background image

V4055F,G FLUID POWER ACTUATOR WITH MANUAL CONTROL

65-0029—01

2

ORDERING INFORMATION

When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the 

TRADELINE® Catalog or price sheets for complete ordering number.

If you have additional questions, need further information, or would like to comment on our products or services, please write or 

phone:

1.

Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).

2.

Honeywell Customer Care

1885 Douglas Drive North

Minneapolis, Minnesota 55422-4386

In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9.

International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, 

Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.

a

Maximum total connected power to both switches (if used) is 

1800 VA.

Nominal Opening Time: 

13 seconds:

Closing Time: 

1 sec maximum when de-energized.

Ambient Operating Temperature Rating:

-40°F to +150°F (-40°C to +66°C) for 60 Hz models; -10°F to 

+158°F (-23°C to +70°C) for 50 Hz and 50/60 Hz models.

Mounting Means:

Actuator mounts directly to valve bonnet with 2 setscrews, 

positioned 90 angular degrees apart. Valve and actuator 

can be mounted in any position.

Mounting Dimensions: 

See Fig. 1.

Replacement Parts:

130928 Red Indicator Lamp.

Accessories:

133568 Auxiliary Switch Bag Assembly.

133569 Valve-Closed Indication Switch Bag Assembly.

Approvals: 

UL and FM. IRI Approvable.

Electrical Ratings: 

See Table 2.

OPERATION

1.

The red READY TO OPEN light will be on if there is 

power to the actuator and the rocker switch is in the 

center position.

2.

To open the valve depress the rocker switch to the 

VALVE OPEN position and hold until the valve is open 

(Red READY TO OPEN light turns off). The valve will 

close if the rocker switch is released from the VALVE 

OPEN position with the red READY TO OPEN light on.

3.

To close the valve depress rocker switch to VALVE 

CLOSED position. The rocker switch stays in the valve 

closed position when released.

4.

The valve automatically closes on power loss. It must 

be manually reopened using the rocker switch.

Table 1. Auxiliary Switch And Valve-closed Indication 

Switch Ratings: 112 hp (0.37 kW)

a

LOAD

120 V

240 V

Full Load

9.8 A

4.9A

Locked Rotor

58.5 A

29.4 A

Table 2. Electrical Ratings.

Voltage and 

Frequency

Opening (Fast)

Holding

Inrush

W

A

VA

W

A

VA

120/60

5.4

71.0

1.33

160

9.5

0.12

14

Summary of Contents for V4055F

Page 1: ...ow only when the gas valve is fully closed Ambient temperature rating of 40 F to 150 F 40 C to 66 C Valve and actuator may be mounted in any position Optional field adjustable spdt auxiliary switch rated at 112 hp 0 37 kW may be added in the field Standard enclosure meets NEMA 1 IP30 general purpose requirements Red light indicates when valve is ready to open Rocker switch allows manual operation ...

Page 2: ...0 Hz and 50 60 Hz models Mounting Means Actuator mounts directly to valve bonnet with 2 setscrews positioned 90 angular degrees apart Valve and actuator can be mounted in any position Mounting Dimensions See Fig 1 Replacement Parts 130928 Red Indicator Lamp Accessories 133568 Auxiliary Switch Bag Assembly 133569 Valve Closed Indication Switch Bag Assembly Approvals UL and FM IRI Approvable Electri...

Page 3: ...HOLES 8 ON 3 3 4 95 RADIUS M23960 3 4 1 1 1 4 1 1 2 2 2 1 2 3 4 VALVE SIZE INCH 13 1 8 13 1 8 13 1 8 13 1 8 13 1 4 13 3 4 13 3 4 16 3 16 333 5 333 5 333 5 333 5 336 5 349 0 349 0 411 0 2 3 4 2 3 4 2 3 4 2 3 4 2 7 8 3 3 8 3 3 8 5 13 16 70 0 70 0 70 0 70 0 73 0 85 5 85 5 128 0 8 3 16 8 3 16 8 3 16 8 3 16 8 5 16 8 13 16 8 13 16 11 7 32 208 0 208 0 208 0 208 0 211 1 224 0 224 0 285 0 5 3 4 5 3 4 5 3 4...

Page 4: ... seal Fig 2 V4055 actuator with cover removed NOTE A V5055A B or D valve can also be fitted with a bon net assembly with 2 seals to provide a valve seal overtravel interlock The SPDT valve closed indication switch is installed to make or break a circuit when the valve is in the closed position The switch is not adjustable NOTE Mark the actuator or valve to indicate any changes made To install the ...

Page 5: ...he installation is complete cycle the valve several times with the manual fuel shutoff cock closed before testing the system in actual operation Service The actuator is not field repairable except for replacing the auxiliary switch valve closed indication switch and READY TO OPEN light See INSTALLATION section for procedure Do not disassemble the valve actuator If the actuator should fail to opera...

Page 6: ...ds 12 Replace the damper crank arm assembly 13 Re attach the wires removed from the actuator terminals and turn on the electrical power 14 With the gas still off cycle the actuator to check for proper mechanical operation CAUTION Be sure to perform a bonnet seal and seat leak check after installation Be sure to read and follow all instructions that come with the actuators valves seal and bonnet ki...

Page 7: ...V4055F G FLUID POWER ACTUATOR WITH MANUAL CONTROL 7 65 0029 01 ...

Page 8: ... Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 customer honeywell com V4055F G FLUID POWER ACTUATOR WITH MANUAL CONTROL U S Registered Trademark 2007 Honeywell International Inc 65 0029 01 M S Rev 06 07 ...

Reviews: