Output Types

The following output types are
available per the model selection
guide:

Current output

Electromechanical relays

Solid state relays

Open collector output

Solid state relay (10 amp)
externally mounted (optional)

Auxiliary current output
(optional)

Output Algorithms

The UDC3000 is available with one
or more of the following output
algorithms:
Time Proportional provides On-
Off or Time Proportional (Relay)
output.
Current Proportional supplies
proportional direct current output for
final control elements which require
a 4-20 mA signal.
Position Proportional positions a
reversible motor with a feedback
slidewire in proportion to the output
of the control algorithm. Requires 2
output relays.

Time Proportional Duplex -
depending on which control
algorithm you select, this duplex
output algorithm can provide On-
Off Duplex, Time Proportional
Duplex, or 3 Position Step Control.
The time proportional duplex output
provides independent PID tuning
constants and two time proportional
outputs; one for heat zone above
the 50% output, and one for cool
zone below 50% output.
Current Proportional Duplex -
similar to current proportional but
provides a second set of tuning
parameters and a split range
current output or a second current
output via the Auxiliary output
option, for the heat and cool zones.

Output Algorithms, 

cont

Current/Relay Duplex (Relay =
Heat) - 
a variation of Duplex with
Current active for 0 to 50% output
(Tuning Set 2) and Relay active 50
to 100% output (Tuning Set 1).
Current/Relay Duplex (Relay =
Cool)
 a variation of Duplex with
Current active for 50 to 100%
output and Relay is active for 0 to
50% output.
“Universal” Output Model -
Flexibility of the Output Algorithms
allows the Current Output Model
with 2 Alarms (DC300K-E) to be
also configured for time simplex,
time duplex, or three position step
control plus, of course, the original
capability of current simplex and
current/time duplex control. A Relay
Output Model with Auxiliary Output
can also be configured for these
output algorithms.

Control Algorithms

Depending on the output algorithms
specified, the controller can be
configured for the following control
algorithms:

On-Off

PID-A

PID-B

PD with Manual Reset

Three Position Step Control
The Three Position Step
Control algorithm allows the
control of a valve (or other actu-
ator), with an electric motor
driven by two controller output
relays; one to move the motor
upscale, the other downscale
without a feedback slidewire
linked to the motor shaft.
Accutune does not apply to this
algorithm. Features of this
algorithm are:
1.

The controller can use all
three  modes of control
(PID) instead of PI only.

2.

Three Position Step is an
automatic backup mode  to
Position Proportional
Control if the feedback
slidewire signal should fail.

Configuration

You decide how the controller is to
interact with the process by select-
ing, through

 simple keystrokes, the

functions you want.
Multi-language prompts guide the
operator step-by-step through

 the

configuration process assuring
quick and accurate entry of all
configurable parameters. There are
no internal jumpers, all configu-
ration is via the keyboard. Five
languages are available via
configuration; English, French,
German, Spanish and Italian.

Control Modes

Manual or Automatic control with
bumpless, balanceless transfer
between modes is a standard
feature. In the manual mode, the
operator directly controls the
controller output level. In the
automatic mode, the controller will
operate from a local setpoint, or a
remote setpoint provided at the
second input or via
communications.

Alarms

Alarm output terminals are located
at the rear terminal panel. One or
two electromechanical alarm relays
are available to activate external
equipment when preset alarm set
points are reached. Each of the two
alarms can be set to monitor two
independent set points. Each alarm
setpoint can be either high or low
alarm. The alarm type can be
selected to be either of the inputs,
the Process Variable, Deviation,
Output, Shed from  communications
or to alarm on manual mode. It can
also be used as an On or Off event
at the beginning or end of a
Ramp/Soak segment. The alarm
hysteresis is configurable from 0 to
100% of range.

Summary of Contents for Versa-Pro UDC3000

Page 1: ...nfigurable upscale or downscale burnout and failsafe output level Decimal Point Location Configurable for none one or two places Accutune IITM Provides a new truly plug and play tuning algorithm which will at the touch of a button or through a digital input accurately identify and tune any process including those with deadtime and integrating processes This speeds up and simplifies startup plus al...

Page 2: ... only 2 Digital Inputs Allows remote dry contact closure to select one of the following for each digital input Manual control mode Local setpoint 1 Local setpoint 2 Direct controller action Reset of Limit Controller Hold SP Ramp Programming Select PID set 2 PV Input 2 External program reset Disable PID integral action To Run SP Ramp Program To Automatic output value Manual mode failsafe output Dis...

Page 3: ...d for these output algorithms Control Algorithms Depending on the output algorithms specified the controller can be configured for the following control algorithms On Off PID A PID B PD with Manual Reset Three Position Step Control The Three Position Step Control algorithm allows the control of a valve or other actu ator with an electric motor driven by two controller output relays one to move the...

Page 4: ...ion of when Remote Setpoint is active the status of the control relays and whether a setpoint program is in Run or Hold mode A 21 segment bargraph displays deviation to 10 of span and an On Control indicator Displays A 4 digit upper display is dedicated to the process vari able during normal operation with alternate 6 character information displayed when in the configure mode During normal operati...

Page 5: ...ation of Conformity 51309303 000 Accuracy 0 20 of span typical 1 digit for display 15 bit resolution typical Temperature Stability 0 01 of Full Scale C change Input Signal Failure Protection Thermocouple Inputs Upscale or downscale burnout Burnout Current 0 13 microamps Failsafe Output Level Configurable 0 100 Input Impedance 4 20 Milliampere Input 250 Ohms 0 10 Volt Input 200K Ohms All Other 10 M...

Page 6: ...amps 55 C and 120 or 240 Vac Inductive Load 50 VA 120 Vac or 240 Vac Motor Rating 1 HP 25 C 0 75 HP 55 C Controller Output Algorithms On Off or Time Proportional One relay or open collector output Control action can be set for direct or reverse Time Proportional Relay Resolution 3 3 msec On Off Duplex Three Position Step Control or Time Proportional Duplex Two relays or open collector outputs Cont...

Page 7: ...will respond according to how each digital input is configured Opening contact causes return to previous state Input Filter Software Single pole lowpass section with selectable time constants off to 120 seconds available on both analog inputs Digital Displays Vacuum fluorescent alphanumeric A six character upper display dedicated to the process variable 4 digits Alternate information displayed dur...

Page 8: ...tent Table 1 Input Actuations Range PV Input F C Thermocouples B E E low J J low K K low NiNiMoly NNM NiNiMoly NNM low NIC Nicrosil Nisil R S T T low W5W26 W5W26 low 0 to 3300 454 to 1832 200 to 1100 0 to 1600 20 to 770 0 to 2400 20 to 1000 32 to 2500 32 to 1260 0 to 2372 0 to 3100 0 to 3100 300 to 700 200 to 500 0 to 4200 0 to 2240 18 to 1815 270 to 1000 129 to 593 18 to 871 7 to 410 18 to 1316 2...

Page 9: ...troller Model Number Interpretation Output 1 C Current 4 20mA without Alarms K Current 4 20mA with Alarm 1 E Relay Electromechanical 5AMP with Alarm 1 A Relay Solid State AC 1AMP with Alarm 1 T Open Collector Output 20mA with 1 Alarm D C 3 0 0 Output 2 or Alarm 2 O None E Relay Electromechanical 5AMP SPDT A Relay Solid State AC 1AMP SPST T Open Collector Output 20mA External Interface O None 1 RS4...

Page 10: ...RSP OUT 1 2 1 2 F C MAN DI FUNCTION LOWER DISPLAY MANUAL AUTO SETPOINT SELECT SET UP HOLD 1 2 24 945 Max Panel Thickness 10 394 Max 2 5 82 147 3 21 6 850 093 2 4 with optional rear cover 90 7 3 57 22073 0 008 92 3 622 0 03 0 0 0 0 0 008 92 3 622 0 03 0 0 0 0 RUN 96 3 780 Figure 5 UDC3000 Versa Pro Controller dimensions not to scale ...

Page 11: ... 11 12 13 14 15 16 17 DI 1 TX or AUX TX or AUX RX TX RX TX SHIELD DI 2 UDC 3000 EXTERNAL WIRING L1 H L2 N 22 23 24 25 26 27 IN 1 IN 2 0 Instrument Power 22840 NOTE The product manual should be consulted for specific details and precautions regarding wiring Figure 6 External Wiring Diagram ...

Page 12: ...l Automation and Control 16404 North Black Canyon HWY Phoenix AZ 85023 800 343 0228 In Europe Honeywell S A 80084 Amiens Cedex 2 33 22 54 56 56 Honeywell Control System Ltd Honeywell House Bracknell UK RG 12 1 EB 44 1344 826000 In Japan Yamatake Honeywell Co Ltd Nagai Int l Bldg 2 12 19 Shibuya Ku Tokyo 150 Japan 81 3 3486 2051 In Asia Honeywell Asia Pacific Inc Room 3213 3225 Sun Hung kai Centre ...

Reviews: