TC500A-N/TC500A-W COMMERCIAL THERMOSTAT

31-00399M-01 | Rev.10-20

2

Introduction

TC500A-N/TC500A-W Commercial Touchscreen 

Thermostat is designed to be wall-mounted indoors. 

Mount in a clean, dry location away from windows, air 

ducts, and other places where environmental factors may 

affect temperature and humidity readings. If you mount 

the Thermostat unit on the interior of an outside wall, 

thoroughly insulate so outside air behind the sensor does 

not affect the sensor reading. 

To meet requirements of the Americans with Disabilities 

Act, mount no higher than 48" from the floor and with a 

minimum clear floor space of 30" X 48" (760 X 1220 mm).

When installing this product

1.

Read these instructions carefully. Failure to follow 

them could damage the product or cause a hazard

-

ous condition.

2.

Check the ratings given in the instructions and 

marked on the product to make sure the product is 

suitable for your application.

3.

Installer must be a trained, experienced service tech

-

nician.

4.

After installation is complete, check the product 

operation.

5.

Be sure wiring complies with all applicable codes, 

ordinances and regulations.

WARNING

Electrical Shock Hazard.

Can cause severe injury, death or property 

damage.                                                                        

Disconnect the power supply before beginning 

installation to prevent electrical shock and 

equipment damage. More than one power supply 

may have to be disconnected.

MERCURY NOTICE

If this control is replacing a control that contains 

mercury in a sealed tube, do not place your old 

control in the trash. Dispose of properly. Contact 

your local waste management authority for 

instructions regarding recycling and the proper 

disposal of an old control. If you have questions, 

contact Honeywell Customer Care Center.

Location

Do not install the Thermostat unit where it can be affected 

by:

— drafts or dead spots behind doors and in corners.

— hot or cold air from ducts.

— radiant heat from sun or appliances.

— concealed pipes and chimneys.

— unheated (uncooled) areas such as an outside wall

-

behind the thermostat.

IMPORTANT

To avoid electrical interference, which can cause 

erratic performances, keep wiring runs as short as 

possible and do not run thermostat wires adjacent 

to the line voltage electrical distribution systems. 

Use shielded cable. The cable shield must be 

grounded only at the controlled equipment case.

WHEN USED TO SENSE ROOM TEMPERATURE

Install the Thermostat about 4 ft. (1.2m) above the floor in 

an area with good air circulation at average temperature. 

(See Fig. 1). Confirm mounting height meets Americans 

with Disabilities Act requirements.

WHEN NOT USED TO SENSE ROOM TEMPERATURE

When using the remote-mounted temperature (and 

humidity) sensor(s) to sense ambient conditions, install 

the Thermostat in an area that is accessible for setting and 

adjusting the temperature and settings.

Fig. 1. Typical mounting location of thermostat

This symbol on our product shows a crossed-out “wheelie-

bin” as required by law regarding the Waste of

Electrical and Electronic Equipment (WEEE) disposal. This 

indicates your responsibility to contribute in saving

the environment by proper disposal of this Waste i.e. Do not 

dispose of this product with your other wastes. To

know the right disposal mechanism please check the 

applicable law.

WEEE

WEEE (Waste of 

Electrical and 

Electronic Equipment)

• At the end of the product life, 

dispose of the packaging and 

product in an appropriate recycling 

center.

• Do not dispose of the device with 

the usual domestic refuse.

• Do not burn the device.

NO

YES

4 FEET

(1.2 METERS)

NO

NO

Summary of Contents for TC500A-N

Page 1: ...a instruktion skall förvaras tillsammans med regler eller anläggningsdokumentationen Elektrisk anslutning med 230 VAC får endast utföras av behörig personal DK Opbevar denne vejledning sammen med regler eller med anlægsdokumentationen Elektrisk tilslutning for 230 VAC bør kun foretages af autoriserede personer N Denne veiledningen skal oppbevares sammen med regler eller anleggsdokumentasjonen Elek...

Page 2: ...ntrol If you have questions contact Honeywell Customer Care Center Location Do not install the Thermostat unit where it can be affected by drafts or dead spots behind doors and in corners hot or cold air from ducts radiant heat from sun or appliances concealed pipes and chimneys unheated uncooled areas such as an outside wall behind the thermostat IMPORTANT To avoid electrical interference which c...

Page 3: ...1 Y2 Y3 are powered from the Thermostat s transformer Minimum load includes Thermostat and analog outputs at full load Max 10V voltage output with 2Kohms load Every relay output is N O Normally Open contacts with a maximum switch rating of 24VAC 1A 24VA The allowed maximum load is 96VA which assumes all 8 relay output loads are powered from the controller transformer Actual power requirements depe...

Page 4: ... with the wall 5 Pull the wires through the wiring opening of the wall plate and position the wallplate over the mounting holes 6 Insert the screws into the holes and tighten screw torque 0 1Nm Mounting the wallplate on the gang box optional The thermostat wallplate can be mounted vertically on a US 2 4 or UK 75 75mm gang box which is already installed onto the wall and wired 1 Before mounting the...

Page 5: ...UI1 1 Universal input COM Common UI2 2 Universal input COM Common Sylk Sylk bus master power output Sylk bus master power output RS485 BACnet Communications _ BACnet Communications R RC Jumper between R and RC for single transformer system remove the jumper in two transformer system 24VAC RC 24VAC power from cooling Class 2 transformer G Fan Y1 Relay output Compressor contactor stage1 Y2 Relay out...

Page 6: ...rt stranded wire end into the wiring terminal push the Release tool into the Tool hole and insert the wires Fig 7 Wire release 4 Push excess wire back into the hole 5 Check for loose or frayed wire that may cause a short Mounting the display unit After all wiring activities have been performed install the display unit onto the wallplate 1 Hold the display unit in a tilted position so that the latc...

Page 7: ...TC500A N TC500A W COMMERCIAL THERMOSTAT 7 31 00399M 01 Rev 10 20 DIMENSIONS 3 19 32 91 2 mm 4 15 32 113 7 mm 4 x 11 32 9mm 2 3 8 60 3mm 3 1 4 82 75mm 4 x 3 16 4 5mm ...

Page 8: ...AL THERMOSTAT U S Registered Trademark 2020 Honeywell International Inc 31 00399M 01 Rev 10 20 Honeywell Building Solutions Honeywell 715 Peachtree Street NE Atlanta GA 30308 customer honeywell com buildingcontrols honeywell com ...

Reviews: