Honeywell T921A User Manual Download Page 3

3

60-2242—2

T921A,B,E-G

SPECIFICATIONS

Fig. 1—T921 approximate installation dimen-
sions in in. [mm].

SETTING
ADJUSTMENT 
KNOB

1

1

M9107

3     

 [84]

5

16

5     

 [145]

11
16

5     

[137]

3
8

7     

[194]

5
8

1

16

3     [78]

5

16

3     [84]

3
8

3    [86]

5

16

5     [135]

1
4

2     [57]

FOR VERTICAL
CONDUIT BOX (2)

HORIZONTAL CONDUIT BOX

ACCESSORY ADAPTER PLATE (127246A) FOR
MOUNTING ON HORIZONTAL CONDUIT BOX

2-11/16 [69] INCHES FOR 
T921F, G MODELS.

7640HX Averaging Element Mounting Kit: For mount-

ing in existing installations where access to the duct
is impractical.

Q615A Enclosure: To protect the device when mounted

outside; splash proof.

801534 Calibration Wrench.
107324A Bulb Holder: For mounting the bulb in a duct.
34886A Outdoor Bulb Shield: To protect the outdoor

bulb mounting.

Fig. 2—T991B approximate installation
dimensions in in. [mm].

TABLE 1—ACCESSORY FACEPLATE.

Scale

Part No.

56

°

 to 84

°

 F [13

°

 to 29

°

 C]

135135A

13

°

 to 29

°

 C [56

°

 to 84

°

 F]

135135B

42

°

 to 75

°

 F [5

°

 to 24

°

 C]

135135C

66

°

 to 95

°

 F [19

°

 to 35

°

 C]

135135D

56

°

 to 84

°

 F [13

°

 to 29

°

 C]

135135C

a

a

Blank faceplate.

REPLACEMENT PART:

130224 Locking Cover Knob.

OPTIONAL SPECIFICATION (USING THE T991B):

Alternate proportional control similar to the T921A, but

uses an outdoor temperature, automatic control point
reset.

T991B with 3-1/2: 1 reset and 50

°

 to 120

°

 F [10

°

 to

49

°

C] temperature setting scale (when the outdoor

bulb is at 60

°

 F [16

°

 C]).

DIMENSIONS:

Refer to Fig. 2.

ACCESSORIES:

Compression fittings, immersion wells: Refer to the

appropriate specification or the TRADELINE

®

 Cata-

log.

314439 Mounting Clips: For mounting a capillary tub-

ing (averaging element) in a duct.

1

1

2

2

3

3

M9108

4     

 [106]

3

16

    [10] 

DIAMETER

3
8

5     

[143]

5
8

 [24]

1
4

1   

  [32]

1
8

2     [57]

1
4

4     [108]

1
4

2     [57]

7

32

      [6] 

DIAMETER (3)

3
4

1    

 [45]

OUTDOOR BULB SIZE VARIES INVERSELY WITH THE RESET RATIO.

INDOOR BULB LENGTH AND DIAMETER IS 4-1/2 [114] INCH BY 
1/2 [13] INCH EXCEPT FOR THE AVERAGING ELEMENT WHICH IS 
1/8 [3] INCH DIAMETER BY 12 FT. [3 M] LONG.

CLEARANCE NECESSARY TO REMOVE COVER.

15
16

 [24]

15
16

 [10]

3
8

2  [51]

KNOCKOUT FOR 1/2 INCH
CONDUIT (BOTH ENDS)

Summary of Contents for T921A

Page 1: ...ls COOL HEAT changeover switch in the T921B Night setback mechanism and switch in the T921E A spdt single pole double throw Class 2 auxiliary switch in the T921F G which operates at the low T921F and high T921G end of the throttling range A bellows element adjusts the potentiometer slider to regulate motor operation Various temperature ranges are available All models are available with a thermomet...

Page 2: ... also include the 127246A Adapter Plate As sembly for vertical mounting on a horizontal conduit box or for horizontal mounting on a vertical conduit box STANDARD MODEL MODELS T921A Heating or cooling applications T921B Is the same as the T921A but includes a cool heat changeover switch T921E Includes a switch and heater that provide a night setback of approximately 10 F 5 5 C T921F Includes an spd...

Page 3: ...35B 42 to 75 F 5 to 24 C 135135C 66 to 95 F 19 to 35 C 135135D 56 to 84 F 13 to 29 C 135135Ca a Blank faceplate REPLACEMENT PART 130224 Locking Cover Knob OPTIONAL SPECIFICATION USING THE T991B Alternate proportional control similar to the T921A but uses an outdoor temperature automatic control point reset T991B with 3 1 2 1 reset and 50 to 120 F 10 to 49 C temperature setting scale when the outdo...

Page 4: ...nduit box with the two screws provided Then fasten the backplate to the adapter plate 6 Make all electrical connections to the terminals on the back of the thermostat before mounting the instrument on the backplate Refer to the Wiring section 7 Mountthethermostatonthebackplatewiththemount ing screws 8 After performing the checkout tests replace the ther mostat cover and tighten the locking screw A...

Page 5: ...tat before mounting the instrument onto the conduit box Terminal locations for all models are shown in Fig 5 Note the difference in terminal designa tions for the auxiliary switch on the T921F and G The H Heater terminal on the T921E is a black leadwire Typical wiring diagrams are shown in Figs 6 through 10 Wire the T921 color to color when the modulating motor must drive the valve or damper open ...

Page 6: ...L IS A BLACK LEADWIRE T R W B T B W R H 2 2 TRANSFORMER Fig 8 Typical wiring diagram for T921E L1 HOT L2 1 1 SERIES 90 MODULATING MOTOR T921B M5992 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED INTERCHANGE B AND W CONNECTIONS TO REVERSE DIRECTION OF MOTOR TRAVEL T R W B T B W R 2 2 TRANSFORMER B W SUMMER COOL WINTER HEAT Setting andAdjusting TEMPERATURE SETTING Adjust a...

Page 7: ...CATOR LOCK SCREW BELLOWS SETTING ADJUSTMENT KNOB POTENTIOMETER WIPER 1 1 SUMMER WINTER COOL HEAT CHANGEOVER SWITCH ON T921B ONLY NIGHT SETBACK SWITCH ON T921E ONLY M9039 80 70 60 In the T921 a vapor filled bellows moves the potenti ometer wiper by expanding or contracting in proportion to temperature changes As the wiper moves the appropriate motor winding is energized opening or closing the valve...

Page 8: ...ng applica tion Raise the setpoint gradually the auxiliary switch should make R W before the setting indicator reaches room temperature As the setting indicator moves above room temperature the valve or damper should open 4 If the valve or damper responds properly to the thermostat move the setpoint to the desired temperature M5991 2 5 F 1 5 C SETPOINT TEMPER ATURE 2 5 F 1 5 C R B MAKES TEMPERATUR...

Reviews: