background image

62-0124—3

5

T7300E SERIES 2000 COMMERCIAL MICROELECTRONIC HEAT PUMP THERMOSTAT

Table 2. Thermostat Installer Setup Options (Continued).

(Continued)

Installer

Setup Number

(Press

Unoccupied

Temp key

Factory-Setting

Other Choices  

(Press 

 or 

 key to change)

Actual  

Select

to change)

Display

Description

Display

Description

Setting

Minimum off
times in heating

38

4

4—4 minute minimum
off time

0, 1, 2, 3,
or 5

Minimum number of minutes
(0 thru 5) the heating
equipment will be off
between calls for heat

Not used

39

Installer Setup
lockout (keypad
lockout is
enabled and
disabled by DIP
switch 1 on back
of thermostat)

40

0

0—No Installer Setup

lockout

1

1—Installer Setup lockout

activated

IMPORTANT

Review the settings to confirm that they match
the system. Press Run Program to exit the
Installer Setup. Be sure to set the current day
and time immediately.

Setting Current Day and Time

1. Press Set Current Day/Time.

NOTE:

On initial power up or after an extended
power loss, 1:00 pm flashes on the LCD
until a key is pressed.

M4951B

Set Current

Day/Time

Set Program

Set Temperature

Change

Time/Temp

Occupied

Temp

Unoccupied
Start Time

Day

System

Fan

Copy

Occupied
Start Time

Run

Program

Temporary
Occupied

Continous

Unoccupied

Set Current

Day/Time

Clear

Start Time

Unoccupied

Temp

Heat/Cool

Settings

Mon

PM

Set Day/Time

2. Press Day until the current day is displayed.

NOTE:

Sun=Sunday, Mon=Monday,
Tue=Tuesday, Wed=Wednesday,
Thu=Thursday, Fri=Friday, Sat=Saturday.

M4952B

Set Program

Set Temperature

Change

Time/Temp

Occupied

Temp

Unoccupied
Start Time

Day

System

Fan

Copy

Occupied
Start Time

Run

Program

Temporary
Occupied

Continous

Unoccupied

Set Current

Day/Time

Clear

Start Time

Unoccupied

Temp

Heat/Cool

Settings

Day

PM

Tue

Set Day/Time

3. Press increase 

 or decrease 

 until the current

time is displayed.

NOTE:

Tapping the Set Current Day/Time will
change the time in one hour increments.

M4953B

Set Program

Set Temperature

Change

Time/Temp

Occupied

Temp

Unoccupied
Start Time

Day

System

Fan

Copy

Occupied
Start Time

Run

Program

Temporary
Occupied

Continous

Unoccupied

Set Current

Day/Time

Clear

Start Time

Unoccupied

Temp

Heat/Cool

Settings

PM

Tue

Set Day/Time

4. Press Run Program.

M4954A

Set Program

Set Temperature

Change

Time/Temp

Occupied

Temp

Unoccupied
Start Time

Day

System

Fan

Copy

Occupied
Start Time

Run

Program

Temporary
Occupied

Continous

Unoccupied

Set Current

Day/Time

Clear

Start Time

Unoccupied

Temp

Heat/Cool

Settings

Auto

System

Fan

Mon

Room

AM

Occupied 1

Heat

Run

Program

INSTALLER SYSTEM TEST

Use the Installer SystemTest to check the thermostat
configurations and operation. Refer to Table 3 for a list of
the available system tests.

Table 3. Tests Available in Installer System Test

Test

Number

System Test Description

10 to 19

Heating equipment can be turned on and off

20 to 29

Emergency heat equipment can be turned
on and off

30 to 39

Cooling equipment can be turned on and off

40 to 49

Fan equipment can be turned on and off

60   0 to
60   19

Keyboard keys test

70 to 79

Thermostat information including date code,
software versions and subbase identification  
are displayed

Summary of Contents for T7300E Series

Page 1: ...duct 1 Read these instructions carefully Failure to follow the instructions can damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to check out the product operat...

Page 2: ...ic systems Installer Setup numbers are listed in Table 2 The table includes all the configuration options available A combination of key presses are required to use the Installer Setup feature To enter the Installer Setup mode press and hold the Heat Cool Settings key with both the increase and decrease keys until the first number is displayed All display segments appear for approximately three se...

Page 3: ...e settings to confirm that they match the system Fig 4 Display of Installer Setup number and setting M10238B INSTALLER SETUP NUMBER DISPLAY COLUMN 2 OF TABLE 2 FACTORY SETTING OR OTHER CHOICE DISPLAY COLUMN 3 OR 5 OF TABLE 2 Table 2 Thermostat Installer Setup Options continued Installer Setup Number Press Unoccupied Temp key Factory Setting Other Choices Press or key to change Actual Select to cha...

Page 4: ...sing activated Keypad lockout level keypad lockout is enabled and disabled by DIP switch 1 on back of thermostat 25 0 No lockout 1 2 3 1 Lockout all keys on thermostat except system and fan settings temporary setpoint clock and day adjustments 2 Lockout all keys except set current Day Time increase and decrease keys 3 Lockout all keys except temporary occupied set day and clock keys Duration of te...

Page 5: ...y M4952B Set Program Set Temperature Change Time Temp Occupied Temp Unoccupied Start Time Day System Fan Copy Occupied Start Time Run Program Temporary Occupied Continous Unoccupied Set Current Day Time Clear Start Time Unoccupied Temp Heat Cool Settings Day PM Tue Set Day Time 3 Press increase or decrease until the current time is displayed NOTE Tapping the Set Current Day Time will change the ti...

Page 6: ...ram to exit the system test The system test times out after four minutes without any key presses continued Key to Press Test Number Description Heating Equipment System Test Heat Cool Settings 10 Enter heating equipment system test 11 Stage one heat comes on The system fan is also energized 12 Stage two heat comes on Stage one heat and system fan remain on 13 Stage three heat comes on Stage one an...

Page 7: ...s Test Number Description Key Operation System Test Heat Cool Settings 60 2 Change from fan to key operation system test Unoccupied Temp 60 0 Unoccupied Temp test number is displayed Occupied Temp 60 1 Occupied Temp test number is displayed 60 3 Increase test number is displayed 60 5 Decrease test number is displayed Clear Start Time 60 7 Clear Start Time test number is displayed Day 60 8 Day test...

Page 8: ... Vac check if the circuit breaker is tripped reset the circuit breaker check if the system fuse is blown replace the fuse check if the power switch on the HVAC equipment is in the Off position set to the On position check wiring between thermostat and HVAC equipment replace any broken wires and tighten any loose connections If 24 Vac is present proceed with troubleshooting Temperature display is i...

Page 9: ...s present proceed with troubleshooting Thermostat minimum off time is activated and wait indicator is displayed Wait up to five minutes for the system to respond Enter Installer Setup number 38 Reconfigure minimum off time if required System selection is not set to Heat Set system selection to Heat Cooling will not come on No power to the thermostat Check that X terminal is connected to the system...