VisionPRO® IAQ
69-1816EFS—03
**See page 6
0502
Furnace filter
alert options
0
Timer counts Heat & Cool run time
1
Timer counts Cool run time only
0510
Humidifier pad
change alert
*
E
Auto Discover
**
0
Off
1
90 calendar days or 30 days run time
2
180 calendar days or 60 days run time
3
365 calendar days or 90 days run time
0520
UV lamp change
alert
E
Auto Discover
**
0
Off
1
365 calendar days (1 year)
2
730 calendar days (2 years)
0530
Adaptive Intelligent
Recovery™
1
On
**
0
Off
0540
Program periods
4
4 program periods
(Wake, Leave, Return, Sleep)
2
2 program periods (Wake, Sleep)
0580
Compressor off
time (min.)
5
5 minute compressor off time
**
[Other options: 0 to 4 minutes]
0600
Heat temperature
range stop
90 Max. heat temperature setting is 90°F (32°C)
[Other options: 40 to 90°F (4°C to 32°C)]
0610
Cool temperature
range stop
60 Min. cool temperature setting is 60°F (15°C)
[Other options: 60-99°F (15°C to 37°C)]
0640
Clock format
12 12-hour time (i.e., "3:30 pm")
24 24-hour time (i.e., "15:30")
0650
Extended fan
timer (heat)
0
Off
[Other options: Fan runs for 30, 60, 90 or 120 seconds after call for
heating ends]
0660
Extended fan
timer (cool)
0
Off
[Other options: Fan runs for 30, 60, 90 or 120 seconds after call for
cooling ends]
0670
Keypad lock
0
Keypad unlocked (fully functional)
1
Partially locked (access to temperature settings only)
2
Fully locked
0680
Heat temperature
control
2
Standard temperature control (recommended)
1
Choose if room is warmer than set temperature
3
Choose if room does not reach set temperature
0690
Cool temperature
control
2
Standard temperature control (recommended)
1
Choose if room is cooler than set temperature
3
Choose if room does not reach set temperature
0700
Temperature
display offset
0
Thermostat displays actual room temperature
[Other options: -3°F to +3°F offset (-1.5°C to 1.5°C)]
0701
Humidity
display offset
0
Thermostat displays actual room humidity
[Other options: -5% to +5% offset]
0710
RESET
0
No reset
1
Reset installer options & program schedule to factory default (only
date and time settings are retained)
Setup function
Settings & options (factory default in bold)
Installer setup
* Humidifier Pad replacement will be displayed in the user interface as run
time days if ISU 372 is set to 1 or 3 and calendar days if ISU 372 is set to 0.