WIRELESS INSTALLATION & INTEGRATION REFERENCE GUIDE FOR TB7200/TB7300/TB7600 SERIES THERMOSTATS
49
63-4522—02
Table Notes
1.
For TB72xx and TB73xx devices, usable enumerations for the System Mode depends on Sequence of Operation
selected. The Auto mode can be used only if the AutoMode configuration parameter is set to On.
2.
For TB72xx and TB73xx, the default value of System Mode depends on the Local Sequence of Operation selected
and the value of the AutoMode configuration parameter.
3.
TB7200 does not have fan outputs and fan mode commands
TB7300 fan mode input is dependent on local Fan Configuration
TB7600 fan mode inputs accepted are: Auto and On. All other modes are rejected.
Available Fan modes for the TB73xx thermostat is dependent on the local configuration of the Fan Menu parameter
Sequence Of
Operation
Function
Auto Mode parameter
Enabled
Auto Mode parameter
Disabled
1
Cooling Only
Cool
Cool
2
Cooling with Reheat
Auto
Heat
3
Heating Only
Heat
Heat
4
Heating with Reheat
Heat
Heat
5
Cooling/Heating 4 Pipes
Auto
Heat
6
Cooling/Heating 4 Pipes with Reheat
Auto
Heat
Fan Menu
Configuration
Fan Modes Index Accepted
Default Value
1
1 Low - 2 Med - 3 High
High
2
1 Low - 2 High
High
3
1 Low - 2 Med - 3 High - 4 Auto
High
4
1 Low - 2 High - 3 Auto
High
5
1 Auto -2 On
Auto