VGF FLANGED GLOBE VALVES

3

62-0213

Mounting Actuator

For information on mounting, refer to the Product Data 
literature for the actuator. Actuator installation clearances 
are provided. It is important to have the correct actuator 
available for the installation. See Table 2 for basic 
clearance information.

Table 2. Installation Clearances 

(from Valve Bonnet, B).

Fig. 5. Flanged valve body installation.

Fig. 6. Dimensions for valve installation.

Table 3. Valve Sizes and Dimensions.

a

Three-way valves only.

NOTE: See VGF family Product Data sheet 

(form 63-2618) for complete specifications.

CHECKOUT

For instructions for operating the valve actuator, see the 
Product Data sheet for the specific actuator. Operate the 
control system and check the valve operation to 
determine that the valve stem positions the valve 
smoothly through full stroke without binding.

Actuator

Minimum 

Vertical Clearance

 in in. (mm)

ML6420, ML7420

12-11/16 (322)

ML6421A, ML7421A

14-1/4 (360)

ML6421B, ML7421B

16-7/8 (430)

ML6425A,B; ML7425A,B

14-5/16 (364)

MN/MS  Q5020

12 (305)

ML6984, ML7984
Modutrol IV + Q5001

14-1/2 (369)

MP953C (8 inch dia)

11-7/8 (302)

MP953C (13 inch dia)

17-11/16 (449)

MP953E (8 inch dia)

16-1/2 (420)

MP953E (13 inch dia)

25-13/16 (655)

COMPANION
FLANGE

GASKET

GASKET

GASKET

BE SURE FACE OF COMPANION FLANGE IS FLUSH
WITH FACE OF VALVE-BODY FLANGE AND ALIGNED
SQUARELY BEFORE TIGHTENING MOUNTING NUTS.

OPTIONAL SERVICE FLANGE

COMPANION FLANGE

PIPE

M7977

Size

Dimensions, in. (mm)

See Fig. 6

in.

DN

A

D

a

ANSI Class 125

2-1/2

65

10-7/8 (276)

3-3/4 (95)

3

80

11-3/4 (298)

4-3/8 (111)

4

100

13-7/8 (352)

5-1/8 (130)

5

125

15-3/4 (400)

5-3/4 (146)

6

150

17-3/4 (451)

6-5/8 (168)

ANSI Class 250

2-1/2

65

11-1/2 (292)

3-3/4 (95)

3

80

12-1/2 (318)

4-3/8 (111)

4

100

14-1/2 (368)

5-1/8 (130)

5

125

16-5/8 (422)

5-3/4 (146)

6

150

18-5/8 (473)

6-5/8 (168)

M22409

D

A

C

B

1

DOTTED LINE REPRESENTS ANSI 125 
VALVE BONNET.

1

E

Stroke  Y

Summary of Contents for VGF

Page 1: ...VGF Valves Safety The valves are to be installed by skilled personnel and in strict accordance with the installation instructions and local regulations See Fig 1 for proper hoisting method Honeywell assumes no responsibility for damages or injuries resulting from non compliance with installation instructions or standard good practice when mounting operating or maintaining the valves even if not ex...

Page 2: ... Location Select a location where the valve and actuator are accessible Allow sufficient space for servicing the valve and actuator See Fig 6 for valve body dimensions Mounting the Valve See Fig 5 for typical installation 1 Hoist valve by its body only Do not lift by stem bonnet flanges or flange holes See Fig 1 2 Install the valve so the flow follows the direction of the arrow indicated on the va...

Page 3: ...ull stroke without binding Actuator Minimum Vertical Clearance in in mm ML6420 ML7420 12 11 16 322 ML6421A ML7421A 14 1 4 360 ML6421B ML7421B 16 7 8 430 ML6425A B ML7425A B 14 5 16 364 MN MS Series Q5020 12 305 ML6984 ML7984 Modutrol IV Q5001 14 1 2 369 MP953C 8 inch dia 11 7 8 302 MP953C 13 inch dia 17 11 16 449 MP953E 8 inch dia 16 1 2 420 MP953E 13 inch dia 25 13 16 655 COMPANION FLANGE GASKET ...

Page 4: ... 9 04 www honeywell com Automation and Control Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 ...

Reviews: