background image

Vertex Continuous Gas Monitor

Operating Manual

Table of Contents

Introduction

Installation

Startup

Operation

Maintenance

Troubleshooting

Installation Drawings

cifica i s

Detectable Gases

Replacement/Consumable

Optional Relay Specs

Network Interfaces

LIT Option

Warranty Statement

Summary of Contents for Vertex

Page 1: ... Manual Table of Contents Introduction Installation Startup Operation Maintenance Troubleshooting Installation Drawings cifica i s Detectable Gases Replacement Consumable Optional Relay Specs Network Interfaces LIT Option Warranty Statement ...

Page 2: ...ing tripping hazards minor corrosive dangers Also used when defining personal protective equipment gloves dust masks etc Personal injury risk machinery hazards around guarded equipment moving parts crush pinch hazards flying debris and arc flash hazards The most dangerous or potentially lethal hazards unguarded equipment confined space entrances and lockout labels Caution possibility of electric s...

Page 3: ...abling At a very minimum all cables should include a braided shield Ideal results have been obtained with twisted pair cabling which has a foil shield surrounding each pair plus foil and 90 braid shielding around the bundle In addition ensure local electrical code requirements are met The following cable parameters must be considered Braid Must have a minimum 90 coverage Foil When used with braid ...

Page 4: ...eved with high quality connectors providing 360 shield coverage These connectors generally had metal shells Failure to properly secure the connector to the equipment will result in high emission levels Also poorly constructed or improperly assembled connectors can be a high source of radiated noise and provide a path for external signals into the monitor ...

Page 5: ...st and Wiring Ports 1 5 1 2 4 Module Front Door Closed 1 6 1 2 5 Analyzer Side Panel exterior 1 7 1 2 6 Analyzer Side Panel interior 1 8 1 2 7 Sample Tubing Connections detail 1 9 1 2 8 System Controls behind screen 1 10 1 2 9 Analyzer Front 1 12 1 2 10 Data Acquisition Computer rear 1 13 1 2 11 ChemCam USB Hub 1 15 1 2 12 Back of Chemcassette Module 1 16 1 2 13 Main PLC 1 17 1 2 14 Relay Option P...

Page 6: ...the Installation Site 2 3 2 2 1 Placement of the Vertex System 2 3 2 2 2 Exposure to Dust and Humidity 2 3 2 2 3 Sample Transport Time 2 3 2 2 4 Monitor Dimensions 2 3 2 2 5 Sample Locations 2 4 2 2 6 Sample Line Particulate Filter Use 2 4 2 3 Optional Floor Mounting 2 4 2 4 Installing Sample Lines Filters 2 4 2 4 1 Sample Line Installation Requirements 2 5 2 4 2 Sample Line Connections 2 6 2 4 3 ...

Page 7: ... 2 21 Validating the System 2 22 3 Startup 3 1 Startup 3 2 3 1 1 Initial Startup 3 2 3 1 2 Factory Configuration 3 2 3 2 Getting Started 3 3 3 3 Verify Installation 3 3 3 4 Startup Sequence 3 4 3 5 Power Up 3 5 3 6 Start Program 3 7 3 7 Configuration Utility 3 9 3 7 1 Define Gas Location 3 21 3 7 2 Configure Analyzers and Points 3 23 3 7 3 Set Analyzer Window 3 24 3 7 4 Configure Point 3 25 3 7 5 ...

Page 8: ...4 1 Introduction 4 2 4 2 Monitoring Mode Overview 4 2 4 3 Main Screen 4 3 4 3 1 System Display Area 4 4 4 3 2 Point Detail Display Area 4 8 4 3 3 Function Buttons 4 10 4 4 Project Functions 4 11 4 4 1 Log In and Log Out 4 12 4 4 2 Changing Password 4 13 4 4 3 Updating Program 4 14 4 4 4 Restore OnScreen Keyboard 4 14 4 4 5 Stopping Project 4 14 4 5 Review Functions 4 15 4 5 1 Event History 4 15 4 ...

Page 9: ...te Analyzer Particulate Filters 5 5 5 3 3 Remove Filters 5 6 5 3 4 Replace Filters 5 7 5 3 5 Change Chemcassette Tape 5 8 5 4 Replacing an Analyzer 5 9 5 4 1 Disconnecting Cables 5 9 5 4 2 Remove Analyzer 5 11 5 4 3 Install Analyzers 5 11 5 5 Remove and Replace Pyrolyzer Filters 5 12 5 5 1 Remove Filters 5 12 5 5 2 Replace Filters 5 13 5 6 Remove and Install Pumps 5 14 5 6 1 Remove Pump 5 15 5 6 2...

Page 10: ... 4 B 4 Nominal Transport Times B 5 C Detectable Gases C 1 Detectable Gases C 2 D Replacement and Consumable Items D 1 Consumables D 3 D 1 1 Chemcassettes D 3 D 1 2 End of Line Particulate Sample Filters See Appendix B D 3 D 1 3 Common to all Analyzers Series 1 or Series 2 Chemcassette or Pyrolyz ers D 3 D 1 4 Common to all Pyrolyzers Series 1 or Series 2 D 3 D 1 4 1 Series 1 Analyzers Chemcassette...

Page 11: ...3 3 Common to all Rack Systems Series 1 or Series 2 D 5 D 3 3 1 Series 1 Rack Systems D 5 D 3 3 2 Series 2 Rack Systems D 6 D 3 4 Common to all Pump Modules Series 1 or Series 2 D 6 D 3 4 1 Series 1 Pump Module D 6 E Optional Relay Specifications E 1 Relay Output Contacts E 2 E 2 Relay Contact Ratings E 3 E 3 Default Relay Assignments E 4 E 3 1 Introduction E 4 E 3 2 Main PLC E 5 E 3 3 Optional Re...

Page 12: ...F 7 ControlNet Interface F 14 F 8 DF1 Interface P N1295 0343 F 15 F 9 Modbus Plus Interface F 16 P N1295 0330 F 16 F 10 LonWorks Interface F 17 P N 1295 0329 F 17 F 11 Modbus TCP P N1295 0520 F 18 F 11 1 Configuring the IP Address F 18 F 12 Ethernet CIP P N1295 0519 F 20 F 12 1 Configuring the IP Address F 22 F 13 RSView32 Active Display F 23 Set Up Instructions F 23 G Line Integrity Test Option H...

Page 13: ...VertexTM 72 Point Continuous Monitor Vertex Technical Handbook 1 1 1 Introduction ...

Page 14: ...nt analyzer modules allow one to stop monitoring with no effect on the remaining modules Power supplies are redundant Pumps are redundant The system powers up in the same state as when powered down Filters Chemcassettes and major components in one of the analyzers can be replaced while the remaining analyzers continue to function Operation can be through an LCD touch screen or through a local area...

Page 15: ... 3 Sample Tubing Connections detail Pyrolyzer Analyzer Module Front Door Closed detail Analyzer Side Panel exterior Analyzer Side Panel interior Exhaust and Wiring Ports System Controls behind screen Universal Chemcassette Analyzer Analyzer Front 1 2 1 Vertex Front ...

Page 16: ...2 Point Continuous Monitor Vertex Technical Handbook 1 4 Relay Wire Raceway Data Acquisition Computer rear ChemCam USB Hubs Back of Chemcassette Module Rear Main Power Main PLC Relay Option PLC 1 2 2 Vertex Back ...

Page 17: ...exTM 72 Point Continuous Monitor Vertex Technical Handbook 1 5 System Exhaust 0 5 in 12 7 mm tubing AC Input 0 75 in pipe thread Alarm Wiring Conduit Plates 4 in 101 6 mm x 2 1 2 3 Exhaust and Wiring Ports ...

Page 18: ...VertexTM 72 Point Continuous Monitor Vertex Technical Handbook 1 6 1 2 4 Module Front Door Closed Protective panel over touch screen Open to use Pyrolyzer Analyzer Analyzer Status LED Slot Tier 1 Tier 2 ...

Page 19: ...VertexTM 72 Point Continuous Monitor Vertex Technical Handbook 1 7 1 2 5 Analyzer Side Panel exterior Slide Latch Access Screws ...

Page 20: ...int Continuous Monitor Vertex Technical Handbook 1 8 1 2 6 Analyzer Side Panel interior Analyzer CPU Proportional Valve Filters ChemCam Option Sample Pressure Transducers Sensor Interface PCB Sample Flow Transducers ...

Page 21: ...Technical Handbook 1 9 1 2 7 Sample Tubing Connections detail Tier 1 Tier 2 Tier 3 Slot 1 Slot 2 Slot 3 Points 1 thru 8 Left to Right 4 Port Manifold for multiple gas sampling See Section B 4 Nominal Transport Times for tubing length limitations ...

Page 22: ... behind screen Series 2 Units Power Distribution Module Rack Power Switch and Circuit Breaker Data Acquisition Computer DAq Hot Swap Hard Drives Set Supply Vacuum 24 VDC Power Supplies DVD Drive Analyzer Communications Hub Ethernet Analyzer DC and Pyrolyzer AC Power Switches with Indicators ...

Page 23: ... Handbook 1 11 Series 1 Units Power Distribution Module Rack Power Switch and Circuit Breaker Data Acquisition Computer DAq 24 VDC Power Supplies CD RW Drive Analyzer Communications Hub Ethernet Analyzer DC and Pyrolyzer AC Power Switches with Indicators ...

Page 24: ...VertexTM 72 Point Continuous Monitor Vertex Technical Handbook 1 12 1 2 9 Analyzer Front Analyzer Window Analyzer Status LED Mounting Slot for Optional Keyboard Product Label location of RoHS sticker ...

Page 25: ...t USB Ports USB Connection to the Hosting Device Mouse Connection Keyboard Connection Note is oto s o s a t ical ort configuration ort and slot locations on our onitor a ar 1 2 10 Data Acquisition Computer rear Series 2 Units white cable Serial Connection to the PLC COM8 Caution estrict access to t e ort to reduce t e ris o alicious so t are eing introduced ...

Page 26: ... o s a t ical ort configuration ort and slot locations on our onitor a ar Serial Interface for Touch Screen COM 1 Parallel Printer Port LCD Video Internal Ethernet Network USB Port Serial to PLC COM2 External Ethernet Network Mouse Connection Keyboard Connection Modem Series 1 Units ...

Page 27: ...VertexTM 72 Point Continuous Monitor Vertex Technical Handbook 1 15 1 2 11 ChemCam USB Hub ChemCam USB Hubs 3 ...

Page 28: ...book 1 16 1 2 12 Back of Chemcassette Module Circular Tubing Harness Cable Carrier ChemCam USB Connection option Analyzer Communications Ethernet Analyzer 24V Power Supply Multifunction Connector Note onnection secured slide latc us u to o en us do n to close ...

Page 29: ...andbook 1 17 1 2 13 Main PLC Advanced Interface Converter PLC Power Supply DH485 Link Coupler Connection to optional 4 20mA System PLC Processor Module Optional Relay Modules DH485 RS232 Interface Module Expansion slot for optional Communications Interface ...

Page 30: ...VertexTM 72 Point Continuous Monitor Vertex Technical Handbook 1 18 1 2 14 Relay Option PLC Power Supply Relay Module up to seven cards ...

Page 31: ...ance Remove and Replace Chemcassette Analyzer Particulate Filters Change Chemcassette Tape Diagnostics Service Alarm Test Fault Test 4 20 mA Test Authorized Service Security Access Configuration Utility Project Functions Define Gas Location Configure Analyzers and Points Set Analyzer Window Configure Point Define and Assign Relays Profile Management File Menu Other Menu Log In and Log Out Changing...

Page 32: ...CC PYRO Slot 1 Slot 2 Slot 3 Table 1 1 Module Tier Structure Chemcassette modules occupy one slot each However Pyrolyzer Chemcassette modules are to be installed in slots 1 and 2 Pyrolyzer configuration and status information will appear in slot 2 Number of Points Installed into Slots Total Possible per Vertex System Chemcassette 8 1 2 or 3 9 Pyrolyzer 8 1 and 2 Only 3 Table 1 2 Required Slots Exa...

Page 33: ...low are Transport flow high velocity large volume air movement through the lines Sampleflow airadmittedtotheChemcassette detection system The high speed of transport flow allows rapid monitoring and response time when using long lines from monitored locations to the Vertex System A small portion of the transport flow sample flow is analyzed to determine concentration levels The complete sampling a...

Page 34: ...ection system Analyzer modules sample and detect a specific gas or family of gases Each eight point Analyzer module Manages Chemcassette tape transport Provides optical detection of stain Directs sample flow through the Chemcassette Stores data for retrieval by the data acquisition computer Components of the detection system include Chemcassette detection tape Optics and electronics for the detect...

Page 35: ...VertexTM 72 Point Continuous Monitor Vertex Technical Handbook 1 23 1 6 2 Stain Pattern The following chart shows the stain pattern of sample detection on the Chemcassette tape ...

Page 36: ...portional to the gas concentration An LED in the detector head illuminates the sample stain and the detector then optically measures the stain Legacy Detection System Reference detector Surface mount LED Light pipe Detector Inlet Sample outlet Chemcassette tape Flow CLO Detection System In the Closed Loop Optics CLO detection system a reference detector monitors and controls the intensity of the L...

Page 37: ...emCam The ChemCam is a small video camera located between the take up reel and the optic head on the module It provides a means to observe alarm level stains 1 6 5 Sample Filters The Chemcassette module includes three types of filters in the sample flow system Particulate filters protect the internal precision orifice from dust particles An acid filter is used on the common line to the pumps Both ...

Page 38: ...particulate filters and one acid scrubber which are identical to the standard Chemcassette filters The left filter compartment houses eight charcoal filters which remove the following compounds Freon 12 Freon 116 Freon 13 HF Freon 21 HCl Freon 113 Cl2 Freon 114 Freon is a registered trademark of E I du Pont de Nemours Company DuPont The charcoal filters may also remove other compounds Contact Hone...

Page 39: ...connects to the manufacturing facility central toxic exhaust system Note e e aust line ro t e erte s ould not e ceed eet The pumps are located in the bottom of the Vertex System cabinet inside a sound deadening enclosure to reduce noise Three cooling fans circulate air over the pumps The Vertex System draws cooling air in through a filter mounted on the pump module access door Pump Status Indicato...

Page 40: ... System equipped with two or more types of Analyzer modules can monitor more than one gas or groups of gases such as hydrides or mineral acids at a location Each Vertex Analyzer module can monitor only one gas family such as hydrides or mineral acids Optional Four port manifold for multiple gas monitoring ...

Page 41: ...ertex System It configures the analyzers stores data and provides a network interface for data transfer to other computers System display and operator control is through an on screen keyboard or an optional external keyboard CAUTION 1 10 2 Programmable Logic Controller The Programmable Logic Controller PLC is the control system path between the DAq and the individual analyzers The PLC polls the an...

Page 42: ...VertexTM 72 Point Continuous Monitor Vertex Technical Handbook 2 1 2 Installation ...

Page 43: ...start up procedure for the Vertex System consists of seven steps described in this and the following sections 2 2 Surveying the Installation Site 2 3 Optional Floor Mounting 2 4 Installing Sample Lines Filters 2 5 Installing Pump Exhaust Line 2 6 Electrical Power 2 7 Data Acquisition System 2 8 Wiring Alarm Relays ...

Page 44: ...ex System up to 400 ft 122 m from sample locations 2 2 2 Exposure to Dust and Humidity Exposure to corrosive gases or materials excess moisture dust and other unusual environmental conditions could seriously hamper the unit s monitoring ability and could cause damage to it Allow room around theVertex System for ventilation and servicing 2 2 3 Sample Transport Time Install the Vertex System central...

Page 45: ... installing sa le lines to deter ine our co an s olic related to sa ling locations and onitoring o t e desired sa le gas 2 2 6 Sample Line Particulate Filter Use See Appendix B Specifications to determine which filter type should be used at the location 2 3 Optional Floor Mounting For added protection with optional floor mounts prepare floor anchors to secure the base of the cabinet and prevent ti...

Page 46: ...e Appendix B Specifications for transport times Avoid running sample lines through areas of great temperature extremes such as adjacent to steam or chiller lines Sample lines should not be crimped bent to less than a 12 in 30 5 cm radius or placed in an area where weight could collapse the tubing Sample lines should be easily accessible for periodic inspection Where possible leave as many bends ex...

Page 47: ... the tube has passed through both the external grab ring and the internal O ring and is firmly seated against the stop The insertion depth for a correctly installed sampling line is 1 2 in to 5 8 in 12 mm 16 mm Verify the insertion depth by holding the tube and marking with your thumb where it emerges from the fitting Remove the tube to measure the insertion depth CAUTION Improper installation of ...

Page 48: ...o less than a 12 in 30 5 cm radius Where possible leave as many bends exposed for periodic visual inspection of the line for kinked or damaged tubing Varying exhaust pressure can induce pump failure or flow faults 2 5 2 Exhaust Line Connection The instrument includes 20 ft 6 m of 3 8 in 10 mm I D x 1 2 in 13 mm O D Teflon tubing Insert the tubing into the exhaust port on the top of the unit to the...

Page 49: ...em requires a dedicated AC circuit rated at 230 volts 50 60 Hz 15 Amp single phase providing hot neutral and ground lines Line voltage should fluctuate no more than 10 The external switch must be clearly labeled and installed in accordance with local electrical codes Input power cable should be 14 AWG minimum The safety ground wire must be the same or larger gauge as the line wires Connect AC powe...

Page 50: ...a multimeter to determine the connections are correct and correct voltages are present at the power connection Note eries and eries erte o er connection oints di er slig tl in t eir a earance and are illustrated in igures and elo Figure 2 Vertex Series 1 Figure 3 Vertex Series 2 Verifying Line Connection Touch the red multimeter lead to the line hot connection and touch the black lead to the groun...

Page 51: ... 5 Verifying Neutral Connection Verifying Operating Voltage Touch the red multimeter lead to the line hot connection and touch the black lead to the neutral see Figure 6 The meter should display a voltage value of 230 VAC 10 Figure 6 Verifying Line to Neutral Note ter confir ing line and neutral connections and t e o erating oltage is it in t e s eci fied range o er u t e erte and c ec t e o erati...

Page 52: ... electricians or approved Honeywell Analytics service representatives should perform these tasks Honeywell Analytics is not liable for any damages caused by incorrect installation by unauthorized or unqualified third parties of electrical apparatus to the Vertex monitor Design Characteristics UL 3R enclosures for indoor and outdoor service Electrostatically shielded for quality power on sizes 1 KV...

Page 53: ... to H6 H1 and H8 Secondary Voltage Interconnect Connect Lines to 240 X2 to X3 X1 and X4 Connect X4 to Ground and Shield Step Up Wiring 0060 1021 as Step Up Transformer 208v to 240v 120 208 240 277 Volt Primary 120 240 Volt Secondary Taps None SHIELD H8 H5 H6 H7 H1 H4 H3 H2 X1 X3 X2 X4 Line In 208v Line In Neutral Line In Ground To Vertex Ground To Vertex Neutral To Vertex Line Single 208VAC Line I...

Page 54: ...transformer protection is not required 1 Primary and secondary protection is required if the transformer has more than two wires on the secondary circuit 2 If the branch circuit feeding the transformer has overcurrent protection to meet the individual primary overcurrent protection requirements in Example 3 then individual primary protection is not required Secondary OCP is required as shown below...

Page 55: ...re rise of the unit Coils Coil conductors shall be either aluminum or copper and must be continuous The entire core and coil assembly shall be impregnated with a thermal setting varnish and cured to reduce hot spots in the coils and seal out moisture Coils with exposed magnet wire will not be acceptable Transformers shall have common core construction All transformers shall incorporate a faraday e...

Page 56: ...entilated transformers are to be floor mounted to a concrete pad The transformer enclosure must be grounded by the installer in accordance with the latest edition of the National Electric Code and any local codes or ordinances Performance Audible sound levels will not exceed limits established in NEMA ST 20 10 to 50 KVA 45 db 51 to 150 KVA 50 db 151 to 300 KVA 55 db 301 to 500 KVA 60 db Transforme...

Page 57: ...ure power is disconnected at the source prior to servicing alarm contacts Series 2 Rack Power Switch Series 1 Rack Power Switch Rack Power Switch 2 6 4 Power On Off An internal rack power switch is located behind the touch screen door After performing self diagnostics the Vertex System main screen opens and the system returns to the same state it was in prior to power down ...

Page 58: ...een keyboard operates similar to a standard keyboard except when using modifier keys CTRL ALT or SHIFT To use modifier keys 1 Touch the modifier key The key changes to show the modifier key is locked down 2 Press the second key of the key combination On screen Keyboard 2 7 1 Optional Keyboard An optional keyboard with touch pad is stored behind the display Use the keyboard to enter text fields at ...

Page 59: ...ex Technical Handbook 2 18 Hooking keyboard to the front of the system To install the keyboard 1 Open the display 2 Remove keyboard from storage shelf All cables are connected Hook front of keyboard tray into slot under first tier of analyzers ...

Page 60: ... 3 Release pins to lock tray into side of rails of cabinet 4 Close and latch display 2 7 2 Printer TheVertex System software can be programmed to print to either a network or local printer To install a local printer connect it to the parallel printer port as shown You may also use the USB port The correct printer driver must also be installed Printer Connections Parallel Printer Port USB Port ...

Page 61: ...osure 2 7 4 Network Computer Security TheVertex relies on the RSView system of accounts and passwords to prevent unauthorized tampering as described in section 4 6 6 of this manual Microsoft Windows provides its own system of accounts and passwords However RSView32 requires that Windows be run in an account with administrator privileges Attempting to run the Vertex RSView32 application in a Window...

Page 62: ...accommodate installation of external devices Relay panels are located at the back of the Vertex System See Appendix E Optional Relay Specifications for for information i i i i s To wire the alarm relays Use agency approved wire such as NRTL in the U S with 300 volt insulation CAUTION Make sure there is proper separation between the 230 volt power supply and alarm wiring Route relay wiring through ...

Page 63: ...ot use the Vertex System power supply for external alarm power Note a e sure all connections co l it a li ca le standards Validating the System The Vertex and Chemcassette products design manufacture and recommended maintenance ensure the correct operation of the system For validation or commissioning after installation by gas exposure these Technical Notes are available upon request from Honeywel...

Page 64: ......

Page 65: ...3 1 2 Factory Configuration ...

Page 66: ...3 2 Getting Started ...

Page 67: ......

Page 68: ......

Page 69: ......

Page 70: ...3 6 Start Program CAUTION ...

Page 71: ......

Page 72: ...3 7 Configuration Utility ...

Page 73: ...Set Initial Configuration Configure Analyzer Points Define Gas Location Names ...

Page 74: ...Define and Assign PLCs Information See Summary Information ...

Page 75: ...Install Current Profile File Save Save As Close Window Done Install Profile Status Open Profile ...

Page 76: ...Inverted Gas Alarm Relays Non Latching Gas Alarm Relays ...

Page 77: ...Disabled Alarm Action Gas Relays Disabled or Full No Gas Events ...

Page 78: ...Set Timeout Values Internal Filter Life in Days User Specified Auto Logout ...

Page 79: ...1st TWA Time ...

Page 80: ...o ten to a oid filling a aila le dis s ace Logging Rate DB Management ...

Page 81: ...Database Management Retention Periods Event Record Retention Period Logged Data Record Retention Period ...

Page 82: ...20 mA PLC Installed Fieldbus Fieldbus Parameters ...

Page 83: ...Use mg m3 units Profile Description User File Rev ...

Page 84: ...3 7 1 Define Gas Location Add New Entry Long names Short names Replace Selected Item Delete Selected Item ...

Page 85: ......

Page 86: ...3 7 2 Configure Analyzers and Points ...

Page 87: ...3 7 3 Set Analyzer Window Family Chemcassette ChemCam AutoPicture ...

Page 88: ...ChemCam AutoPicture 3 7 4 Configure Point Lower Detection Limit LDL level ...

Page 89: ......

Page 90: ...Alarm Level 1 and Alarm Level 2 ...

Page 91: ...Alarm Level 1 Alarm Level 2 User programmable LDL see page 3 25 ...

Page 92: ...Log never Log always Log if filling a aila le dis s ace PLC F S Conc Data Output ...

Page 93: ...Unit choices are F S mg m3 ...

Page 94: ...No Monitoring Associated HTM File Perform Optional Line Integrity Test ...

Page 95: ...Line Integrity Test PLC Network Generate Window Zero Reset Faults Generate Accelerated CC Usage Faults Virtual Reference ...

Page 96: ...Virtual Reference Function c fi ...

Page 97: ...3 7 5 Define and Assign Relays ...

Page 98: ...3 7 6 Configure PLC PLC Relay Cards Relays per Card ...

Page 99: ...Fault Relay Count alar rela definitions ou c ange t e nu er o ault rela s t e current rela definitions eco e in alid and ust e redefined Shift Pad ...

Page 100: ...3 7 7 Set Alarm Relays ting alar rela definitions ou c ange t e definitions a c ange and ust e redefined ection onfigure ...

Page 101: ...Selected relay in the Clear all alarm definitions from relays Squares that represent the point or points to associate with the relay ...

Page 102: ...3 7 8 Set Fault Relays configura le ee ection onfigure ...

Page 103: ......

Page 104: ...3 7 9 Profile Management File Menu ...

Page 105: ...3 7 10 Other Menu Copy Az definition Copy Gas Location Name Copy htm File Name Alarm Defaults ...

Page 106: ...3 7 11 Profile Management Utility ...

Page 107: ...3 8 Load Tape ...

Page 108: ...9 Verify Flow Rates and Supply Vacuum 3 9 1 Set Supply Vacuum Series 2 ains a not e a le to ac ie e g n t is case t e a i u ac ie a le sa le oint o rate s o n 3 9 2 Verify Flow Rates Supply Vacuum Adjust ...

Page 109: ...Flow cc min Point Vacuum in Hg Vacuum Selection Pad Optional Line Integrity Test Option ...

Page 110: ...Target Flow Flow Rate ...

Page 111: ...Range Minimum Flow Maximum Flow ...

Page 112: ...3 10 Leak Checking Sample Lines 3 11 Reconfigure ...

Page 113: ...ower is disconnected at the source prior to servicing alarm contacts A NIN sample areas For leak tight connections fol low the instructions in the Installing Pump Exhaust Line section and the Remove Pump section ith the system running verify the leak integrity with a small amount of leak test fluid ...

Page 114: ...3 13 System Shut Down CAUTIO Failure to properly shut down the ertex could result in system file corruption ...

Page 115: ......

Page 116: ......

Page 117: ...in ust e s ut do n e ore closing t e ser er ailure to do t is ill result in t e ser er ...

Page 118: ......

Page 119: ......

Page 120: ......

Page 121: ......

Page 122: ......

Page 123: ...Pump Health Indication Pump Operation Indication Pump Status Indicator ...

Page 124: ......

Page 125: ...fi i ...

Page 126: ......

Page 127: ...a il at a ti e en ou configure t e erte ...

Page 128: ......

Page 129: ......

Page 130: ......

Page 131: ......

Page 132: ......

Page 133: ......

Page 134: ...anges to sort and filter o tions ill not ta e e ect until ...

Page 135: ......

Page 136: ...a fi s ...

Page 137: ......

Page 138: ......

Page 139: ......

Page 140: ......

Page 141: ......

Page 142: ......

Page 143: ......

Page 144: ......

Page 145: ......

Page 146: ......

Page 147: ......

Page 148: ......

Page 149: ......

Page 150: ......

Page 151: ...and needs to e erified or ad usted i anal ers ...

Page 152: ......

Page 153: ......

Page 154: ......

Page 155: ......

Page 156: ...erte cannot ad ust t e o to t e ro er l ers installed ill a ect s ste acuu and a ect t e o rate e auto alance a ...

Page 157: ......

Page 158: ......

Page 159: ......

Page 160: ......

Page 161: ......

Page 162: ......

Page 163: ......

Page 164: ......

Page 165: ......

Page 166: ......

Page 167: ......

Page 168: ......

Page 169: ......

Page 170: ...fi a i ...

Page 171: ......

Page 172: ......

Page 173: ......

Page 174: ......

Page 175: ......

Page 176: ......

Page 177: ...Arrow must point downward Note location of Acid Scrubber Filter ...

Page 178: ...Arrows must point downward ...

Page 179: ...align ent reading ca a ilit ...

Page 180: ......

Page 181: ...r to t e o en osition and ull t e connector o lign t e orts on t e connector seat t e connector ull ta to loc o disconnect t is de ress t e loc ta on t e o er con nector and ull to onnection secured slide latc us u to o en us do n to close ...

Page 182: ...en reconnecting t e anal er connect t e nal er o unications ca le to t e anal er first ...

Page 183: ......

Page 184: ......

Page 185: ...ou a re lace a u onl en t e s ste laces it in stand o not re lace an o erating u ...

Page 186: ...CAUTION fitting improperly installed or with one of the A NIN ...

Page 187: ...A NIN ...

Page 188: ...Handle Slide Catch Locking knob ...

Page 189: ......

Page 190: ...o e serial co unication cards locat ed in slot do not a e atter ac u ...

Page 191: ...o e ac u edia a c ange t e files to read onl and a require an additional ste o c anging t e ttri utes it in t e file ro erties to a e t e usa le a a as fi s a si i i a a i ...

Page 192: ... alar s nstead use or a co ressed source t at is ree o oils and conta inants e o e and clean one ort at a ti e to insure ro er orientation o tu ing o not re o e t e ca illar tu ing icrotu es CAUTION after service can adversely affect instrument ers are reinstalled and firmly fastened ...

Page 193: ......

Page 194: ......

Page 195: ......

Page 196: ......

Page 197: ......

Page 198: ......

Page 199: ......

Page 200: ......

Page 201: ......

Page 202: ......

Page 203: ......

Page 204: ......

Page 205: ......

Page 206: ......

Page 207: ......

Page 208: ......

Page 209: ......

Page 210: ......

Page 211: ......

Page 212: ......

Page 213: ......

Page 214: ......

Page 215: ......

Page 216: ......

Page 217: ......

Page 218: ......

Page 219: ......

Page 220: ......

Page 221: ...ent istor eac ti e t e o tion is in o ed isting anal ers configured or ill e una ected ...

Page 222: ......

Page 223: ......

Page 224: ......

Page 225: ......

Page 226: ......

Page 227: ......

Page 228: ......

Page 229: ......

Page 230: ......

Page 231: ......

Page 232: ......

Page 233: ......

Page 234: ......

Page 235: ......

Page 236: ...cifica i s ...

Page 237: ...c i ...

Page 238: ...i a i i i a a i i a i A i i ...

Page 239: ...a cifica i s ...

Page 240: ...i a a s i s i si ia i i i a i i a i i s A a s i P ss i i P ss i i a i a a s i s ...

Page 241: ......

Page 242: ......

Page 243: ......

Page 244: ......

Page 245: ......

Page 246: ......

Page 247: ......

Page 248: ......

Page 249: ......

Page 250: ......

Page 251: ......

Page 252: ......

Page 253: ......

Page 254: ......

Page 255: ......

Page 256: ......

Page 257: ......

Page 258: ......

Page 259: ......

Page 260: ...cifica i s ...

Page 261: ...a ac s ...

Page 262: ...a ac a i s a i s A s Amperes i s A s a a ac a i s ...

Page 263: ...a a Assi s ...

Page 264: ......

Page 265: ......

Page 266: ...i a Assi a ...

Page 267: ...A a a a a s A a a a a A a s ...

Page 268: ...a a P i A a s a a P i A a s c ...

Page 269: ...a a P i A a s c a a P i A a s c ...

Page 270: ...a a P i A a s c a a P i A a s c ...

Page 271: ...a a P i A a s c a a P i A a s c ...

Page 272: ...a a P i A a s c ...

Page 273: ...i a Assi a figuration en rela s are used e de ault settings do not include co lete alar and ault settings or all nine anal ers or all oints ...

Page 274: ...A a a a a s A a a a a A a s ...

Page 275: ...a a P i A a s a a P i A a s c ...

Page 276: ...a a P i A a s a a P i A a s c ...

Page 277: ......

Page 278: ...CAUTION fieldbus networks and the internet These networks are not designed to resist cyberattack so their cabling must have rigorous physical isolation from malicious tra c ...

Page 279: ...optional external keyboard OPC via Ethernet is not recommend ed for the primary safety system notification CAUTION Tunnel OPC communication outside the er tex rack using secure software such as OPC communication among Micro soft indows computers is not highly resistant to cyberattack ...

Page 280: ......

Page 281: ......

Page 282: ......

Page 283: ......

Page 284: ......

Page 285: ......

Page 286: ......

Page 287: ...P fi s i ...

Page 288: ...P fi s fi a i P c a i P fi s fi a i ...

Page 289: ......

Page 290: ......

Page 291: ......

Page 292: ......

Page 293: ......

Page 294: ...fi i P A ss ...

Page 295: ......

Page 296: ......

Page 297: ... the ertex monitor the eart beat byte in word 0 This is because the M I DF T will continue to communicate if the ertex PLC ceases to run External automation e uipment must be programmed to treat a failure of the heartbeat to increment as a complete loss of gas detection ...

Page 298: ...fi i P A ss ...

Page 299: ......

Page 300: ......

Page 301: ......

Page 302: ...CAUTION Protect both the remote station and the net work between it and the ertex monitor from unauthori ed contact Software changes in crease the vulnerability of the ertex rack to malicious attack ...

Page 303: ......

Page 304: ......

Page 305: ......

Page 306: ...fi ac ...

Page 307: ...DCOM Configuration ...

Page 308: ......

Page 309: ......

Page 310: ...ipcofig all ...

Page 311: ......

Page 312: ......

Page 313: ...no enclature t e e ect o a sa le line lea ...

Page 314: ...i i ifi P a ic c a ic ...

Page 315: ......

Page 316: ...i Acc ss A i ic i Acc ss i i fi a i i ...

Page 317: ...a s anal ers configured or ill e una ected i fi a i i Pa ...

Page 318: ......

Page 319: ...ic i fi a c s s is s is c s a a s i a a s s si a a s ic s i c a a A a ics a i i a s ac A a ics s a i i a i a ai a ic ac s cass ...

Page 320: ...cass ...

Page 321: ...Asia Pacific ...

Reviews: