V5832B/V5833A SMALL LINEAR VALVES PN16 – PRODUCT DATA
EN0B-0408GE51 R0612
2
FLOW CAPACITIES AND CLOSE OFF PRESSURE RATINGS
TWO-WAY VALVES
DN
k
VS
order no.
close-off pressure (= max. operating
pressure) in kPa for 300-N actuators
(M6410C,L / M7410C1015 / M7410E1028)
close-off pressure (= max. operating
pressure) in kPa for 400-N actuators
(ML6435B / ML7430E / ML7435E)
25 4.0
V5832B2075
1600
1600
25 6.3
V5832B2083
1600
1600
25 10.0
V5832B2091
1600
1600
32 16.0
V5832B2109
1200
1200
40 25.0
V5832B2117
1000
1000
THREE-WAY VALVES
DN
k
VS
order no.
close-off pressure (= max. operating
pressure) in kPa for 300-N actuators
(M6410C,L / M7410C1015 / M7410E1028)
close-off pressure (= max. operating
pressure) in kPa for 400-N actuators
(ML6435B / ML7430E / ML7435E)
25 4.0
V5833A2076
600
1600
25 6.3
V5833A2084
600
1600
25 10.0
V5833A2092
600
1600
32 16.0
V5833A2100
300
1200
40 25.0
V5833A2118
--
1000
OPERATION
A built-in return spring produces a closing force.
The valves are supplied with an adjustment cap for manual
operation and to protect the stem. This allows the stem set up
for filling or initial heating/cooling during the building
construction phase without the use of a controller or actuator.
The small electric valve actuators provide automatic control
during the opening and closing movement of the valve stem.
TYPICAL OPERATION
All types of valves should be mounted in the return flow. If the
p-values exceed 60 kPa, attention should be paid to the
development of noise.
Two-Way Valves
Direction of flow always
from port A to port B
Port B: Outlet
outlet
inlet
+
-
outlet
inlet
+
-
Fig. 1. Two-way valve operation
Three-Way Valves
These valves are preferably used as mixing valves, this
means:
Port AB:
Total flow outlet
Port A:
Controlled flow inlet
Port B:
Bypass inlet
AB
A
B
inlet
+
-
AB
A
B
inlet
+
-
Fig. 2. Three-way valve operation