Honeywell V5832B Product Data Download Page 2

V5832B/V5833A  SMALL LINEAR VALVES PN16 – PRODUCT DATA 

EN0B-0408GE51 R0612 

FLOW CAPACITIES AND CLOSE OFF PRESSURE RATINGS 

TWO-WAY VALVES 

 

DN 

k

VS

 

order no. 

close-off pressure (= max. operating 

pressure) in kPa for 300-N actuators 

(M6410C,L / M7410C1015 / M7410E1028)

close-off pressure (= max. operating 

pressure) in kPa for 400-N actuators 

(ML6435B / ML7430E / ML7435E) 

25 4.0 

V5832B2075 

1600 

1600 

25 6.3 

V5832B2083 

1600 

1600 

25 10.0 

V5832B2091 

1600 

1600 

32 16.0 

V5832B2109 

1200 

1200 

40 25.0 

V5832B2117 

1000 

1000 

 

THREE-WAY VALVES 

 

DN 

k

VS

 

order no. 

close-off pressure (= max. operating 

pressure) in kPa for 300-N actuators 

(M6410C,L / M7410C1015 / M7410E1028)

close-off pressure (= max. operating 

pressure) in kPa for 400-N actuators 

(ML6435B / ML7430E / ML7435E) 

25 4.0 

V5833A2076 

600 

1600 

25 6.3 

V5833A2084 

600 

1600 

25 10.0 

V5833A2092 

600 

1600 

32 16.0 

V5833A2100 

300 

1200 

40 25.0 

V5833A2118 

-- 

1000 

 

OPERATION 

A built-in return spring produces a closing force. 
The valves are supplied with an adjustment cap for manual 
operation and to protect the stem. This allows the stem set up 
for filling or initial heating/cooling during the building 
construction phase without the use of a controller or actuator. 
The small electric valve actuators provide automatic control 
during the opening and closing movement of the valve stem. 
 

TYPICAL OPERATION 

All types of valves should be mounted in the return flow. If the 

p-values exceed 60 kPa, attention should be paid to the 

development of noise. 
 

Two-Way Valves 

Direction of flow always

 

from port A to port B 

Port B: Outlet 

outlet

inlet

+

-

outlet

inlet

+

-

 

Fig. 1. Two-way valve operation 

 

Three-Way Valves 

These valves are preferably used as mixing valves, this 
means: 
Port AB: 

Total flow outlet 

Port A: 

Controlled flow inlet 

Port B: 

Bypass inlet 

 

AB

A

B

inlet

+

-

AB

A

B

inlet

+

-

 

Fig. 2. Three-way valve operation 

Summary of Contents for V5832B

Page 1: ... for different connections Easy to mount no tools required Flat sealing connections Flat surfaces on body to fit installation tools Standard external threads for Honeywell or field supplied fittings Adjustment cap for manual operation SPECIFICATIONS Model Two way V5832B Three way V5833A Operation Stem up to close port A to AB Nominal pressure rating PN16 Capacity index kVS see tables on page 2 Lea...

Page 2: ...92 600 1600 32 16 0 V5833A2100 300 1200 40 25 0 V5833A2118 1000 OPERATION A built in return spring produces a closing force The valves are supplied with an adjustment cap for manual operation and to protect the stem This allows the stem set up for filling or initial heating cooling during the building construction phase without the use of a controller or actuator The small electric valve actuators...

Page 3: ...e is supplied complete with mounting instructions The water quality should meet VDI 2035 requirements ACCESSORIES Valves V5832B need two connection sets valves V5833A need three connection sets Connection Pipe Size DN Order Number Connection Set Description External Thread R1 R11 4 R11 2 25 32 40 AC 25T AC 32T AC 40T Consisting of 1 union nut 1 tailpiece and 1 gasket Internal Thread Rp1 Rp11 4 Rp1...

Page 4: ... Honeywell GmbH Böblinger Strasse 17 71101 Schönaich Germany Phone 49 7031 63701 Fax 49 7031 637493 http ecc emea honeywell com Subject to change without notice Printed in Germany EN0B 0408GE51 R0612 DIMENSIONS Fig 3 Dimensions in mm Allow 200mm for the actuator and clearance for removal 6 5 Stroke 18 Allow 200mm for the actuator and clearance for removal e 6 5 Stroke 18 V5832B DN a b c d e 25 105...

Reviews: