Honeywell T8524 Product Data Download Page 13

T8524 DELUXE ELECTRONIC THERMOSTAT

68-0202

13

Symptom

Possible Cause

Action

Temperature settings will
not change. (Example:
Cannot set the heating

The upper or lower
temperature limits were
reached.  

Check the temperature setpoints:

Heating limits are 45°F to 88°F (7°C to 31°C)

Cooling limits are 48°F to 99°F (9°C to 37°C).

higher or the cooling lower.) The setpoint

temperature range
stops were configured.

Check Installer Setup numbers 34 and 35 and reconfigure the setpoint
stops.

Heating will not come on.

No power to the
thermostat.

Check that C terminal is connected to the system transformer.

Check for 24 Vac between C and R or RH terminals.

If missing 24 Vac:

check if the circuit breaker is tripped—reset the circuit 
breaker.

check if the system fuse is blown—replace the fuse.

check if the system switch at the equipment is in the Off 
position—set to On position.

check wiring between thermostat and HVAC equipment—
replace any broken wires and tighten any loose 
connections.

If 24 Vac is present, proceed with troubleshooting.

System selection is not
set to Heat.

Set system selection to Heat.

Cooling will not come on.

No power to the
thermostat.

Check that C terminal is connected to the system transformer.

Check for 24 Vac between C and R or RC and Y terminals.

If missing 24 Vac:

check if the circuit breaker is tripped—reset the circuit
breaker.

check if the system fuse is blown—replace the fuse.  

check if the system switch at the equipment is in the Off
position—set to the On position.

check wiring between thermostat and HVAC equipment—
replace any broken wires and tighten any loose connections.

If 24 Vac is present, proceed with troubleshooting.

Thermostat minimum off
time is activated.

Wait up to five minutes for the system to respond.

Enter Installer Setup mode number 33. Reconfigure minimum off
time (if required).

System selection is not
set to Cool.

Set system selection to Cool.

System On indicator is lit,
but no heat is being
delivered.

Heating equipment is
not operating.

Verify operation of heating equipment in system test.

Outdoor temperature  
not displayed

 

(select

models)

Option not activated.

Enter Installer Setup number 24 and set to 1. Thermostat must have
OT terminals and a C7089B1000 installed.

Outdoor temperature  

Outdoor sensor is
connected incorrectly.

Refer to C7089B1000 installation instructions and check wiring
between the thermostat and sensor.

Display is incorrect

 

(select

models)

Wrong sensor.

Replace sensor with C7089B1000 sensor.

Summary of Contents for T8524

Page 1: ...figurable features allows one model to be used to replace many different models less inventory no need to carry separate models to get these features F or C temperature display automatic or manual changeover electric or conventional heat fan operation adjustable heating cycle rate Minimum off time for cooling compressors and heat pumps protects and extends the life of the equipment Easy installati...

Page 2: ... individual unit may not exactly match the listed specifications Also This product is tested and calibrated under closely controlled conditions and some minor differences in performance can be expected if those conditions are changed Models See Table 1 Electrical Rating Input Power 18 to 30 Vac 50 60 Hz Load Rating See Table 2 Temperature Setpoint Range 40 F to 99 F 4 C to 37 C depending on model ...

Page 3: ...uctions can damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to checkout the product operation CAUTION Disconnect power supply to prevent electrical shock or eq...

Page 4: ...Fig 13 through 18 for typical hookups A letter code is located near each terminal for identification Refer to Table 3 for terminal designations Table 3 Terminal Designations and Descriptions a Some OEM models label the terminal for transformer common B Standard Terminal Designations Alternate Terminal Designations Typical Connection Function Terminal Type B Heating damper or changeover valve Outpu...

Page 5: ...at Fig 4 Proper wiring technique Mounting Thermostat 1 Engage tabs at the top of thermostat and wallplate Fig 5 2 Press lower edge of case to latch NOTE To remove the thermostat from the wall first pull out at the bottom of the thermostat remove top last M6798A B PRESS LOWER EDGE OF CASE TO LATCH A ENGAGE TABS AT TOP OF THERMOSTAT AND WALLPLATE Fig 5 Mounting thermostat on wallplate Using Thermost...

Page 6: ...ss and hold the Information i key with the increase and decrease keys until the first number is displayed All display segments appear for approximately three seconds before the number is displayed See Fig 8 and 9 To advance to the next Installer Setup press the Information i key To change a setting use the increase and decrease keys To exit the Installer Setup press and hold the Information i key ...

Page 7: ...ends 1 Fan operation is extended 90 seconds after the call for heat ends Extended fan operation in cooling 20 0 No extended fan operation after the call for cool ends 1 Fan operation is extended 90 seconds after the call for cool ends Not used 21 thru 23 Outdoor temperature display models with OT terminals 24 0 No outdoor temperature is displayed 1 Outdoor temperature is displayed Needs a C7089B10...

Page 8: ...out after five minutes without any key presses Press and hold the increase and decrease keys at the same time until two zeros appear All segments of the display will be displayed before the two zeros appear See Fig 10 and 11 Installer Setup Number Press Time key to Factory Setting Other Choices Press or key to change Actual Select change Display Description Display Description Setting Temperature ...

Page 9: ...equipment system test 41 Fan comes on 40 Fan turns off Key or Switch Operation System Test SYSTEM KEY SYSTEM TEST i 60 Change from cooling or fan to key operation system test System 61 Heat test number is displayed System 62 Off test number is displayed System 63 Cool test number is displayed System 64 Auto test number is displayed FAN KEY SYSTEM TEST Fan 68 Fan on test number is displayed Fan 69 ...

Page 10: ...is displayed to exit the system test The system test times out after five minutes without any key presses CHECKOUT Outdoor Temperature Sensor where applicable Allow the outdoor temperature sensor to soak in the outdoor air for a minimum of five minutes before taking a reading With an accurate thermometer 1 F 0 5 C measure the temperature at the sensor location allowing time for the thermometer to ...

Page 11: ...gral error which is a deviation based on the length of error time The sum of the two errors is the P I error The cycle rate used to reach and maintain the setpoint temperature in computed using the P I The addition of the integral error is what differentiates the thermostat from many other electronic and electromechanical thermostats See Fig 13 Operation Sequence The thermostat energizes specific ...

Page 12: ...how the outdoor temperature if installer setup number 24 is set to 1 W2 L1 HOT L2 M11309 FAN RELAY Y1 G C THERMOSTAT RC HEAT RELAY 1 R W1 L1 HOT L2 COMPRESSOR CONTACTOR 1 Y2 COMPRESSOR CONTACTOR 2 HEATING TRANSFORMER COOLING TRANSFORMER HEAT RELAY 2 OT OT B HEAT DAMPER OUTDOOR SENSOR COOL DAMPER O 2 2 3 3 3 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED JUMPER RC TERMI...

Page 13: ...o the thermostat Check that C terminal is connected to the system transformer Check for 24 Vac between C and R or RC and Y terminals If missing 24 Vac check if the circuit breaker is tripped reset the circuit breaker check if the system fuse is blown replace the fuse check if the system switch at the equipment is in the Off position set to the On position check wiring between thermostat and HVAC e...

Page 14: ...T8524 DELUXE ELECTRONIC THERMOSTAT 68 0202 14 ...

Page 15: ...T8524 DELUXE ELECTRONIC THERMOSTAT 68 0202 15 ...

Page 16: ...trol Honeywell Limited Honeywell Limitée 155 Gordon Baker Road North York Ontario M2H 3N7 Honeywell Latin American Division Miami Lakes Headquarters 14505 Commerce Way Suite 500 Miami Lakes FL 33016 68 0202 J H 12 97 Printed in U S A Home and Building Control Honeywell Inc Honeywell Plaza P O Box 524 Minneapolis MN 55408 0524 Printed on recycled paper containing at least 10 post consumer paper fib...

Reviews: