Honeywell VGF Installation Instructions Download Page 2

VGF FLANGED GLOBE VALVES

62-0213

2

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow 
them could damage the product or cause a 
hazardous condition.

2.

Check ratings given in instructions and on the 
product to ensure the product is suitable for your 
application.

3.

Installer must be a trained, experienced service 
technician.

4.

After installation is complete, check out product 
operation as provided in these instructions.

WARNING

Severe Burn Hazard.
Contact with hot liquid can lead to severe 
injury or cause death.

Release system pressure and isolate or drain the 
valve pipe section so the medium (steam, water 
or glycol solution) does not leak out of the valve 
body during installation (see Fig. 3).

CAUTION

Electrical Shock or Equipment Damage Hazard.
Can shock individuals or short equipment
 circuitry.

Disconnect power supply to the actuator to 

prevent electrical shock and equipment 
damage, or remove and cap the air line to the 
actuator.

IMPORTANT

• Before installing the valve, raise and lower the 

valve stem to make sure that the valve stem 
operates freely. Impaired stem operation can 
indicate that the stem was bent by rough 
handling. This condition can require replacing 
the valve.

• Protect the stem from damage due to bending 

or scratching.

Fig. 3. Piping must prevent leakage.

Location

Select a location where the valve and actuator are 
accessible. Allow sufficient space for servicing the valve 
and actuator. See Fig. 6 for valve body dimensions.

Mounting the Valve

See Fig. 5 for typical installation.

1.

Hoist valve by its body only. Do not lift by stem, 
bonnet, flanges, or flange holes. (See Fig. 1.)

2.

Install the valve so the flow follows the direction of 
the arrow indicated on the valve body.

3.

Install the valve so the actuator is above the valve 
body. The valve can be installed in any position 
between vertical and horizontal. Do not install the 
valve with the stem below horizontal or upside 
down.

4.

When controlling steam, use appropriate high 
temperature kit 43196000 and rotate valve body so 
that actuator is not positioned directly above the 
piping.

5.

Use companion flanges with the same number of 
bolt holes and dimensions as the valve to be 
installed. The optional service flange may be 
installed in the lower port. See Table 1 for part 
numbers. Use standard cast-iron flanges for the 
two end ports.

6.

Use a gasket material recommended for the 
medium to be handled.

7.

Use mounting bolts long enough so the nuts can 
use the full length of the nut threads. (See Fig. 4.
Use bolts 1/8 in. smaller than the diameter of the 
bolt hole to allow clearance for installing. (See 
Fig. 5.)

Table 1. Service Flange Part Numbers.

Fig. 4. Basic proper bolt length.

Valve Size 

in in. (mm)

ANSI 125

ANSI 250

2 1/2 (65) 

208628

208633

3 (80)

208629

208634

4 (100)

208630

208635

5 (125)

208631

208636

6 (150)

208632

208637

133 in-lb
 (15 Nm)

Summary of Contents for VGF

Page 1: ...VGF Valves Safety The valves are to be installed by skilled personnel and in strict accordance with the installation instructions and local regulations See Fig 1 for proper hoisting method Honeywell assumes no responsibility for damages or injuries resulting from non compliance with installation instructions or standard good practice when mounting operating or maintaining the valves even if not ex...

Page 2: ... Location Select a location where the valve and actuator are accessible Allow sufficient space for servicing the valve and actuator See Fig 6 for valve body dimensions Mounting the Valve See Fig 5 for typical installation 1 Hoist valve by its body only Do not lift by stem bonnet flanges or flange holes See Fig 1 2 Install the valve so the flow follows the direction of the arrow indicated on the va...

Page 3: ...ull stroke without binding Actuator Minimum Vertical Clearance in in mm ML6420 ML7420 12 11 16 322 ML6421A ML7421A 14 1 4 360 ML6421B ML7421B 16 7 8 430 ML6425A B ML7425A B 14 5 16 364 MN MS Series Q5020 12 305 ML6984 ML7984 Modutrol IV Q5001 14 1 2 369 MP953C 8 inch dia 11 7 8 302 MP953C 13 inch dia 17 11 16 449 MP953E 8 inch dia 16 1 2 420 MP953E 13 inch dia 25 13 16 655 COMPANION FLANGE GASKET ...

Page 4: ... 9 04 www honeywell com Automation and Control Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 ...

Reviews: