MOUNTING

 

When installing the valve care must be taken that the flow 
direction is correct (see section "Typical Operation"). The 
valve must not be mounted with the stem pointing downward. 
The adjustment cap must be removed from the valve only 
when the actuator is fitted. The valve should be installed as 
stress-free as possible with a tightening torque of 25 to 
30 Nm. 
The valve is supplied complete with mounting instructions. 
The water quality should meet VDI 2035 requirements.  

 
 
 
 
 
 
 
 

ACCESSORIES 

Valves V5832B need two connection sets, valves V5833A need three connection sets. 

Connection 

Pipe Size 

DN 

Order Number

Connection Set 

Description 

External 

Thread 

R1" 

R11/4" 

R11/2" 

25 

32 

40 

AC-25T 

AC-32T 

AC-40T 

 

Consisting of 1 union nut 
1 tailpiece and 1 gasket 

Internal 

Thread 

Rp1" 

Rp11/4" 

Rp11/2" 

25 

32 

40 

AC-25TF 

AC-32TF 

AC-40TF 

 

 

Consisting of 1 union nut 
1 tailpiece and 1 gasket 

 

Dimensions of Connection Sets 

Order Number 

 

 

G11/2” 

G2” 

G21/4” 

R1” 

R11/4” 

R11/2” 

 

 

 

AC-25T 

AC-32T 

AC-40T 

 

G11/2” 

G2” 

G21/4” 

 

 

 

Rp1” 

Rp11/4” 

Rp11/2” 

AC-25TF 

AC-32TF 

AC-40TF 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

Summary of Contents for V5832B

Page 1: ... for different connections Easy to mount no tools required Flat sealing connections Flat surfaces on body to fit installation tools Standard external threads for Honeywell or field supplied fittings Adjustment cap for manual operation SPECIFICATIONS Model Two way V5832B Three way V5833A Operation Stem up to close port A to AB Nominal pressure rating PN16 Capacity index kVS see tables on page 2 Lea...

Page 2: ...92 600 1600 32 16 0 V5833A2100 300 1200 40 25 0 V5833A2118 1000 OPERATION A built in return spring produces a closing force The valves are supplied with an adjustment cap for manual operation and to protect the stem This allows the stem set up for filling or initial heating cooling during the building construction phase without the use of a controller or actuator The small electric valve actuators...

Page 3: ...e is supplied complete with mounting instructions The water quality should meet VDI 2035 requirements ACCESSORIES Valves V5832B need two connection sets valves V5833A need three connection sets Connection Pipe Size DN Order Number Connection Set Description External Thread R1 R11 4 R11 2 25 32 40 AC 25T AC 32T AC 40T Consisting of 1 union nut 1 tailpiece and 1 gasket Internal Thread Rp1 Rp11 4 Rp1...

Page 4: ... Honeywell GmbH Böblinger Strasse 17 71101 Schönaich Germany Phone 49 7031 63701 Fax 49 7031 637493 http ecc emea honeywell com Subject to change without notice Printed in Germany EN0B 0408GE51 R0612 DIMENSIONS Fig 3 Dimensions in mm Allow 200mm for the actuator and clearance for removal 6 5 Stroke 18 Allow 200mm for the actuator and clearance for removal e 6 5 Stroke 18 V5832B DN a b c d e 25 105...

Reviews: