Honeywell TROL-A-TEMP Q674B Installation Instructions Manual Download Page 10

Fig. 14—Thermometer calibration.

Calibration

THERMOSTAT

T874 thermostats are accurately calibrated at the

factory. They do not have provision for field calibration.

THERMOMETER

The thermometer in your thermostat has been accu-

rately calibrated at the factory. The thermometer should
only need adjustment if it has been dropped or shifted due
to mishandling.

If the set point lever and the thermometer reading do

not agree:

1. Remove the thermostat cover by pulling up from the

bottom of cover until it clears the mounting slots.

2. Set the thermostat cover on a table near an accurate

thermometer.

3. Allow ten minutes for the cover thermometer to

sense the area temperature; compare the readings. Be care-
ful not to touch the thermometer or breathe on it.

4. If the readings are the same, replace the cover and put

the system into operation.

5. If the readings are different, insert a small screw-

driver in the thermometer slot (Fig. 14) and turn it until the
thermometers have the same reading.

6. Replace the thermostat cover and put the system into

operation.

NOTE: Hand heat will offset the thermometer reading.

After making each adjustment, wait ten minutes for
the thermometer to stabilize before comparing.

M5070

Home and Building Control

Home and Building Control

Helping You Control Your World

Honeywell Inc.

Honeywell Limited—Honeywell Limitée

1985 Douglas Drive North

740 Ellesmere Road

Golden Valley, Minnesota  55422

Scarborough, Ontario
M1P 2V9

Printed in U.S.A.

QUALITY IS KEY

Summary of Contents for TROL-A-TEMP Q674B

Page 1: ...d control in the trash Contact your local waste management authority for instructions regarding recycling and the proper disposal of this control or of an old control containing mercury in a sealed tube If you have questions call Honeywell at 1 800 468 1502 M3375 Installation Instructions for the Trained Service Technician TABLE 1 THERMOSTAT SUBBASE AND SYSTEM COMPATIBILITY Thermostat Application ...

Page 2: ...irectly on the wall 1 To mount on a horizontal outlet box install the sub base on the outlet box as shown in Fig 1 For a wall installation hold the subbase in position and mark holes for the anchors Fig 2 Obtain wall anchors locally Take care that the wires do not fall back into the wall opening Set aside subbase Drill two 3 16 in 4 8 mm holesandgentlytapanchorsintotheholesuntilflushwiththe wall 2...

Page 3: ...mostat Q674B D Subbase in single stage heating cooling two zone system POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED ZONE 1 O AND B TERMINALS MUST BE CONNECTED FOR PROPER SYSTEM OPERATION JUMPER RC AND RH TERMINALS TOGETHER AND WIRE AS SINGLE R TERMINAL DO NOT CONNECT W2 AND Y2 TERMINALS TO CONTROL PANEL 1 1 M1633 HEAT RELAY COOL RELAY ZONE 1 RELAY ZONE 2 RELAY Y2 Y1 O ...

Page 4: ...ult Fig 7 Typical hookup for MABS II and MABS II L Control Panels with T874A Thermostat Q674B D Subbases in single stage heating cooling zone system MABS II Control Panel shown MABS II L Control Panel hookup is the same 4 M1634 Y 2 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED JUMPER RC RH TOGETHER AND WIRE AS SINGLE R TERMINAL ZONE 1 O AND B TERMINALS MUST BE CONNECT...

Page 5: ...G DO NOT CONNECT W2 Y1 O G2 G1 RC RH B W2 W1 E ADD A ZONE EM HEAT RELAY SECOND STAGE RELAY FAN RELAY HEAT RELAY COOL RELAY CAC RELAY ZONE 1 RELAY ZONE 2 RELAY ZONE 3 RELAY A4 A3 A2 A1 T8 T7 T6 T5 T4 M6 M4 M1 ZONE 3 T8 T7 T6 T5 T4 M6 M4 M1 ZONE 2 T8 T7 T6 T5 T4 M6 M4 M1 ZONE 1 O1 G1 B1 E1 2 1 CHANGEOVER CONTROL COOL FAN HEAT EM HEAT 24 V 40 VA TRANSFORMER 4 5 6 Z DAMPER ACTUATOR 1 2 3 X 4 5 6 Z DAM...

Page 6: ...T HAS R RC RH TERMINALS JUMPER TOGETHER AND WIRE AS SINGLE R TERMINAL DO NOT CONNECT THERMOSTAT O AND B TERMINALS TO CONTROL PANEL 2 ZONE 1 ZONE 2 ZONE 3 O B RC RH 1 2 G Y R W M6 M4 M1 VO VC ZONE 1 G Y R W M6 M4 M1 VO VC ZONE 2 G Y R W M6 M4 M1 VO VC ZONE 3 OPEN CLOSE DAMPER ZONE SYS ZONE 1 OPEN CLOSE DAMPER ZONE SYS ZONE 2 OPEN CLOSE DAMPER ZONE SYS ZONE 3 FAN FAN FAN G Y1 Y2 R W1 W2 O T874A THER...

Page 7: ...r ...

Page 8: ...Settings ...

Page 9: ...set it to ON See Fig 13 After 30 seconds place your hand in front of an air register in that zone to check for air flow at the register 2 Reset fan switch if provided to AUTO After 30 sec onds make sure air flow at register has stopped 3 Move heating set point lever on zone thermostat 10 F 6 C above room temperature to call for heat 4 After 30 seconds longer if necessary for time delay on plenum f...

Page 10: ...eter to sense the area temperature compare the readings Be care ful not to touch the thermometer or breathe on it 4 If the readings are the same replace the cover and put the system into operation 5 If the readings are different insert a small screw driver in the thermometer slot Fig 14 and turn it until the thermometers have the same reading 6 Replace the thermostat cover and put the system into ...

Reviews: