T921A,B,E-G

INSTALLATION

Installation

!

CAUTION

Disconnect power supply before installation to
prevent electrical shock and equipment damage.

WHEN INSTALLING THIS PRODUCT…

1. Installer must be a trained, experienced service tech-

nician.

2. All wiring must comply with applicable electrical

codes, ordinances and regulations.

3. Do not exceed the ratings listed on the device name-

plate.

4. After the installation is complete, conduct a thorough

checkout of the product operation.

LOCATION

Locate the thermostat about 5 feet [1.5m] above the

floor in an area with good air circulation at average room
temperature.

Do not mount the thermostat where it can be affected by:
— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from the sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall

behind the thermostat.

MOUNTING

1. Disconnect power supply before installation to pre-

vent electrical shock and equipment damage.

2. Loosen the locking screw at the bottom of the case

with an Allen wrench.

3. Lift off the thermostat cover.
4. Remove the mounting screws that secure the thermo-

stat to the backplate and remove the backplate.

5. Fasten the backplate to the conduit box (see Fig. 3).

Use the 127246A Adapter Plate Assembly (ordered sepa-
rately) to mount the thermostat vertically on the horizontal
conduit box; or to mount the thermostat horizontally on the
vertical conduit box (see Fig. 4).

NOTE: When an accessory adapter plate is used, fasten the

adapter plate to the conduit box with the two screws
provided. Then fasten the backplate to the adapter plate.

6. Make all electrical connections to the terminals on

the back of the thermostat before mounting the instrument
on the backplate. Refer to the Wiring section.

7. Mount the thermostat on the backplate with the mount-

ing screws.

8. After performing the checkout tests, replace the ther-

mostat cover and tighten the locking screw.

ADD FACEPLATES FOR HORIZONTAL
MOUNTING (T921A,B,E ONLY)

T921 models are shipped with a faceplate for vertical

mounting. When mounting the T921A,B,E horizontally,
see Table 2 to order the faceplate with the appropriate scale.
NOTE: Do not mount the T921F,G horizontally.

TABLE 2—ACCESSORY FACEPLATE

Scale

Part No.

56

°

 to 84

°

 F [13

°

 to 29

°

 C]

135135A

13

°

 to 29

°

 C [56

°

 to 84

°

 F]

135135B

42

°

 to 75

°

 F [5

°

 to 24

°

 C]

135135C

66

°

 to 95

°

 F [19

°

 to 35

°

 C]

135135D

56

°

 to 84

°

 F [13

°

 to 29

°

 C]

135135C

a

a

Blank faceplate.

Affix the accessory faceplate when mounting the

T921A,B,E models horizontally with contemporary cov-
ers. Peel the backing strip from the faceplate and place it
lightly over the vertical faceplate. Align the edges and
corners and make sure the scales align with the markings.
Press firmly over the entire surface. Do not attempt to
reapply once the faceplate has been mounted.

Fig. 3—Vertical mounting of T921A,B,E-G
Thermostats on vertical conduit box.
T921A,B,E Thermostats can also be mounted
horizontally on horizontal conduit box using
add-on faceplate. (Do not mount T921F,G
horizontally.)

H O N

E Y W

E L L

80 
70 
60

60 70 80 90

NOTE:  ACCESSORY FACEPLATE FOR USE WHEN 
THE THERMOSTAT IS MOUNTED HORIZONTALLY.  
PEEL OFF BACKING AND APPLY OVER VERTICAL 
FACEPLATE AFTER MOUNTING IS COMPLETE.

MOUNTING 
SCREWS

BACKPLATE

CONDUIT 
BOX

COVER

LOCKING 
SCREW

M9037

Summary of Contents for T921A

Page 1: ...ls COOL HEAT changeover switch in the T921B Night setback mechanism and switch in the T921E A spdt single pole double throw Class 2 auxiliary switch in the T921F G which operates at the low T921F and high T921G end of the throttling range A bellows element adjusts the potentiometer slider to regulate motor operation Various temperature ranges are available All models are available with a thermomet...

Page 2: ... also include the 127246A Adapter Plate As sembly for vertical mounting on a horizontal conduit box or for horizontal mounting on a vertical conduit box STANDARD MODEL MODELS T921A Heating or cooling applications T921B Is the same as the T921A but includes a cool heat changeover switch T921E Includes a switch and heater that provide a night setback of approximately 10 F 5 5 C T921F Includes an spd...

Page 3: ...35B 42 to 75 F 5 to 24 C 135135C 66 to 95 F 19 to 35 C 135135D 56 to 84 F 13 to 29 C 135135Ca a Blank faceplate REPLACEMENT PART 130224 Locking Cover Knob OPTIONAL SPECIFICATION USING THE T991B Alternate proportional control similar to the T921A but uses an outdoor temperature automatic control point reset T991B with 3 1 2 1 reset and 50 to 120 F 10 to 49 C temperature setting scale when the outdo...

Page 4: ...nduit box with the two screws provided Then fasten the backplate to the adapter plate 6 Make all electrical connections to the terminals on the back of the thermostat before mounting the instrument on the backplate Refer to the Wiring section 7 Mountthethermostatonthebackplatewiththemount ing screws 8 After performing the checkout tests replace the ther mostat cover and tighten the locking screw A...

Page 5: ...tat before mounting the instrument onto the conduit box Terminal locations for all models are shown in Fig 5 Note the difference in terminal designa tions for the auxiliary switch on the T921F and G The H Heater terminal on the T921E is a black leadwire Typical wiring diagrams are shown in Figs 6 through 10 Wire the T921 color to color when the modulating motor must drive the valve or damper open ...

Page 6: ...L IS A BLACK LEADWIRE T R W B T B W R H 2 2 TRANSFORMER Fig 8 Typical wiring diagram for T921E L1 HOT L2 1 1 SERIES 90 MODULATING MOTOR T921B M5992 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED INTERCHANGE B AND W CONNECTIONS TO REVERSE DIRECTION OF MOTOR TRAVEL T R W B T B W R 2 2 TRANSFORMER B W SUMMER COOL WINTER HEAT Setting andAdjusting TEMPERATURE SETTING Adjust a...

Page 7: ...CATOR LOCK SCREW BELLOWS SETTING ADJUSTMENT KNOB POTENTIOMETER WIPER 1 1 SUMMER WINTER COOL HEAT CHANGEOVER SWITCH ON T921B ONLY NIGHT SETBACK SWITCH ON T921E ONLY M9039 80 70 60 In the T921 a vapor filled bellows moves the potenti ometer wiper by expanding or contracting in proportion to temperature changes As the wiper moves the appropriate motor winding is energized opening or closing the valve...

Page 8: ...ng applica tion Raise the setpoint gradually the auxiliary switch should make R W before the setting indicator reaches room temperature As the setting indicator moves above room temperature the valve or damper should open 4 If the valve or damper responds properly to the thermostat move the setpoint to the desired temperature M5991 2 5 F 1 5 C SETPOINT TEMPER ATURE 2 5 F 1 5 C R B MAKES TEMPERATUR...

Reviews: