Honeywell T87F Series Product Data Download Page 8

T87F THERMOSTATS

60-2222—3    G.H.  Rev. 8-02 

www.honeywell.com/yourhome

Automation and Control Solutions

Honeywell

Honeywell Limited-Honeywell Limitée

1985 Douglas Drive North

35 Dynamic Drive

Golden Valley, MN  55422

Scarborough, Ontario
M1V 4Z9

Printed in U.S.A. on recycled 
paper containing at least 10% 
post-consumer paper fibers.

IMPORTANT

When the T87F is used in a series 20 heating circuit 

(requires contact on both a rise and fall in tempera-

ture), set the anticipator indicator to 1.2.

If the current rating is not known, proceed as follows:

1.

Connect an ac ammeter of appropriate range (for exam-

ple; 0 to 2A) between the R and W terminals on the 

wallplate, or between R and W on the subbase.

2.

Let the system operate through the ammeter for at least 

one minute before taking the reading.

3.

Set the heat anticipator to correspond to the ammeter 

reading (see Fig. 15).

4.

A slightly higher setting to obtain longer burner-on times 

(and fewer cycles per hour) may be desirable in sys-

tems such as a one-pipe steam system. For example: 

• if burner on-time is too short with a heater setting of 

0.4, adjust to the 0.45 setting and check the system 

operation, then

• adjust to the 0.5 setting and recheck until the desired 

burner-on time is obtained.

OPERATION

CAUTION

Equipment Damage Hazard.

Improper installation can burn out thermostat heat 

anticipator.

On systems using a low voltage gas valve, 

do not 

apply a jumper across the valve coil terminals.

To check thermostat operation:

1.

Turn down the temperature setting to the lowest point. 

2.

If the subbase is used, move the system switch to the 

HEAT position. 

3.

Raise the temperature setting until the burner starts. 

4.

Slowly turn the dial back. (The burner should stop when 

the dial has been turned down below the room tempera-

ture.) 

5.

If the T87F controls cooling, move the subbase system 

switch (if used) to COOL and lower the setting until the 

cooling equipment starts.

6.

Raise the setting above the room temperature and the 

cooling system should shut down.

7.

Make certain that the equipment functions properly in 

response to the thermostat.

RECALIBRATION

IMPORTANT

— If the thermostat scaleplate moves (pointer is station-

ary) when setting the temperature, the thermostat is 

a Group I model.

— If the scaleplate is stationary and the pointer moves, 

the thermostat is a Group II model.

The T87F is accurately calibrated at the factory under 

controlled conditions and no recalibration should be 

necessary. If it appears that the thermostat is out of 

calibration, make sure that it is level and is not subjected to 

radiant heat from the sun, radiators, or appliances.

Remove the thermostat cover ring so you can observe the 

mercury switch action. After a five- or ten-minute off-period 

(with thermostat setting below the room temperature), slowly 

raise the setting until the switch just makes contact. If the 

thermometer pointer and setting indicator read the same the 

instant you see the switch make, no recalibration is 

necessary. If recalibration is necessary, proceed as follows:

1.

Turn the setting dial a few degrees above the room tem-

perature and remove the cover.

2.

Slip the 104994 Calibration Wrench (available on 

request) onto the hex under the bimetal coil (see Fig. 

14).

3.

Hold the dial firmly, and turn the hex counterclockwise 

for Group I models and clockwise for Group II models, 

until the mercury breaks contact.

4.

Turn the dial to a low setting so that the thermostat 

loses the heat it has gained from your hands and its 

own operation.

5.

Wait at least five minutes.

6.

Slowly turn the dial until the pointers read the same.

7.

Firmly hold the dial—carefully turning the hex clockwise 

for Group I models, counterclockwise for Group II mod-

els—until the mercury switch slips to the heating contact 

end of the tube.

8.

Recheck the calibration, select the desired temperature 

and replace the cover.

NOTE: When the T87F provides cooling control, calibration 

for heating automatically calibrates for cooling.

Summary of Contents for T87F Series

Page 1: ...es cooling anticipation The Q539 Subbase may be added for system and fan switching The Q539 Subbase also provides cooling anticipation FEATURES For 24 Vac to 30 Vac control of heating or cooling systems Thermostat cover ring may be painted to match room decor Knurled dial provides easy setpoint adjustment Separate temperature setting and thermometer scale located on face of thermostat T87F distinc...

Page 2: ...wire spst heating or cooling 3 wire spdt heating cooling or 3 wire spdt series 20 heating systems Additional Tradeline Features Cover ring included for covering old thermostat marks or for mounting T87F on outlet box 137421 Wallplate extends beyond thermostat for trim appear ance 198170A Wallplate for Designer Models Tradeline pack with cross reference label and special instruction sheet Standard ...

Page 3: ...2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service techni cian 4 After installation is complete check out product opera tion as provided in these instructions Location Locate the thermostat about 5 ft 1 5m above the floor in an area with good air circulation at average temperat...

Page 4: ...ms represent typical applications SPIRIT LEVEL LEVELING POSTS 2 MOUNTING SLOTS SPIRIT LEVEL 104456B WALLPLATE 137421A B D WALLPLATE MOUNTING SLOTS BE SURE WALL HOLE IS PLUGGED MOUNTING SLOTS TERMINAL SCREWS M20772 OPENING FOR THERMOSTAT WIRING T87F THERMOSTAT COVER RING M20773 THERMOSTAT COVER RING MOUNTING SLOTS 4 THERMOSTAT CABLE OPENING 104456B WALLPLATE OUTLET BOX 127293 COVER RING Q539 SUBBAS...

Page 5: ...E COOLING ANTICIPATOR TO SYSTEM CONNECTIONS COOLING ONLY THERMOSTAT MODEL WITH POSITIVE OFF SWITCH OPENS THE THERMOSTAT CIRCUIT WHEN SETPOINT DIAL IS MOVED TO THE OFF POSITION MAKE SYSTEM WIRING CONNECTIONS TO TERMINALS ON 137421D WALLPLATE R1 W1 TERMINALS ON THERMOSTAT ARE DIRECTLY CONNECTED TO R Y TERMINALS ON WALLPLATE WHEN THERMOSTAT IS MOUNTED ON WALLPLATE M20775 TEMPERATURE FALL ADJUSTABLE H...

Page 6: ...ust be used A three wire open contact high limit control requires a jumper as shown in Fig 12 Fig 11 T87F replacing a series 10 thermostat connected to a 2 or 3 wire low limit control L2 COMBINATION FAN AND LIMIT CONTROL FAN MOTOR BURNER MOTOR THERMOSTAT Y R W CAD CELL 1 2 3 R8184G WHITE ORANGE BLACK IGNITION OIL VALVE POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED R8184...

Page 7: ...Adjustment The thermostat has an adjustable heat anticipator that must be set on the number that corresponds to the current rating of the primary control of the system for example gas valve oil primary Fig 14 T87F interior detail Fig 15 Adjust heat anticipator to match current rating of primary control Series 20 Thermostat T87F Thermostat R R B W W Y LOW LIMIT OPERATING CONTROL T87F SERIES 10 OPEN...

Page 8: ...tting until the cooling equipment starts 6 Raise the setting above the room temperature and the cooling system should shut down 7 Make certain that the equipment functions properly in response to the thermostat RECALIBRATION IMPORTANT If the thermostat scaleplate moves pointer is station ary when setting the temperature the thermostat is a Group I model If the scaleplate is stationary and the poin...

Reviews: