background image

T8011R PROGRAMMABLE HEAT PUMP THERMOSTAT

68-0196–1

9

CHECKOUT

CAUTION

Damage to Compressor Possible.
Operating at too low of an outdoor temperature
may cause compressor damage.

Do not operate cooling if outdoor temperature is
below 50

°

F (10

°

C).

Allow compressor to remain off for five minutes before
restarting. Refer to manufacturer’s recommendations.

Heating

1.

Slide the SYSTEM switch to Heat and the FAN switch
to Auto.

2.

Press and hold the 

 key to raise the temperature

setting several degrees above the room temperature;
the heating equipment and fan should start.

3.

Press the 

 key to lower the temperature setting below

the room temperature. Heating equipment should stop.

Cooling

1.

Slide the SYSTEM switch to Cool and the FAN switch
to Auto.

2.

Press the 

 key to lower the temperature setting

several degrees below the room temperature; the
cooling equipment and fan should start.

NOTE:

If the unit does not start immediately, remember, the
thermostat has a built-in minimum off-time of five
minutes to protect the compressor. A flashing

or

indicates that the minimum off-timer is in effect.

3.

Press the 

 key to raise the temperature setting above

the room temperature. Cooling system should shut down.

Fan

1.

Slide the SYSTEM switch to Off and the FAN switch to
On. The fan should run continuously.

2.

Slide the FAN switch to Auto. The system turns the fan
on and off with the equipment.

Make certain all equipment responds properly to the
thermostat.

Sequence of Operations

The Fan, Heat and Cool outputs are relay controlled. A loss of
ac power, or a change in the SYSTEM switch setting can
cause the outputs to turn off. Table 3 shows the sequence of
operations for the Fan and System settings.

Em. Ht.

With the system switch at Em. Ht., the thermostat controls the
emergency heat. On a call for emergency heat, the E, G and
L terminals are energized and an indicator points to Em. Ht.
on the display. L terminal is powered continuously while
system switch is in Em. Ht. In severe weather, the W2
terminal may also energize.

Minimum Off-Timer

A minimum off-timer in the T8011R assures that the
compressor does not come on again for at least five minutes
after it turns off. The minimum off-timer is triggered when the
compressor turns off and when the SYSTEM switch position
is changed. If the compressor turns off when the setpoint is
changed, the minimum off-timer is triggered. Power
interruption and power restoration also trigger the minimum
off-timer. The minimum off-timer operates in first stage
heating or cooling. A flashing

or

indicates that the

minimum off-timer is in effect. The minimum off timer is
bypassed during the optional system checkout. See page 6.

Table 3. Sequence of Operations.

FAN Switch Settings

SYSTEM Switch Settings

Call for Action

Energize Terminals

Display Icons

Auto

Cool

None

O

None

Auto

Cool

Cooling

O,  Y,  G

Auto

Heat

None

B

None

Auto

Heat

Stage  1  Heat

B,  W1,  G

Auto

Heat

Stage  2  Heat

B,  W1,  W2,  G

Aux Ht  

Auto

Em.  Ht.

None

L

          Em Ht

Auto

Em.  Ht.

Stage  1  Heat

L,  E,  G

Em  Ht

Auto

Em.  Ht.

Stage  2  Heat

L,  E,  W2,  G

Em Ht and  

      Aux Ht

a

O terminal is powered continuously in cooling, B terminal is powered continuously in heating and the L terminal is

powered continuously in emergency heat as a function of the SYSTEM switch position even without a call for heat or
cool.

Summary of Contents for TRADELINE T8011R

Page 1: ...er satisfaction Large temperature display for quick easy readability Conveniently sized thermostat 5 1 2 x 3 1 2 with optional decorator cover plates 7 3 8 x 5 3 4 make it easy to install in a variety of locations Keys are located by the display for easy access FAN and SYSTEM switches are located on the lower edge to eliminate accidental setting changes Easy installation setup and system checkout ...

Page 2: ...lplate for wiring and mounting thermostat and Owner s Guide Power T8011R 24 Vac nominal 18 to 30 Vac 50 or 60 Hz Electrical Ratings First Stage Heating 02 to 1 5A run 7 5A inrush Second Stage Heating 02 to 1 5A run 3 5A inrush Cooling 02 to 1 5A run 7 5A inrush Fan 02 to 0 5A run 2 5A inrush Emergency Heat Output E 02 to 1 5A run 3 5A inrush Heating Changeover Valve B 02 to 0 5A run 2 5A inrush Co...

Page 3: ...of a control If you have questions call the Honeywell Customer Response Center at 1 800 468 1502 5 FEET 1 5 METERS YES NO NO NO M11338 Location Install the thermostat about 5 ft 1 5m above the floor in an area with good air circulation at average room temperature See Fig 2 Do not install the thermostat where it can be affected by drafts or dead spots behind doors and in corners hot or cold air fro...

Page 4: ...tat restrict all wiring to the shaded area in the center of the terminals See Fig 5 KEEP WIRING IN SHADED AREA MOUNTING SCREW HOLE MOUNTING SCREW HOLE WIRING ENTRANCE HOLE M11331 G C R Y W1 L W2 E B O Fig 5 Restrict wiring to shaded area The T8011R Heat Pump Thermostat is powered directly from the system transformer Refer to Fig 6 for typical wiring hookup Mounting Thermostat to Wallplate 1 Slide ...

Page 5: ... CONTACTOR COMPRESSOR CONTACTOR HEAT FAN RELAY RELAY EMERGENCY HEAT RELAY G C THERMOSTAT LOGIC THERMISTOR SENSOR POWER SUPPLY ON AUTO STAGE 2 RELAY STAGE 1 RELAY FAN SWITCH M11333 Fig 6 T8011R two stage heat one stage cool wiring diagram with manual changeover Fig 7 Mounting thermostat to wall plate DASHED LINES INDICATE TABS ON BACK OF THERMOSTAT ENGAGE TABS AT TOP OF THERMOSTAT WITH SLOTS ON MOU...

Page 6: ...the key momentarily displays 2 When the keys are released these one digit codes are no longer displayed 2 Setting C or F a Press the key again to display the current setting b Press the key to change the C or F indication 3 Setting Heat Cycle Rate see Table 1 for cycle rate options NOTE Cycle rate settings are for second stage heat First stage heat and cool are fixed at 3 cph a Press the key to di...

Page 7: ...d weekends Four time periods are available during weekdays and weekends WAKE LEAVE RETURN and SLEEP IMPORTANT Always press the keys with your fingertip or similar blunt tool Sharp instruments like pens and pencil points can damage the keyboard Setting the Current Time and Day 1 To Set Current Time Press Select twice Press or to set current time While setting the current time the word SET is displa...

Page 8: ...ress and hold the Hold and Select keys simultaneously The display will begin counting down from 36 to zero b The thermostat display will go blank then will display the current time and temperature c Release keys the program has reverted to the preprogrammed time and temperature settings Setting Temperature Hold Slide the SYSTEM switch to the heat or cool position Temporary Temperature Hold 1 Press...

Page 9: ... power or a change in the SYSTEM switch setting can cause the outputs to turn off Table 3 shows the sequence of operations for the Fan and System settings Em Ht With the system switch at Em Ht the thermostat controls the emergency heat On a call for emergency heat the E G and L terminals are energized and an indicator points to Em Ht on the display L terminal is powered continuously while system s...

Page 10: ...ACE THERMOSTAT PARTIAL DISPLAY OR IS FLASHING AND COOLING OR FIRST STAGE HEATING WILL NOT OPERATE INOPERATIVE THERMOSTAT SEE THE INSTALLER SETUP SECTION FOR INSTRUCTIONS STILL IN INSTALLER SETUP MODE RECONFIGURE THE DISPLAY SEE INSTALLER SETUP SECTION TEMPERATURE DISPLAY IS INCORRECT THERMOSTAT IS CONFIGURED FOR F OR C DISPLAY CHECK THAT C TERMINAL IS CONNECTED TO THE SYSTEM TRANSFORMER COMMON CHE...

Page 11: ...T8011R PROGRAMMABLE HEAT PUMP THERMOSTAT 68 0196 1 11 ...

Page 12: ... Kong Home and Building Control Honeywell Limited Honeywell Limitée 35 Dynamic Drive Scarborough Ontario M1V 4Z9 Honeywell Latin American Region 480 Sawgrass Corporate Parkway Suite 200 Sunrise FL 33325 68 0196 1 G H Rev 9 00 Home and Building Control Honeywell 1985 Douglas Drive North Golden Valley MN 55422 Printed in U S A on recycled paper containing at least 10 post consumer paper fibers www h...

Reviews: