck for 24 Vac between C and Rc Verify AAA batteries installed correctly and good Temperature settings do not change The upper or lower temperature limits were reached Check temperature setpoints Check Installer Setup Numbers 0600 and 0610 modify The keypad is fully locked Check Installer Setup Number 0670 to change keypad lock options Heating or cooling does not come on Thermostat minimum off ti...

Reviews: