Cooling System (CT8775C Only)
CAUTION
Equipment Damage Hazard.
Can cause permanent damage to compressor or other equipment.
Do not operate cooling when outside temperature is below 50°F (10°C).
Allow compressor to remain off for five minutes before restarting.
See equipment manufacturer instructions.
❑
Slide the system switch to Cool and the Fan switch to Auto.
❑
Turn the dial counterclockwise to lower the temperature setting several degrees below the room temperature.
NOTE:
If a call for cooling is made before the compressor has been off for five minutes, or if a power interruption
occurs while the compressor is running, the thermostat will go into a five-minute delay to protect the com-
pressor. The snowflake
will flash during this delay.
❑
After five minutes, the thermostat will display a solid snowflake
to indicate the thermostat has called for cooling.
The cooling system should turn on.
❑
Turn the dial clockwise to raise the temperature setting above the room temperature.
❑
The snowflake
will disappear from the display to indicate the thermostat has ended the call for cooling. The
cooling system should turn off.
Fan (CT8775C Only)
❑
Slide the system switch to Off and the fan switch to On. The fan should run continuously.
❑
Slide the Fan switch to Auto. The fan should turn off.