background image

3. PROGRAMMING OUTPUTS (MOD AND RELAY) WITH RESET

T775U SERIES 2000 CONTROLLER 

31

62-0255–05

Fig. 72. Program - Action Selection.

3.2.6. ACTION

For the MOD 1 output (and for outputs with RESET=NO), 
the ACTION selection displays.

For all other outputs with RESET=YES, the ACTION 
selection does 

not

 display; continue with “3.2.7. 

SETBACK OFFSET (if configured)” on page 31.

1.

From the menu, use the 

S

 and 

T

 buttons to high-

light ACTION.

Default: HEAT

2.

Press the 

X

 button to display the action selections.

3.

Use the 

S

 and 

T

 buttons to select the desired 

value.

4.

Press the 

X

 button to accept the highlighted selec-

tion and display the next option. 

Fig. 73. Program - Setback (Offset).

3.2.7. SETBACK OFFSET 

(if configured)

The Setback temperature option displays only if 
scheduling is enabled (see Fig. 47 on page 21) or the DI 
Option is set to Setback. (see Fig. 49 on page 22).

This value is the number of degrees plus (+) or minus (-) 
that you want the temperature to be offset from the 
setpoint. 

For example, If you want the temperature to be 10°F less 
than the setpoint during setback mode, enter -10°F. In 
normal operations for heating, the offset will be negative. 
For cooling, the offset will be a positive value.

1.

From the menu, use the 

S

 and 

T

 buttons to high-

light SETBACK.

2.

Use the 

S

 and 

T

 buttons to increase/decrease the 

desired setpoint temperature.

Default: 0°F
Range: -150°F to 150°F (-101°C to 66°C)

3.

Press the 

X

 button to accept the value and display 

the menu.

This completes the programming of the MOD 1 output.
To program the second Modulating output and the two 
relays, continue with “3.3. Second Modulating Output and 
Relays”.

PROGRAM
 RELAY 

1

 ACTION

MENU

PROGRAM

RELAY 1

ACTION

SELECT

ACTION

FOR 

RELAY 1

HEAT

COOL

REV ACT

DIR ACT

HUMID

DEHUMID

M24578

PROGRAM
 RELAY 

1

 

SETBACK

MENU

PROGRAM

RELAY 1

SETBACK

-10

F

ENTER

SETBACK

SETPOINT

FOR RELAY 1

M24579

Summary of Contents for T775U2006

Page 1: ...ng safety or limit controls a separate safety or limit control device is required Table 1 T775U Controller Configurations Controller Modela a The T775U includes a digital input for use with the disable or setback option Description Replaces Output Reset SPDT Relay Outputs Analog Mod Outputsb b The modulating analog outputs may be 4 20 mA 0 10 Vdc 2 10 Vdc or Series 90 selectable Sensor Inputs Nbr ...

Page 2: ...rs and is settable in PPM units Universal Sensors Sensor A only The controller accepts 0 5 Vdc 0 10 Vdc or 4 20 mA input for temperature pressure humidity CO2 etc They may be programmed in units of F C Pa kPa PSI In W C PPM or may be unitless none The PPM range is 0 to 9990 Choosing none for units results in no units being displayed on the home screen If no unit is specified the range is 9999 to 9...

Page 3: ...erface and Programming overview see page 11 5 Setup see page 13 6 Programming the Controller with no Reset see page 25 or Programming the Controller with Reset page 28 7 Scheduling optional see page 33 Additional topics are Sensor calibration begins on page 10 Interface overview begins on page 11 Summary menu begins on page 37 Troubleshooting begins on page 37 MOUNTING This section describes the m...

Page 4: ...l series wired to sense average temperatures in large spaces See Fig 3 on page 5 WIRING All wiring must comply with applicable electrical codes and ordinances or as specified on installation wiring diagrams Controller wiring is terminated to the screw terminal blocks located inside the device The remainder of this section describes the sensor wiring and the T775U controller wiring Wiring Connectio...

Page 5: ... as a temperature input Sensors use standard AWG 18 unshielded wire For cable runs greater than 25 feet shielded cable is recommended The sensors in Fig 5 8 beginning on page 6 are examples and illustrate voltage and current wiring for 3 wire and 2 wire sensors to the Sensor A terminal For terminal wiring details see Fig 11 and Table 2 on page 8 Other sensors are supported See sensor descriptions ...

Page 6: ...SOR 0 10 VDC CONNECTION SENSOR A 1 SENSOR B C S V T T VO GND VIN C S V SHIELDED CABLE M24890A V S NOTES 1 SHIELDED CABLE MUST BE CONNECTED TO A SEPARATE EARTH GROUND HOWEVER DO NOT GROUND SHIELDED CABLE AT SENSOR END 2 TO MINIMIZE NOISE PICKUP MAKE SENSOR CONNECTION FROM SHIELDED CABLE AS CLOSE AS POSSIBLE TO SENSOR BODY 3 THE T775 HAS AN INTEGRAL LOAD OF 500 OHMS WHICH RESULTS IN A 10V DROP AT 20...

Page 7: ...ltage wiring Knockouts C D and E can be used to gain access to the load relay output terminals and 120 240 Vac power wiring Controller Wiring Method Wire the sensors and outputs then wire the power connection Each terminal can accommodate the following gauges of wire Single wire from 14 AWG to 22 AWG solid or stranded Multiple wires up to two 22 AWG stranded For 24 120 or 240 Vac power connections...

Page 8: ...scription of Wiring Terminal Connections Connection Terminal Label Description Connection Terminal Label Description Sensors Outputs Sensor Aa a For applications that do not use Reset only Sensor A is available for use C common S signal V voltage 0 10 Vdc input Universal sensor for humidity pressure temperature etc Mod 1 Vdc or mA W R B Series 90 b b For Series 90 connections you must insert a 340...

Page 9: ...oad Fig 15 Wiring for Digital Input dry contact Fig 16 Wiring for mod motor or direct coupled actuator with 0 10 Vdc control input L1 HOT L2 24 VAC COM NO COM NO M24554A C S V T T LOAD 2 LOAD 1 C NO NC C NO NC C FOR SPECIFIC SENSOR WIRING TEMPERATURE HUMIDITY PRESSURE ETC REFER TO THE SENSOR WIRING SECTIONS BEGINNING ON PAGE 4 1 1 USE SEPARATE TRANSFORMER FOR T775 WHEN USING 24 VAC 1 M24557A MODUL...

Page 10: ...e amount shown in the Table 4 on page 11 For example a wire run with 18 gauge wire of 1 000 feet requires a calibration offset of 6 0 F IMPORTANT If the calibration value in the table exceeds the controller s calibration limits of 10 F 6 C you must use a heavier gauge wire For example with a wire run of 1 000 feet you must use 20 AWG wire or heavier in order to cal ibrate for wire loss within the ...

Page 11: ...h the menus and enter or change parameter values Home Button Pressing the HOME button at any time exits the current Programming or Setup display screen and returns to the home screen as shown in Fig 20 and Fig 21 Menu Button Pressing the MENU button always displays the Program menu If you are in Setup mode you exit setup and return to the Program menu Pressing and holding the MENU button for five ...

Page 12: ...screen displays the effective setpoint IMPORTANT After four minutes of inactivity no buttons pressed the LCD display reverts to the home screen display Accessing the Menus Menus are used for programming scheduling viewing the summary settings and setup of advanced options Program Schedule and Summary Menus To access these menus from the home screen press the MENU button See Fig 22 Fig 22 Menus Dep...

Page 13: ... energizes Setpoint High Limit You can set an irreversible setpoint high limit maximum value for any single displayed setpoint value Adjust the setpoint at any output to the desired maximum setpoint Then simultaneously press the HOME W and X buttons and continue to press all three buttons for five seconds to set the setpoint high limit maximum to this value NOTE You must press all three buttons at...

Page 14: ...he value entered here determines the number of sensors displayed on the home screen NOTE For applications that do not use Reset only one sensor Sensor A is available for use 1 From the Sensors menu highlight SENSORS then press the X button to display the number of sensors 2 Use the S and T buttons to enter the number of sensors 1 or 2 Default 2 3 Press the X button to accept the value and display ...

Page 15: ...m the Sensor A selections use the S and T buttons to highlight UNITS 2 Press the X button to display the temperature units 3 Use the S and T buttons to highlight F or C Default F Fahrenheit 4 Press the X button to accept the units and return to the Sensor A selections Continue with 1 2 2 3 CALIBRATE Sensor A or B Fig 29 Setup Sensors Sensor A Units 1 2 2 2 2 UNITS Sensor A only 0 5V 0 10V or 4 20m...

Page 16: ... the S and T buttons to increase decrease the desired calibration value Default 0 0 Sensor Range Temperature 10 F 6 C Other Sensor Range 10 of the Min to Max values specified previously See Table 3 on page 10 for examples 4 Press the X button to accept the value and return to the Sensor A selections Fig 32 Setup Sensors Sensor A Label 1 2 2 4 LABEL Sensor A or B input For a sensor already labeled ...

Page 17: ... 1 2 2 4 LABEL Sensor A or B input beginning on page 14 but perform only those steps applicable to Sensor B 4 Press the W button to exit SENSOR B and return to the Sensors menu or Use the S and T buttons to highlight EXIT and press the X button 5 Press the W button to exit the Sensors menu and return to the Setup menu Continue with 1 3 Setting up the Outputs Fig 35 Setup Outputs Menu 1 3 Setting u...

Page 18: ...g the time clock or digital input to disable the output forces the output to 0 1 From the Mod menu use the S and T buttons to highlight MIN OUT 2 Press the X button to display the Min Out 3 Use the S and T buttons to increase decrease the desired value from 0 to 100 in 1 increments Default 0 Range 0 to 100 4 Press the X button to accept the percentage and return to the Mod menu Fig 39 Setup Output...

Page 19: ...o a setpoint even with a wide throttling range Fig 40 Setup Outputs Mod Out Derivative 1 3 1 4 DERIVATIVE The Derivative default value is factory set to zero no derivative control It is strongly recommended that the derivative remain at zero 0 unless you have a very good reason to adjust it Derivative control is not needed in the vast majority of HVAC applications 1 From the Mod menu use the S and...

Page 20: ...ide 1 3 1 7 Hide The Hide option is used to prevent the MOD 1 and MOD 2 outputs from displaying on the Home screen 1 From the Mod menu use the S and T buttons to highlight HIDE 2 Use the S and T buttons to highlight YES or NO Default YES 3 Press the X button to accept the selection and return to the MOD menu NOTE The MOD1 and MOD2 outputs are still active even when hidden from the Home screen Fig ...

Page 21: ...play the schedule selections 2 Use the Sand T buttons to highlight YES or NO Default NO 3 Press the X button to accept the value and display the MIN OFF option Selecting NO disables scheduling for all outputs Selecting YES enables scheduling for all outputs When YES is selected all individual outputs default to follow the schedule However each individual output can be removed from scheduling as de...

Page 22: ...nt Setback values entered in the Schedule 1 Press the X button to display the DI Option selec tions 2 Use the S and T buttons to highlight DISABLE SETBACK or IGNORE Default DISABLE 3 Press the X button to accept the value and display the SHOW RT option When the digital input DI closes all outputs follow the DI option value Disable Setback or Ignore DISABLE disables the outputs relays return to de ...

Page 23: ...and T buttons to highlight the desired relay 1 or 2 2 Press the X button to display the selected Relay menu Continue with the remainder of this section to setup the relay outputs Fig 53 Setup Outputs Relay Schedule 1 3 4 1 SCHEDULE This selection displays only if Use Sched YES is selected during the Output Options setup see page 21 When selected individual outputs default to follow the schedule 1 ...

Page 24: ...to select YES or NO Default NO 3 Press the X button to accept the value and return to the Relay menu Selecting YES immediately resets the output run time hours to zero for this output When you subsequently return to this screen the RESET RT defaults to NO NOTE Run times can be reset to zero for each individ ual relay You must do this for each relay that you want to reset to zero Fig 56 Setup Outpu...

Page 25: ...s the screens for selecting MOD 1 but other than as noted below the programming is the same for each output NOTE For Relays DIFFRNTL replaces THROT RNG NOTE The Setback parameter displays only if schedul ing is enabled see Fig 47 on page 21 or the DI Option is set to Setback see Fig 49 on page 22 Continue with 2 1 2 SETPOINT Fig 59 Program Setpoint 2 1 2 SETPOINT 1 From the menu use the S and T bu...

Page 26: ...r DIFFERENTIAL Throttling Range displays for Modulating outputs Differential is used for the Relay outputs 1 From the menu use the S and T buttons to high light THROT RNG or DIFFERNTL 2 Press the X button to display the throttling range value 3 Use the S and T buttons to increase decrease the desired value Default 20 F 6 6 C Range 1 F to 150 F 1 C to 66 C 4 Press the X button to accept the value a...

Page 27: ...2 Program Next Output Modulating Output or Relay For the next output select the desired MOD or Relay from the Program menu see Fig 57 on page 25 Go to 2 1 2 SETPOINT on page 25 to continue programming When you finish programming the outputs continue with 1 3 Exit Programming without Reset 1 3 Exit Programming without Reset Press the HOME button to leave programming mode and return to the home scre...

Page 28: ...t be sensing the controlled temperature e g Boiler Sensor B must be sensing the resetting temperature e g outdoor temp To program an output for Reset refer to the values as shown in the examples below Choose your own appropriate values for Sensor A maximum and minimum and Sensor B maximum and minimum Reset Example see Fig 65 Sensor A is the boiler sensor and Sensor B is the outdoor sensor Maximum ...

Page 29: ...X or SP MAX A1 2 Press the X button to display the maximum setpoint value 3 Use the S and T buttons to increase decrease the desired maximum setpoint temperature Default 180 F 82 C Range 40 F to 248 F 40 C to 120 C 4 Press the X button to accept the setpoint tempera ture and display the next option Fig 68 Program Sensor B Max Setpoint 3 2 2 RESET B1 or OUTSD MIN Sensor B value when at SP MAX A1 Se...

Page 30: ...odulating outputs Differential is used for the Relay outputs 1 From the menu use the S and T buttons to high light THROT RNG or DIFFERNTL 2 Press the X button to display the throttling range value 3 Use the S and T buttons to increase decrease the desired value Default 20 F 6 6 C Range 1 F to 150 F 1 C to 66 C 4 Press the X button to accept the value and display the next option The Throttling Rang...

Page 31: ...t to Setback see Fig 49 on page 22 This value is the number of degrees plus or minus that you want the temperature to be offset from the setpoint For example If you want the temperature to be 10 F less than the setpoint during setback mode enter 10 F In normal operations for heating the offset will be negative For cooling the offset will be a positive value 1 From the menu use the S and T buttons ...

Page 32: ...ed temperature OFFSET Default 0 F OFFSET Range 150 F to 150 F 101 C to 66 C 4 Press the X button to accept the value and display the next option 3 3 2 Second Modulating Output and Relays Programming To complete the programming of MOD 2 or a Relay perform the procedures in 3 2 5 THROTTLING RANGE or DIFFERENTIAL through 3 2 7 SETBACK OFFSET if configured beginning on page 30 3 4 Exit Programming wit...

Page 33: ...he home screen 2 If you press the MENU button you exit Scheduling mode and return to the menu To create or change a schedule you use the Left arrow button W to scroll backward through the Setup menus Right arrow button X to select the highlighted menu item and display its content Up and Down arrow buttons S and T to scroll up and down through a list of items or to increase or decrease the value of...

Page 34: ... S and T buttons to highlight SET DATE 2 Press the X button to display the current system date setting 3 Use the X button to cycle between the month day and year values 4 Use the S and T buttons to increase decrease the desired value for the month day and year 5 Press the W button to accept the Date and return to the Options menu Fig 80 Schedule Options Daylight Saving Time 4 2 3 DAYLIGHT daylight...

Page 35: ...SETPT setpoint for event 1 The following figures show the MON FRI menu but the menu selections are the same for any time period Fig 82 Schedule Event 1 Setpoint 4 3 1 E1 SETPT setpoint for event 1 1 From the selected time period menu use the S and T buttons to highlight E1 SETPT 2 Press the X button to display the setpoint options 3 Use the S and T buttons to highlight the desired option 4 Press t...

Page 36: ...bove 4 3 4 E2 TIME time for event 2 Creating the time for event 2 is accomplished the same way as the first event See 4 3 2 E1 TIME time for event 1 above 4 3 5 EXIT exit from selected time period settings After entering the time for event 2 use the W button to exit the schedule time period and return to the Schedule menu to select a different time period When you finish scheduling the time period...

Page 37: ...ame as written into the EEPROM This error cannot be field repaired Replace the device Diagnostic Messages There are two diagnostic messages that can display in response to sensor problems The diagnostic codes that can flash on the display are Sensor Open or Shorted Two dashes display when a sensor typically temperature is open or shorted An open circuit is considered anything greater than 1570 ohm...

Page 38: ...adio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause interference to radio or television equipment reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures Reorient or relocate the receiving antenna M...

Page 39: ...T775U SERIES 2000 CONTROLLER 39 62 0255 05 ...

Page 40: ...ns Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2009 Honeywell International Inc 62 0255 05 M S Rev 02 09 ...

Reviews: