Honeywell TROL-A-TEMP Q674B Installation Instructions Manual Download Page 4

MOUNTING THE THERMOSTAT

1. Remove the thermostat cover by pulling the bottom

edge of the cover outward away from the base until it snaps
free from the cover clip.

NOTE: The cover is hinged at the top and is removed by

pulling out at the bottom.

2. Carefully remove and discard the polystyrene packing

insert that protects the mercury switches during shipment.

3. Turn over the thermostat base and note the spring

fingers that engage the subbase contacts. Make sure the

spring fingers are not bent flat, preventing proper electri-
cal contact with the subbase.

4. Set the heat anticipator indicator(s) to 0.1A for

proper system operation (Fig. 11).

5. Note the two tabs on the top inside edge of the

thermostat base. The tabs fit into the corresponding slots
on the top of the subbase. Mount the thermostat on the
subbase. See Fig. 12.

6. Align the two captive mounting screws in the thermo-

stat base with the posts on the subbase (Fig. 12). Tighten
both screws. Do not overtighten the screws or damage to
the subbase posts can result.

Fig. 7—Typical hookup for MABS II and MABS II-L Control Panels with T874A Thermostat/Q674B,D
Subbases in single-stage heating-cooling zone system. MABS II Control Panel shown; MABS II-L Control
Panel hookup is the same.

4

M1634

Y
2

1

POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.  

JUMPER RC, RH TOGETHER AND WIRE AS SINGLE R TERMINAL.

ZONE 1 O AND B TERMINALS MUST BE CONNECTED FOR PROPER SYSTEM OPERATION.

DO NOT CONNECT W2 AND Y2 TERMINALS TO CONTROL PANEL.

Y
1
O

G

2

G

1

R
C
R
H
B

W

2

W

1
E

ADD-A-

ZONE

EM. HEAT
RELAY

SECOND 
STAGE 
RELAY

FAN
RELAY

HEAT
RELAY

COOL
RELAY

CAC
RELAY

ZONE 1
RELAY

ZONE 2
RELAY

ZONE 3
RELAY

A
4
A
3

A
2
A
1

T
8
T
7

T
6
T
5

T
4

M

6

M

4

M

1

ZONE 3

T
8
T
7

T
6
T
5

T
4
M

6

M

4

M

1

ZONE 2

T
8
T
7

T
6
T
5

T
4

M

6

M

4

M

1

ZONE 1

O

1

G

1

B
1
E
1

2

1

CHANGEOVER 
CONTROL

COOL

FAN

HEAT

EM. HEAT

24 V, 40 VA

TRANSFORMER

4

5

6

Z

DAMPER
ACTUATOR

1

2

3

X

4

5

6

Z

DAMPER
ACTUATOR

1

2

3

X

4

5

6

Z

DAMPER
ACTUATOR

1

2

3

X

L1
(HOT)

L2

1

MABS II
CONTROL PANEL

Y1

Y2

RC

RH W2

W1

2

T874A THERMOSTAT/
Q674D SUBBASE

Y1

Y2

RC

RH

W2 W1

2

T874A THERMOSTAT/
Q674D SUBBASE

Y1

RC

RH

W1 W2

Y2

2

T874A THERMOSTAT/Q674B SUBBASE

O

G

B

TO SINGLE-
STAGE 
HEATING/
COOLING 
EQUIPMENT

3

4

4

2

4

3

4

Summary of Contents for TROL-A-TEMP Q674B

Page 1: ...d control in the trash Contact your local waste management authority for instructions regarding recycling and the proper disposal of this control or of an old control containing mercury in a sealed tube If you have questions call Honeywell at 1 800 468 1502 M3375 Installation Instructions for the Trained Service Technician TABLE 1 THERMOSTAT SUBBASE AND SYSTEM COMPATIBILITY Thermostat Application ...

Page 2: ...irectly on the wall 1 To mount on a horizontal outlet box install the sub base on the outlet box as shown in Fig 1 For a wall installation hold the subbase in position and mark holes for the anchors Fig 2 Obtain wall anchors locally Take care that the wires do not fall back into the wall opening Set aside subbase Drill two 3 16 in 4 8 mm holesandgentlytapanchorsintotheholesuntilflushwiththe wall 2...

Page 3: ...mostat Q674B D Subbase in single stage heating cooling two zone system POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED ZONE 1 O AND B TERMINALS MUST BE CONNECTED FOR PROPER SYSTEM OPERATION JUMPER RC AND RH TERMINALS TOGETHER AND WIRE AS SINGLE R TERMINAL DO NOT CONNECT W2 AND Y2 TERMINALS TO CONTROL PANEL 1 1 M1633 HEAT RELAY COOL RELAY ZONE 1 RELAY ZONE 2 RELAY Y2 Y1 O ...

Page 4: ...ult Fig 7 Typical hookup for MABS II and MABS II L Control Panels with T874A Thermostat Q674B D Subbases in single stage heating cooling zone system MABS II Control Panel shown MABS II L Control Panel hookup is the same 4 M1634 Y 2 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED JUMPER RC RH TOGETHER AND WIRE AS SINGLE R TERMINAL ZONE 1 O AND B TERMINALS MUST BE CONNECT...

Page 5: ...G DO NOT CONNECT W2 Y1 O G2 G1 RC RH B W2 W1 E ADD A ZONE EM HEAT RELAY SECOND STAGE RELAY FAN RELAY HEAT RELAY COOL RELAY CAC RELAY ZONE 1 RELAY ZONE 2 RELAY ZONE 3 RELAY A4 A3 A2 A1 T8 T7 T6 T5 T4 M6 M4 M1 ZONE 3 T8 T7 T6 T5 T4 M6 M4 M1 ZONE 2 T8 T7 T6 T5 T4 M6 M4 M1 ZONE 1 O1 G1 B1 E1 2 1 CHANGEOVER CONTROL COOL FAN HEAT EM HEAT 24 V 40 VA TRANSFORMER 4 5 6 Z DAMPER ACTUATOR 1 2 3 X 4 5 6 Z DAM...

Page 6: ...T HAS R RC RH TERMINALS JUMPER TOGETHER AND WIRE AS SINGLE R TERMINAL DO NOT CONNECT THERMOSTAT O AND B TERMINALS TO CONTROL PANEL 2 ZONE 1 ZONE 2 ZONE 3 O B RC RH 1 2 G Y R W M6 M4 M1 VO VC ZONE 1 G Y R W M6 M4 M1 VO VC ZONE 2 G Y R W M6 M4 M1 VO VC ZONE 3 OPEN CLOSE DAMPER ZONE SYS ZONE 1 OPEN CLOSE DAMPER ZONE SYS ZONE 2 OPEN CLOSE DAMPER ZONE SYS ZONE 3 FAN FAN FAN G Y1 Y2 R W1 W2 O T874A THER...

Page 7: ...r ...

Page 8: ...Settings ...

Page 9: ...set it to ON See Fig 13 After 30 seconds place your hand in front of an air register in that zone to check for air flow at the register 2 Reset fan switch if provided to AUTO After 30 sec onds make sure air flow at register has stopped 3 Move heating set point lever on zone thermostat 10 F 6 C above room temperature to call for heat 4 After 30 seconds longer if necessary for time delay on plenum f...

Page 10: ...eter to sense the area temperature compare the readings Be care ful not to touch the thermometer or breathe on it 4 If the readings are the same replace the cover and put the system into operation 5 If the readings are different insert a small screw driver in the thermometer slot Fig 14 and turn it until the thermometers have the same reading 6 Replace the thermostat cover and put the system into ...

Reviews: