Honeywell V4730C Manual Download Page 14

V4730C/V8730C/V4734C 1:1 Gas/Air Servo Regulated Gas Valves

EN2R-9074 0612R1-NE

ELECTRICAL CONNECTIONS

Wiring

1. Use 14, 16 or 18 AWG copper conductor, 600 volt insulation,

moisture-resistant wire for line voltage connections. Recom-
mended wire types are TTW60C, THW75C or THHN90C.

2. Follow the instructions below for wiring the gas valve. See 

Fig. 16 and 17 for reference.
2.a T1 (yellow) will be L2 (120 Vac or 24 Vac). 
2.b T2 (black) will be L1 (120 Vac or 24 Vac) to Valve 1. 
2.c T3 (blue) will be L1 (120 Vac or 24 Vac) to Valve 2. 
2.d Ground (green) will be earth ground.

Fig. 16: Four-pin electrical plug connector

Fig. 17: Electrical connection diagram

WARNING

Electrical Shock Hazard. Can cause severe injury 
or death.

Disconnect the power supply before beginning wiring 
to prevent electrical shock. More than one disconnect 
may be involved.

ADJUSTMENTS AND FINAL CHECKOUT

The following procedures are related to the adjustments on the 
main gas valve. For adjustments of the other devices (i.e., pres-
sure switches), refer to the instructions supplied with the applica-
ble device.

Pressure Tap Points (Fig. 18)

The V4730C/V8730C/V4734C Valves have a number of connec-
tion points (1/8 in. [3 mm] NPT plugs) for measuring pressure 
and/or mounting a pressure switch. The pressure tap points are:

1 inlet pressure at first SSOV flange tap.
2 inlet pressure at first SSOV.
P outlet pressure at first SSOV.
3 inlet pressure at second SSOV.
4 outlet pressure at second SSOV flange tap.

The following pressures can be measured:
1. Inlet pressure-tap on inlet flange (1).
2. Pressure after inlet screen (2).
3. Unregulated intermediate pressure-pressure between the 

two shutoff seats (P).

4. Regulated intermediate pressure-pressure between the shu-

toff valves (3).

5. Outlet pressure-tap from flange (4).

The corresponding numbers (2, P, 3) can be found on the side of 
the valve.
Note: To mount the C6097 Pressure Switch, refer to instructions

in form number 65-0237, furnished with the switch. The
pressure switch can be mounted to 2, P, or 3 on either
side of the valve.

Fig. 18: Pressure tap points

Second Valve, Fast Opening

Flow rate is adjusted from 0% to 100% of full rated flow. To ad-
just the flow rate:
1. Remove the flat, round, blue plastic cap from the cover.

Using a 3 mm (7/64 in.) hex wrench, turn the adjustment
screw counterclockwise to increase or clockwise to decrease
the flow rate.

2. Snap the flat, round, blue plastic cap back onto the cover.

Final Checkout of the Installation

Set the system in operation after any adjustment is completed 
and observe several complete cycles to ensure that all burner 
components function correctly.

WARNING

Fire or Explosion Hazard.
Can cause severe injury, death or property da-
mage.

Only fully qualified, experienced, flame safeguard 
technicians should make adjustments on the valve.

Summary of Contents for V4730C

Page 1: ...Unit VMU and dc fan are used for modulating premix appliances such as gas bur ners gas boilers rooftop units makeup air units and process ap plications FEATURES Wide modulation range 14 to 100 of burner load 24 Vac and 120 Vac models Main valve body with two shutoff seats double block valve Closing time less than one second Mesh screen strainer between inlet flange and main body Various pressure t...

Page 2: ...4 mBar Note CSA Certification to 1 2 psi Connections 1 8 in 3 mm NPT pressure taps at inlet and outlet flanges Eight flange connections are provided at the main body to mount either a pressure switch high or low or a ValveProving System VPS Torsion and Bending Stress Pipe connections meet EN151 Group 2 requirements Electrical Equipment Standard DIN plug connector with 36 in 914 mm leadwires Valve ...

Page 3: ...wall 3 cu in hr 50 cm3 h at test pressure of 0 87 psi 6 mBar and 7 83 psi 540 mBar First Valve 2 5 cu in hr 40 cm3 h at test pressure of 0 87 psi 6 mBar and 7 83 psi 540 mBar Second Valve 2 4 cu in hr 40 cm3 h at test pressure of 0 87 psi 6 mBar and 7 83 psi 540 mBar High Pressure Test In the OFF condition the valve will withstand 21 75 psi 1 5 Bar inlet pressure without damage Accessories FL02000...

Page 4: ...734C 1 1 Gas Air Servo Regulated Gas Valves 4 EN2R 9074 0612R1 NE Fig 1 V4730C V8730C Gas Valves 1 2 in 13 mm and 3 4 in 19 mm size dimensions in in mm Fig 2 V4730C V8730C Gas Valves 1 in 25 mm size dimensions in in mm ...

Page 5: ... V8730C V4734C 1 1 Gas Air Servo Regulated Gas Valves EN2R 9074 0612R1 NE 5 Fig 3 V4730C V8730C Gas Valves 1 1 4 in 32mm size dimensions in in mm Fig 4 V4734C Gas Valves 1 1 4 in 32mm size dimensions in in mm ...

Page 6: ...R1 NE Fig 5 Venturi 150 335 kW with 1 2 in to 1 in gas valves and valve shutoff kit installed dimensions in in mm See Table 3 for dimensions Table 3 Dimensions in inches millimeters Valve Size in inches A B C D 1 2 3 4 6 1 4 159 15 15 16 405 2 15 16 75 7 7 1 2 191 1 8 5 16 211 ...

Page 7: ...V4730C V8730C V4734C 1 1 Gas Air Servo Regulated Gas Valves EN2R 9074 0612R1 NE 7 Fig 6 Venturi 500kW with V4730 gas vlave and valve shutoff kit installed dimensions in in mm part 1 ...

Page 8: ...V4730C V8730C V4734C 1 1 Gas Air Servo Regulated Gas Valves 8 EN2R 9074 0612R1 NE Fig 7 Venturi 500 kW with V4730 gas valve and valve shutoff kit installed dimensions in in mm part 2 ...

Page 9: ...V4730C V8730C V4734C 1 1 Gas Air Servo Regulated Gas Valves EN2R 9074 0612R1 NE 9 Fig 8 V4734 VMU 500 680 ...

Page 10: ... V4734C 1 1 Gas Air Servo Regulated Gas Valves 10 EN2R 9074 0612R1 NE Fig 9 Capacity curves for V4730C V8730C and VMU 150 Venturi 1 2 in size Fig 10 Capacity curves for V4730C V8730C and VMU 300 Venturi 3 4 in size ...

Page 11: ... V4734C 1 1 Gas Air Servo Regulated Gas Valves EN2R 9074 0612R1 NE 11 Fig 11 Capacity curves for V4730C V8730C and VMU 300 Venturi 1 in size Fig 12 Capacity curves for V4730C V8730C and VMU 335 Venturi 1 1 4 in size ...

Page 12: ...4734C 1 1 Gas Air Servo Regulated Gas Valves 12 EN2R 9074 0612R1 NE Fig 14 Capacity curves for V4734C V8734C and VMU 680 Venturi 1 1 4 in size Fig 13 Capacity curves for V4730C V8730C and VMU 500 Venturi 1 1 4 in size ...

Page 13: ... commissioning the burner check for proper lightoff and verify correct fuel air mix and combustion quality through out the entire firing range from lowest to highest fan speeds used Mounting Locations The distance between the gas valve and the wall ground must be a minimum of 11 5 16 in 30 cm Fig 15 Regulating adjusting screw Main Gas Connection 1 Take care that dirt does not enter the gas valve d...

Page 14: ...ure at first SSOV flange tap 2 inlet pressure at first SSOV P outlet pressure at first SSOV 3 inlet pressure at second SSOV 4 outlet pressure at second SSOV flange tap The following pressures can be measured 1 Inlet pressure tap on inlet flange 1 2 Pressure after inlet screen 2 3 Unregulated intermediate pressure pressure between the two shutoff seats P 4 Regulated intermediate pressure pressure b...

Page 15: ...e rate of bubbles coming through the water stabili zes count the number of bubbles appearing during a ten se cond period Each bubble appearing represents a flow rate of 0 001 cfh 28 cch See Table 4 10 Close the upstream manual gas cock A 11 Remove the leak test tap from the valve body 12 Using a small amount of pipe sealant on the 1 8 in 3 mm NPT plug reinstall the plug in pressure tap point P 13 ...

Page 16: ...a short in the electrical circuit and repair it as ne cessary WARNING Electrical Shock Hazard Can cause severe inju ry death or property damage Use extreme caution when troubleshooting line volta ge is present IMPORTANT Do not replace the valve until all other sources of trouble are eliminated SERVICE INFORMATION Scheduled Inspection and Maintenance Set up and follow a schedule for periodic inspec...

Reviews: