WIRELESS INSTALLATION & INTEGRATION REFERENCE GUIDE FOR TB7200/TB7300/TB7600 SERIES THERMOSTATS
41
63-4522—02
This object is linked to UI3 input on all TB7200 and TB7300 series thermostat when used in binary mode. The Not Activated /
Activated flag status is changed upon a local contact closing on the input and will also result in the SupplyTemp Numeric to
respond from one end of its range to the other.
Object Name
Object Type
Range Restrictions
Dehumidification Lockout
Boolean Writable
falseText=Disabled,trueText=Enabled
Aux Command
Boolean Writable
falseText=Off,trueText=On
Units
Boolean Writable
falseText=Imperial,trueText=SI
Progressive Recovery
Boolean Writable
falseText=Off,trueText=Active
Aux Contact
Boolean Writable
falseText=Normally Opened,trueText=Normally Closed
Fan Purge Delay
Boolean Writable
falseText=Off,trueText=On
Display Scale
Boolean Writable
falseText=C,trueText=F
Menu Scroll
Boolean Writable
falseText=No Scroll,trueText=Scroll Active
Config Motion Detection
Boolean Writable
falseText=No PIR,trueText=PIR Cover Present
AO2 RA/DA
Boolean Writable
falseText=Direct Acting,trueText=Reverse Acting
BO5 Time Base
Boolean Writable
falseText=15 Minutes,trueText=10 Seconds
BO5 Contact Function
Boolean Writable
falseText=Normally Opened,trueText=Normally Closed
Room Temperature Override
Boolean Writable
falseText=Normal,trueText=Override
Config Setpoint Type
Boolean Writable
falseText=Permanent,trueText=Temporary
Outdoor Temperature Override
Boolean Writable
falseText=Normal,trueText=Override
Room Humidity Override
Boolean Writable
falseText=Normal,trueText=Override
Auto Mode Enable
Boolean Writable
falseText=Disabled,trueText=Enabled
Setpoint Function
Boolean Writable
falseText=Dual Setpoints,trueText=Attached Setpoints
Reheat Time Base
Boolean Writable
falseText=15 Minutes,trueText=10 Seconds
Auto Fan
Boolean Writable
falseText=Auto Speed,trueText=Auto Speed / Auto Demand
RH Display
Boolean Writable
falseText=Disabled,trueText=Enabled
Control Type
Boolean Writable
falseText=On/Off,trueText=Floating
Direct Reverse Acting
Boolean Writable
falseText=Direct Acting,trueText=Reverse Acting
Fan Options
Boolean Writable
falseText=On Heat,trueText=Auto Heat
Frost Protection
Boolean Writable
falseText=Off,trueText=On
Fan Control
Boolean Writable
falseText=Off,trueText=On
Mechanical Cooling Enable
Boolean Writable
falseText=Off,trueText=On
Comfort Mode
Boolean Writable
falseText=Comfort,trueText=Economy
Reversing Valve Config
Boolean Writable
falseText=Normally Cool,trueText=Normally Heat
Comp Aux Lockout
Boolean Writable
falseText=Off,trueText=On
Dehumidification Lockout Functions
Boolean Writable
falseText=Disabled,trueText=Enabled
Heat No/Nc
Boolean Writable
falseText=Normally Closed,trueText=Normally Openend
Cool No/Nc
Boolean Writable
falseText=Normally Closed,trueText=Normally Openend
Pulsed Heat
Boolean Writable
falseText=Off,trueText=On