background image

2

TP970 AND TP9600 SERIES PNEUMATIC THERMOSTATS

77-9382—1

INTRODUCTION

This Engineering Data sheet provides detailed information
on the operation of TP970 and TP9600 Series Pneumatic
Thermostats (Thermostats). These Thermostats use the
force-balance design with high nozzle feedback for stability.
The TP970 and TP9600 Series includes the following
thermostat models:

TP970A-D and TP9600A, B:
High capacity
Proportional control
Single temperature

TP971A-C and TP9610A, B:
Dual temperature
Day/night control (automatic switchover through
diaphragm logic)
Two sensing elements
Individual setpoint control

TP972A and TP9620A, B:
High capacity
Heating/cooling control (automatic switchover
through diaphragm logic)
Two sensing elements (one for heating control,
one for cooling control)

TP973A, B and TP9630A, B:
Low capacity
Proportional control
Single temperature

TP974A:
Room temperature sensor
Used as a remote temperature transmitter for the RP920
Pneumatic Controller

This Engineering Data sheet describes the TP973A, B and
TP9630A, B Thermostats first, because they are the
simplest.

FUNDAMENTALS OF THERMOSTAT
OPERATION

General

In force-balance design, two forces oppose each other until
they are equal, or balanced. The TP970 and TP9600 Series
Thermostats use the force of the bimetal to close the flapper
over the nozzle and the opposing force of the air pressure in
the nozzle chamber to lift the flapper (see the Flapper-
Nozzle Operation section). When the forces are equal, a
force-balance condition exists.

The throttling range setting and the calibration reference
temperature determine the Thermostat span and calibration
point. At control point the nozzle-flapper-bimetal assembly
(acting through the calibration screw, setpoint cam, and the

throttling range (TR) adjustment) has a fixed branchline
pressure (BLP) for each temperature within the temperature
and throttling range settings. The forces within the nozzle-
flapper-bimetal assembly always seek a balanced condition;
giving the same BLP for the same temperature regardless of
fluctuations in main air or the relative positions of the nozzle,
flapper, and bimetal.

Flapper-Nozzle Operation

Flapper-nozzle operation is generally the same for all TP970
and TP9600 Thermostats. The Thermostat provides a
branchline air pressure that is a function of the ambient
temperature in the room or controlled space. As shown in
Figure 1, the force of the temperature-sensing bimetal acting
on one side of the flapper (Force A) is balanced by the
feedback force of the pilot pressure through the nozzle
acting on the other side of the flapper (Force B).

Fig. 1. Flapper-Nozzle-Bimetal Assembly.

The position of the flapper over the nozzle changes and
creates a new pilot pressure when the bimetal force changes
(through temperature or setpoint change). This pilot pressure
feeds into the valve unit, which converts the low-capacity
pilot pressure to a high-capacity branchline change (see the
Valve Unit Operation section). Feedback at the nozzle
regulates the pressure to negate the effect of normal main
air supply fluctuations on the branch line.

Adjusting the throttling (proportioning) range changes the
flapper lever position. Moving the setpoint cam changes the
bimetal operating force and thus the setpoint.

Valve Unit Operation

TP970, TP9600, TP971, TP9610, TP972, and TP9620
Thermostats use force-balance valve units to amplify airflow
and minimize air consumption without loss of required device
capacity. Figure 2 is a cross-section of a TP970 and TP9600
Thermostat showing the relationship of the valve unit to the
bimetal, nozzle, and other components.

IN BALANCED STATE, 
FORCE B EQUALS FORCE A

NOZZLE

FLAPPER

THROTTLING RANGE
ADJUSTMENT

BIMETAL

SETPOINT 
CAM

CALIBRATION
SCREW

SETPOINT
KNOB

FORCE B

FORCE A

C6046

Summary of Contents for TP9600 Series

Page 1: ...ts 4 General 4 Operation 5 Direct Action 5 Reverse Action 5 TP970A D and TP9600A B High Capacity Single Temperature Thermostats 6 General 6 Operation 6 Direct Action 6 Reverse Action 7 TP971A C and TP9610A B High Capacity Dual Temperature Thermostats 7 TP971B and TP9610B 7 TP971C 7 TP971A and TP9610A 7 Daytime Operation 8 Nighttime Operation 8 Manual DAY Override 9 TP972A and TP9620A High Capacity...

Page 2: ... a fixed branchline pressure BLP for each temperature within the temperature and throttling range settings The forces within the nozzle flapper bimetal assembly always seek a balanced condition giving the same BLP for the same temperature regardless of fluctuations in main air or the relative positions of the nozzle flapper and bimetal Flapper Nozzle Operation Flapper nozzle operation is generally...

Page 3: ...METAL FILTER RESTRICTOR BRANCH LINE THROTTLING RANGE ADJUSTMENT CALIBRATION SCREW SETPOINT CAM SETPOINT KNOB NOZZLE BRANCHLINE PRESSURE TAP BRANCHLINE CHAMBER BLEED PILOT PILOT CHAMBER EXHAUST VALVE MAIN LINE TP970 TP9600 TP971 TP9610 TP972 and TP9620 Thermostats are designed around a valve unit for flow amplification rather than conventional pressure amplification Branchline chamber and pilot cha...

Page 4: ... operation is very important to understanding TP970 TP9600 TP971 TP9610 TP972 and TP9620 operation As can be seen from Figures 3 4 and 5 pilot pressure changes affect BLP changes in the same ratio There is no pressure gain to amplify errors as with other pneumatic Thermostats Still the main air supply being switched through the valve unit provides fast high capacity increase and decrease of BLP TP...

Page 5: ... the bimetal are again in equilibrium with the opposing force 8 psi 55 kPa times the area of the nozzle at the flapper A reduction in setpoint causes the reverse to happen The calibration screw allows for matching the bimetal start position with the indicated setting on the setpoint cam to achieve an 8 psi 55 kPa BLP at the indicated setpoint The TR adjustment Fig 9 provides a means for changing t...

Page 6: ...reater temperature change at the bimetal to throttle the flapper over the nozzle The result is a wider TR or very low sensitivity for instance a 1 F 0 56 C change in temperature results in only a 1 psi 7 kPa BLP change TP970A D AND TP9600A B HIGH CAPACITY SINGLE TEMPERATURE THERMOSTATS General The TP970 and TP9600A B Thermostats Fig 10 are the basic TP973 with a valve unit added for greater capaci...

Page 7: ... TP9610A On the TP971A and TP9610A direct acting Thermostats Fig 12 the daytime bimetal controls the system when the main air pressure is 13 psi 90 kPa The nighttime element controls the system when the main air pressure reaches 18 psi 124 kPa Models are available with switchover pressures of 16 to 21 psi 110 to 145 kPa and 20 to 25 psi 138 to 172 kPa Fig 12 TP971 and TP9610 Day Night Thermostat T...

Page 8: ...and TP9610 Operation on Day Cycle Main Air Pressure 13 psi 90 kPa Nighttime Operation In Figure 14 the main air pressure is at 18 psi 124 kPa for nighttime operation The airflow shown by arrows is the same as the daytime cycle up to Logic Module A and Logic Module B The main air pressure 18 psi 124 kPa is now enough to overcome the spring loaded diaphragm in Logic Module A Because the manual overr...

Page 9: ...ic switchover The secondary branch line operates with the manual DAY AUTO lever position as follows 1 System in normal daytime operation 13 psi 90 kPa main air pressure Fig 13 dotted lines 2 Move the manual DAY AUTO lever to the DAY position It snaps back to AUTO because there is no air pressure on logic switch C Fig 13 The secondary branch line is always at the main air pressure when the system o...

Page 10: ... the system to normal operation by manually switching the DAY AUTO lever to AUTO In the preceding situation the P E switch contacts are closed This is because the secondary BLP is under 15 psi 103 kPa the DAY AUTO lever is held in the DAY position by pressure on Logic Module C and the Thermostat uses its daytime bimetal because the airflow through Logic Module D is closed off TP972A AND TP9620A HI...

Page 11: ...rride and the independent setpoint adjustment Cooling control requires a lower pressure in the main air supply Figure 17 shows the workings and traces the air path within the TP972A and TP9620A when it is controlling with the cooling bimetal NOTE The TP972A2036 A2168 and A2176 and TP9620A limited control range Thermostats have separate concealed setpoints for heating and cooling and limit the heat...

Page 12: ... the Module The air pressure is applied to the diaphragm of Logic Module B closing off Port B1 and opening Port B2 Now the air is directed to the flapper nozzle of the heating bimetal and the Thermostat controls in the heating mode TP974A ROOM TEMPERATURE SENSOR General The TP974A Fig 19 20 is a bimetal element proportioning temperature sensor for either two or one pipe applications The sensor bim...

Reviews: