Specifications
TP1MAN Issue 3 Apr 06 (MAN0630)
52
General
Environmental
Use
Wall mounted single channel control panel for the local annunciation of gas
hazards as detected by the Zareba range of Sensepoint gas detectors.
Suitable for small scale, indoor installations requiring a self contained gas
detection and control system
User interface
Operation
Single Test/Accept/Reset push-button for normal operational use. Three
further hidden push buttons for configuration via intuitive menu system
Backlit
display
Channel status including measuring range, units of measure, digital gas
reading, bar graph displays 0-100% full scale, status indicators including
alarm set point, alarm activated, and power health
Other
Indicators
Ultra-bright LEDs: alarm (red), power (green), fault (amber)
Audible Alarm
85 dBA at 1 m / 90 dBA at 1 foot, user hush facility, re-activated on new event
Terminations
Accessed via hinged front cover (latch to hold open as required). All cable/
conduit entry via pre-formed knockouts in gland plate at bottom of controller.
Screw terminals suitable for use with 0.5 mm
2
(20 AWG) to 2.5 mm
2
(14 AWG)
wires. Crimped connection recommended. Take care not to over tighten screw
terminals. The recommended torque setting for the terminals is 12 lb in.
IP Rating
Indoor use, IP44 in accordance with EN60529:1992
Weight
2.5 Kg / 5.5 lb (approx.)
Operating
Temp Range
-10°C to +40°C / 14°F to 104°F continuous (up to +50°C/122°F intermittent)
Operating
Humidity
Range
10 to 90% RH (non condensing)
Operating
Pressure
Range
90-110 kPa
Storage
-40
o
C to +80
o
C / -40
o
F to +176
o
F, 20 to 80% RH (non condensing)
Specifications