T8524 DELUXE ELECTRONIC THERMOSTAT
68-0202
8
Table 4. Thermostat Installer Setup Options (continued).
IMPORTANT
Review the settings to confirm that they match the
system.
INSTALLER SYSTEM TEST
Use the Installer System Test to check the thermostat
configurations and operation. Refer to Table 5 for a list of the
available system tests.
To start the system test:
NOTE:
The minimum off time for compressors is bypassed
during the Installer System Test.
Fig. 10. All the segments of the LCD displayed.
Em HeatOffCool Auto Only
Heat Cool
OnAuto
System
Fan
Room
Outdoor
Em Ht Temporary Setting
Wait
%Humid
Aux Ht
Remote
Repl
Batt
M4844
Fig. 11. Test number displayed.
Refer to Table 6 for the directions and results of the specific
tests.
NOTE:
Press and hold the increase
▲
and decrease
▼
keys
together for three seconds to exit the system test.
The system test will time out after five minutes
without any key presses.
Press and hold the increase
▲
and decrease
▼
keys at the
same time until two zeros appear. All segments of the display
will be displayed before the two zeros appear. See Fig. 10
and 11.
Installer Setup
Number (Press
Time
▲
key to
Factory-Setting
Other Choices
(Press
▲
or
▼
key to change)
Actual
Select
change)
Display
Description
Display
Description
Setting
Temperature range
stops in cooling
35
45
Lowest setpoint
cooling can be set to
46 to 99
Temperature range (1°F
increments) cooling setpoint
can be set to
Not used
36
—
—
—
—
—
Temperature
display adjustment
37
0
No difference in
displayed temperature
and actual room
temperature
+3 thru
-3
1—Display adjusts to 1°F
higher than actual room
temperature
2—Display adjusts to 2°F
higher than actual room
temperature
3—Display adjusts to 3°F
higher than actual room
temperature
-1—Display adjusts to 1°F
lower than actual room
temperature
-2—Display adjusts to 2°F
lower than actual room
temperature
-3—Display adjusts to 3°F
lower than actual room
temperature
M6792A
TEST NUMBER