background image

S. M.  •  Rev. 6-93  •          •  ©Honeywell Inc. 1993  •  Form Number 69-0580—2

M3375

T874A,D Zone Thermostats/

Q674B,D,E Subbases

TABLE 2—THERMOSTAT/SUBBASE SPECIFICATIONS.

Thermostat/

Anticipator Range (A)

Thermostat/Subbase

Switching

Subbase

Heating

Cooling

Order Number

a

System

Fan

Color

(Adj.)

(Fixed)

T874A1465/Q674B1471 HEAT-OFF-COOL

ON-AUTO

White/Gray

Stg. 1—

Stg. 1—

T874A1465/Q674D1123 None

None

White/Gray

0.1 to 1.2

0 to 1.5

T874A1465/Q674E1379 HEAT-OFF-COOL-AUTO ON-AUTO

White/Gray

T874D1801/Q674B1463 HEAT-OFF-COOL

ON-AUTO

Beige/Brown

Stg. 1—

Stg. 1—

T874D1827/Q674B1471 HEAT-OFF-COOL

ON-AUTO

White/Gray

0.1 to 1.2;

0 to 1.2;

T874D1801/Q674D1115 None

None

Beige/Brown

Stg. 2—

Stg. 2—

T874D1827/Q674D1123 None

None

White/Gray

0.1 to 1.0.

0 to 1.0.

T874D1827/Q674E1379 HEAT-OFF-COOL-AUTO ON-AUTO

White/Gray

a

Subbase not included with thermostat; order separately.

Operation

On a 2-heat thermostat, the two stages of heat make

sequentially as the temperature drops. Make refers to the
mercury switch initiating a call for heat or cool.

There are about 2

°

 F [1

°

 C] between stages so that the

second stage makes only when the first stage cannot
handle the load. This is the interstage differential.

Recycling Notice

This control contains mercury in a sealed tube. Do not

place control in the trash at the end of its useful life.

If this control is replacing a control that contains mercury

in a sealed tube, do not place your old control in the trash.

Contact your local waste management authority for

instructions regarding recycling and the proper disposal of
this control, or of an old control containing mercury in a
sealed tube.

If you have questions, call Honeywell at 1-800-468-1502.

M3375

Installation Instructions for the Trained Service Technician.

TABLE 1—THERMOSTAT/SUBBASE AND SYSTEM COMPATIBILITY.

Thermostat/

Application

Subbase Model

Number

a

Mini-Zone

Mabs II, Mabs II-L

Mabs XX

Stages

T874A/Q674B

Zone 1; conventional

Zone 1; conventional

Any zone; conventional heat-cool. Single-stage

heat-cool.

heat-cool.

T874A/Q674D

Zones other than zone 1;

Zones other than zone 1;

Not applicable

Single-stage

conventional heat-cool.

conventional heat-cool.

T874A/Q674E

Not applicable

Not applicable

Any zone; conventional heat-cool. Single-stage

T874D/Q674B

Not applicable

Zone 1; conventional

Any zone; conventional heat-cool. Multistage

heat-cool.

T874D/Q674D

Not applicable

Zones other than zone 1;

Not applicable

Multistage

conventional heat-cool
and heat pump.

T874D/Q674E

Not applicable

Not applicable

Any zone; conventional heat-cool. Multistage

a

Subbase not included with thermostat; order separately.

Application

These T874A,D Zone Thermostats and Q674B,D,E

Subbases provide 24 to 30 Vac temperature control in
Honeywell Trol-A-Temp heating/cooling zone systems.

See Table 1 for thermostat/subbase and system compatibil-
ity; see Table 2 for thermostat specifications. For complete
Honeywell Trol-A-Temp System specification and appli-
cation information, refer to the system specification in-
cluded with the control panel.

Summary of Contents for TROL-A-TEMP Q674B

Page 1: ...d control in the trash Contact your local waste management authority for instructions regarding recycling and the proper disposal of this control or of an old control containing mercury in a sealed tube If you have questions call Honeywell at 1 800 468 1502 M3375 Installation Instructions for the Trained Service Technician TABLE 1 THERMOSTAT SUBBASE AND SYSTEM COMPATIBILITY Thermostat Application ...

Page 2: ...irectly on the wall 1 To mount on a horizontal outlet box install the sub base on the outlet box as shown in Fig 1 For a wall installation hold the subbase in position and mark holes for the anchors Fig 2 Obtain wall anchors locally Take care that the wires do not fall back into the wall opening Set aside subbase Drill two 3 16 in 4 8 mm holesandgentlytapanchorsintotheholesuntilflushwiththe wall 2...

Page 3: ...mostat Q674B D Subbase in single stage heating cooling two zone system POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED ZONE 1 O AND B TERMINALS MUST BE CONNECTED FOR PROPER SYSTEM OPERATION JUMPER RC AND RH TERMINALS TOGETHER AND WIRE AS SINGLE R TERMINAL DO NOT CONNECT W2 AND Y2 TERMINALS TO CONTROL PANEL 1 1 M1633 HEAT RELAY COOL RELAY ZONE 1 RELAY ZONE 2 RELAY Y2 Y1 O ...

Page 4: ...ult Fig 7 Typical hookup for MABS II and MABS II L Control Panels with T874A Thermostat Q674B D Subbases in single stage heating cooling zone system MABS II Control Panel shown MABS II L Control Panel hookup is the same 4 M1634 Y 2 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED JUMPER RC RH TOGETHER AND WIRE AS SINGLE R TERMINAL ZONE 1 O AND B TERMINALS MUST BE CONNECT...

Page 5: ...G DO NOT CONNECT W2 Y1 O G2 G1 RC RH B W2 W1 E ADD A ZONE EM HEAT RELAY SECOND STAGE RELAY FAN RELAY HEAT RELAY COOL RELAY CAC RELAY ZONE 1 RELAY ZONE 2 RELAY ZONE 3 RELAY A4 A3 A2 A1 T8 T7 T6 T5 T4 M6 M4 M1 ZONE 3 T8 T7 T6 T5 T4 M6 M4 M1 ZONE 2 T8 T7 T6 T5 T4 M6 M4 M1 ZONE 1 O1 G1 B1 E1 2 1 CHANGEOVER CONTROL COOL FAN HEAT EM HEAT 24 V 40 VA TRANSFORMER 4 5 6 Z DAMPER ACTUATOR 1 2 3 X 4 5 6 Z DAM...

Page 6: ...T HAS R RC RH TERMINALS JUMPER TOGETHER AND WIRE AS SINGLE R TERMINAL DO NOT CONNECT THERMOSTAT O AND B TERMINALS TO CONTROL PANEL 2 ZONE 1 ZONE 2 ZONE 3 O B RC RH 1 2 G Y R W M6 M4 M1 VO VC ZONE 1 G Y R W M6 M4 M1 VO VC ZONE 2 G Y R W M6 M4 M1 VO VC ZONE 3 OPEN CLOSE DAMPER ZONE SYS ZONE 1 OPEN CLOSE DAMPER ZONE SYS ZONE 2 OPEN CLOSE DAMPER ZONE SYS ZONE 3 FAN FAN FAN G Y1 Y2 R W1 W2 O T874A THER...

Page 7: ...r ...

Page 8: ...Settings ...

Page 9: ...set it to ON See Fig 13 After 30 seconds place your hand in front of an air register in that zone to check for air flow at the register 2 Reset fan switch if provided to AUTO After 30 sec onds make sure air flow at register has stopped 3 Move heating set point lever on zone thermostat 10 F 6 C above room temperature to call for heat 4 After 30 seconds longer if necessary for time delay on plenum f...

Page 10: ...eter to sense the area temperature compare the readings Be care ful not to touch the thermometer or breathe on it 4 If the readings are the same replace the cover and put the system into operation 5 If the readings are different insert a small screw driver in the thermometer slot Fig 14 and turn it until the thermometers have the same reading 6 Replace the thermostat cover and put the system into ...