Installation Guide
69-1816EFS—03
**See page 6
0372
Indoor humidifica-
tion control
E
Auto Discover
**
0
Off
1
Humidify (no frost protection)
3
Humidify (with frost protection)
0374
Humidifier fan action 0
Humidify only while fan or heat is on
1
Humidify forces fan on
2
Humidify only when heat is on
3
Humidifier operates independent of fan
0379
Dehumidification
control
0
No dehumidification control
1
Dehumidify with air conditioner
3
Whole house dehumidifier
0383
Over-cooling limit
3
3°F (1.5°C)
[Other options: 1, 2 (1°F or 2°F/0.5°C to 1.5°C)]
0384
Dehumidification
fan action
0
System fan turns on with dehumidifier
1
Dehumidifier operates independent of fan
0390
Dehumidification
away mode
0
No
1
Yes
0391
Dehum. away mode
fan setting
0
Fan auto
1
Fan always on
2
Fan circulate
0392
Dehum. away mode
low limit temp.
76 Low limit temperature 76°F (24°C)
[Other options: 70°F to 80°F (21°C to 27°C)]
0393
Dehum. away mode
temp. setting
85 Away temperature 85°F (29°C)
[Other options: 70°F to 99°F (21°C to 37°C)]
0394
Away dehumidifica-
tion setting
65 Away humidity level 65%
[Other options: 55% to 70%]
0400
Ventilation control
0
No ventilation
1
Ventilation always allowed
2
Ventilation not allowed during sleep period
0401
Number of
bedrooms
2
Two bedrooms
[Other options: 1 to 6]
0402
Size of house
10 1,000 square feet
[Other options: 11 to 50 (1,100 to 5,000 square feet)]
0403
Ventilation level
160 CFM (cubic feet per minute)
[Other options: (30 to 195 CFM)]
0404
Max. ventilation
% limit
50 50% ventilation limit
[Other options: 30% to 60% or 100%]
P
Meets ASHRAE 62.2 standard
F
Does not meet ASHRAE 62.2 standard
0405
Ventilation fan
action
1
Ventilation on forces fan on
2
Ventilation does not force fan on
0406
Ventilation in high
humidity
1
On (heat mode only)
0
Off
0500
Furnace filter
change alert
E
Auto Discover
**
7
270-day run time
0
Off
8
365-day run time
1
10-day run time
9
30 calendar days
2
30-day run time
10 60 calendar days
3
60-day run time
11 90 calendar days
4
90-day run time
12 120 calendar days
5
120-day run time
13 180 calendar days
6
180-day run time
14 365 calendar days
Setup function
Settings & options (factory default in bold)
Installer setup